Professional Documents
Culture Documents
Abstract: Dynamic Resistance Measurement (DRM) has been used for circuit-breaker
diagnostics for over 20 years. It is an interesting technique that can be used also to verify
the switching operation of load tap changers (LTC). Existing methods and techniques for
dynamic measurements on load tap-changers are based on measuring current and/or
voltage on the primary side of the transformer and short-circuiting the secondary side to
minimize the inductance in the circuit. Static resistance measurements per tap are
performed in a separate test sequence with the secondary side open. A new technique
(patent pending) is to combine current measurement with voltage measurements on both
primary and secondary side of the transformer and then use the transformer parameters
to calculate inductive and resistive voltages to be able to calculate the dynamic
resistance during a tap change. Measurements have been performed on non-mounted
tap-changers (no-oil condition) and after being mounted inside a transformer (with oil).
Different test setups have also been evaluated including the new technique where current
measurement is combined with voltage measurements on both primary and secondary
side of the transformer.
1 INTRODUCTION