"FMG128" --- FACTORY MUTUAL GLOBAL WIND UPLIFT RATINGS

Program Description:

"FMG128" is a spreadsheet program written in MS-Excel for the purpose of determining Factory Mutual Global
(FMG) required roof zone ratings for the three (3) zones of a roof, based on FMG Data Sheet 1-28 (2009/2011).

This program is a workbook consisting of two (2) worksheets, described as follows:

Worksheet Name Description


Doc This documentation sheet
FMG Roof Uplift Ratings Roof Wind Uplift Pressure Ratings per Factory Mutual Global 1-28

Program Assumptions and Limitations:

1. This program is based on the following reference:


Data Sheet 1-28: "Wind Design" - by Factory Mutual Global, 2009 (Revised April 2011)
2. In the "FMG Roof Uplift Ratings" worksheet, the FMG roof Zone 1 (Field Area) Rating is determined as follows:
a. Get Field Area design pressure from either Table 3, 4, or 5 depending on the Exposure, either B, C, or D.
b. Apply multiplier for Zone 1 from Table 6.
c. Apply a Factor of Safety multiplier of 2.
d. Round value up to the next highest 15 psf rating interval to arrive at the FMG Zone 1 (Field Area) Rating.
Note: for Zone 2 (Perimeter) and Zone 3 (Corners)
3. In the "FMG Roof Uplift Ratings" worksheet, the FMG roof Zone 2 (Perimeter) Rating is determined as follows:
a. Get Field Area design pressure from either Table 3, 4, or 5 depending on the Exposure, either B, C, or D.
b. Apply multiplier for Zone 2 from Table 6.
c. Apply a Factor of Safety multiplier of 2.
d. Round value up to the next highest 15 psf rating interval to arrive at the FMG Zone 2 (Perimeter) Rating.
4. In the "FMG Roof Uplift Ratings" worksheet, the FMG roof Zone 3 (Corners) Rating is determined as follows:
a. Get Field Area design pressure from either Table 3, 4, or 5 depending on the Exposure, either B, C, or D.
b. Apply multiplier for Zone 3 from Table 6.
c. Apply a Factor of Safety multiplier of 2.
d. Round value up to the next highest 15 psf rating interval to arrive at the FMG Zone 3 (Corners) Rating.
5. For components and cladding (roof deck, fasteners, and above deck components), FMG 1-28 requires that
the effective area be set = 10 ft.^2 along with an Importance Factor = 1.15.
For secondary supporting members (purlins or joists) per FMG 1-28 Section 2.2.3, refer to applicable
ASCE 7 Standard and apply the appropriate effective tributary area along with an Importance Factor = 1.15.
6. This program contains numerous “comment boxes” which contain a wide variety of information including
explanations of input or output items, equations used, data tables, etc. (Note: presence of a “comment box”
is denoted by a “red triangle” in the upper right-hand corner of a cell. Merely move the mouse pointer to the
desired cell to view the contents of that particular "comment box".)
"FMG128.xls" Program
Version 1.1

ROOF WIND UPLIFT PRESSURE RATINGS


Per Factory Mutual Global (FMG) Data Sheet 1-28: "Wind Design" (2009/2011)
for Roof Deck Securement and Above-Deck Roof Components
Job Name: Subject: Part. Encl.
Job Number: Originator: Checker: B
C
Input Data: D
Gable
Basic Wind Speed, V = 90 mph Monoslope
Enclosed or Part. Encl. = Enclosed
Exposure Category = C
Ridge Height, hr = 62.08 ft. (hr >= he)
Eave Height, he = 60.00 ft. (he <= hr)
Building Dimension, L = 100.00 ft.
Building Dimension, B = 200.00 ft.
Roof Type = Gable Index
###
###
Results: ###
###
Parameters and Coefficients: Nomenclature ###
Roof Angle, q = 2.39 deg. ###
Mean Roof Ht., h = 60.00 ft. h = he, for roof angle <=10 deg. ###
w = 100.00 ft. w = Lesser of L or B building dimension ###
h/w = 0.600 Ratio of mean roof ht. to least bldg. dimension (for Table 6) ###
Importance Factor, I = 1.15 I = 1.15, per FMG 1-28, Section 2.2(a) ###
Effective Area, Ae = 10.0 ft.^2 Ae <= 10 ft.^2, as limited by FMG 1-28, Section 2.2(d) ###
Zone 2 Dimension, a = 10.000 ft. a = max. of (min. of (0.1*w or 0.4*h), 0.04*w or 3')
Zone 3 Dimension, a = 10.000 ft. a = max. of (min. of (0.1*w or 0.4*h), 0.04*w or 3')
###
Zone 1 (Roof Field Area) Uplift Design Pressure and Rating: ###
Zone 1 (Field Area) Basic Uplift Pressure, pb1 = 27.00 psf pb1 = from FMG 1-28, Table 4 ###
Zone 1 Negative Pressure Multiplier, C1 = 1.00 C1 = from FMG 1-28, Table 6 Result:
Zone 1 (Field Area) Design Uplift Pressure, pd1 = 27.00 psf pd1 = pb1*C1 ###
FMG Factor of Safety, FS = 2 FS = 2, per FMG 1-28
FMG Zone 1 (Field Area) Pressure, p1 = 54.00 psf p1 = pd1*FS
Zone 1 FMG Rating = 1-60 p1 rounded up to next 15 psf interval FMG DS 1
Index
Zone 2 (Perimeter Area) Uplift Design Pressure and Rating: ###
Zone 1 (Field Area) Basic Uplift Pressure, pb1 = 27.00 pb1 = from FMG 1-28, Table 4 ###
Zone 2 Negative Pressure Multiplier, C2 = 1.68 C2 = from FMG 1-28, Table 6 ###
Zone 2 (Perimeter) Design Uplift Pressure, pd2 = 45.36 psf pd2 = pb1*C2 ###
FMG Factor of Safety, FS = 2 FS = 2, per FMG 1-28 ###
FMG Zone 2 (Perimeter Area) Pressure, p2 = 90.72 psf p2 = pd2*FS ###
Zone 2 FMG Rating = 1-105 p2 rounded up to next 15 psf interval ###
###
Zone 3 (Corner Area) Uplift Design Pressure and Rating: ###
Zone 1 (Field Area) Basic Uplift Pressure, pb1 = 27.00 psf pb1 = from FMG 1-28, Table 4 ###
Zone 3 Negative Pressure Multiplier, C3 = 2.53 C3 = from FMG 1-28, Table 6 ###
Zone 3 (Corner) Design Uplift Pressure, pd3 = 68.31 psf pd3 = pb1*C3
FMG Factor of Safety, FS = 2 FS = 2, per FMG 1-28 Interpolatin
FMG Zone 3 (Corner Area) Pressure, p3 = 136.62 psf p3 = pd3*FS ###
Zone 3 FMG Rating = 1-150 p3 rounded up to next 15 psf interval ###

2 of 3 03/05/2020 12:23:59
"FMG128.xls" Program
Version 1.1

###
Result:

3 of 3 03/05/2020 12:23:59