EPCI-1
Contract N. F12515
Facility Sub Facility Name Scale Sheet of Sheets
Floating Production Unit n.a. 1 / 43
Document Title Supersedes N.
identification and numbering, the instrumentation device tagging rules for the Jangkrik
FPU.
Document Verification
REVISION List
00 Issued for COMPANY Review
01 Issued for COMPANY Approval
02 Issued for Construction
03 Issued for Construction/INFO for ENI
HOLD List
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 4 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
TABLE OF CONTENTS
1 PURPOSE .......................................................................................................... 6
1.1 Project Background .......................................................................................... 6
1.2 Scope and Purpose ........................................................................................... 6
2 REFERENCE DOCUMENTS .................................................................................. 7
2.1 Code and Standards ......................................................................................... 7
2.2 ENI Standard Document ................................................................................... 7
2.3 Project Document ............................................................................................. 7
3 DEFINITION AND ABBREVIATIONS .................................................................. 8
4 RESPONSIBILITY.............................................................................................. 9
5 ITEM IDENTIFICATION SYSTEM (NUMBERING SYSTEM) .................................. 9
5.1 General Criteria For Item Identification Implementation ............................... 10
5.1.1 Prefix ............................................................................................................. 10
5.1.2 Facility Code .................................................................................................... 10
5.1.3 Sub Facility Code ............................................................................................. 11
5.1.4 Facility Functional Unit (FFU) ............................................................................. 11
5.1.5 Train N° .......................................................................................................... 11
5.1.6 Measured Variable ............................................................................................ 11
5.1.7 Function ......................................................................................................... 11
5.1.8 Sequential Number ........................................................................................... 12
5.1.9 Suffix ............................................................................................................. 13
5.2 Instruments Identification ............................................................................. 14
5.2.1 Loop Identification ............................................................................................ 14
5.2.2 Instruments Identification ................................................................................. 14
5.3 Operated Valves, Functions And Fire & Gas Devices ....................................... 15
5.3.1 Operated ON/OFF Valves ................................................................................... 15
5.3.2 Electrical Users/Motors ...................................................................................... 17
5.3.3 Fire and Gas Detectors/Devices .......................................................................... 18
5.4 Instrumentation And Automation Equipment ................................................. 19
5.4.1 FFU Identification ............................................................................................. 19
5.4.2 Circuit Type ..................................................................................................... 19
5.4.3 Panel Type Code .............................................................................................. 20
5.5 Individual Cable ............................................................................................. 20
5.6 Multi Core Cables To Junction Boxes .............................................................. 21
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 5 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
1 PURPOSE
1.1 Project Background
Jangkrik Field (also abbreviated as JKK) is a gas discovery made in March 2009. It is
located about 70 km from the coast, in the Muara Bakau permit area, Makassar Strait,
offshore Borneo of Indonesia, at a water depth ranging from 250 to 500 m. Eni,
through its Indonesian subsidiary, operates the Muara Bakau PSC with a 55% interest,
in joint venture with GDF Suez, holding the remaining 45% interest.
To date, three exploration wells (Jangkrik-1, Jangkrik-2 and Jangkrik-3) have been
drilled. A Feasibility study, completed in July 2011, has led to the identification of the
most attractive concept for development of Jangkrik Field. The selected concept is
based on a subsea development with seven wells, full treatment facilities on a spread
moored FPU and export line to shore at Sapi landfall.
Jangkrik North East (also abbreviated as JNE), located at about 25 km NNE from JKK is
a recent gas discovery, made in July 2011, through the explorative well Jangkrik North
East 1. An appraisal well has been drilled in September 2011.
The concept defined during the FEED of the Concept Definition phase and confirmed for
the EXECUTION foresees:
A Barge Shaped FPU performing Full Offshore Process and exporting treated gas
onshore near Sapi existing plant for tie-in of gas to the existing 42” existing
pipeline to Badak Plant and stabilised condensate to the 20” existing pipeline to
Senipah Plant. An additional tie-in to an existing 20” pipeline is foreseen to route
part of the produced gas to the domestic market;
7 Subsea Wells for JKK tied back to the FPU (EP3 and EPCI-2 Contractor scope);
4 Subsea Wells for JNE tied back to the FPU (EP3 and EPCI-2 Contractor scope);
Export gas and condensate flowlines to shore (EPCI-2 Contractor scope);
Final destination of Jangkrik gas is the Bontang LNG Plant and local market.
Final destination of Jangkrik condensate is Senipah Plant.
2 REFERENCE DOCUMENTS
The following codes, standards, recommended practices, and guides shall be
interpreted as the minimum requirements applicable to the subject work, and no
statement contained in this specification shall be construed as limiting the work to such
minimum requirements. The latest editions of the documents listed shall govern all
work.
4 RESPONSIBILITY
Project Engineering Teams shall have overall responsibility for tagging requirements in
project engineering, procurement, construction, commissioning phases within the
Company and contractors/Vendors.
Leaders and Discipline Specialists shall be responsible for ensuring that all the
instrumentation devices are numbered in accordance with this procedure whenever
item identification is required and for number uniqueness.
Sequential numbers range between Contractors shall be assigned by Company, if
required.
Sequential numbers range between Subcontractors shall be assigned by Contractors.
Contractors shall ensure that sequential numbers within their scope of work and their
own range are unique.
The identification system includes eleven (11) structures defined in the following paragraphs.
Each structure is dedicated to an item type that have specific hardware or functional
characteristics.
1. Instruments identification,
2. Operated valves, functions and Fire & Gas devices,
3. Instrumentation and automation equipment,
4. Individual cables,
5. Multi core cables to junction boxes,
6. Multi core cables between cabinets,
7. Air supply manifold,
8. Pneumatic & Process tubing,
9. Hydraulic tubing,
10. MCT frame,
11. Telecommunication equipment identification,
12. Telecommunication cables identification,
13. Instrument wire marker identification,
14. Terminal Strip inside the ICSS Marshalling Cabinet,
15. ICSS Wiring
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 10 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
The general identification criteria outlined below is applicable to all items that need to be
identified for engineering, operation, maintenance, quality control or project management
needs.
Once an identification code is cancelled, it cannot be reused; it will be kept in the item list as
"cancelled item".
It is assumed that maintenance will not create tags in addition to those created by
engineering.
It is therefore a requirement for engineering to provide a tag population in accordance to
maintenance requirements.
When two or more identical instrumentation devices are installed in non-redundant purpose,
they must have different sequential numbers.
The tag shall be reported in documentation, instrumentation data base, reports and labels.
Prefix
Facility Functional
Facility Code
Measured
Sequential
Function
Number
Train N°
Variable
Facility
Code
Code
Code
Suffix
Unit
Sub
(1)
(1)
Note 1: Codes automatically implemented
5.1.1 Prefix
The Prefix is a term which is normally used to identify the Facility code, the Sub facilities code,
the Facility Functional unit code and the train number.
5.1.2 Facility Code
XXXX: Alphanumeric code
Facility: it's the code that identifies the plant.
It is assigned by COMPANY in order to guarantee the traceability of the project documents.
Note: The Facility code is not copy out in each following sections, but it has to be integrated
automatically in each code. The facility code will be the “Plant” code of SPI.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 11 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Note: The Sub-facility code is not copy out in each following sections, but it has to be
integrated automatically in each code.
The sub facility code is the “Area” code of SPI.
5.1.4 Facility Functional Unit (FFU)
XXX: Alphanumeric code
The whole plant will be divided and identified in distinct functional units, according to the
Company Specification – Facility Functional Unit. The facility Functional unit is the unit which
the measured variable belongs. In the same loop if devices belong to different FFU , the loop
will be identified with the most relevant unit. Therefore the FFU of concerned devices will be
the same than the loop FFU.
The FFU is the first element to identify the item. This code is mainly used for loop, and
instrument tagging definition.
5.1.5 Train N°
N: Numeric code
Train defines the facilities allowing a process function. This notion is used on numbering
procedure when almost two trains are involved. If there is no train, the relevant code is
omitted.
Thus only the train number code differentiates the identical instrumentation devices installed
in two different trains.
5.1.6 Measured Variable
A: Alphabetic code
The list of Measured variables and their codes are reported in Annex 1 (Measured variables
list). The First letter of Function code is generally identical to measured variable.
5.1.7 Function
AAAAA: Alphabetic code
The Function is an alphabetic code with a maximum of 5 characters, issued from the "ISA"
codification, whose list can be found in Annex 3 (Function code table).
Actuated valves and dampers identification shall be in accordance with this procedure.
On the other hand, manual valves without any instrumentation device shall be according
piping identification procedure.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 12 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
From 700 to 849 Dedicated to top side package instrument tag number
From 001 to 499 Dedicated to top site power generation instrument tag number
From 500 to 699 Dedicated to hull power generation instrument tag number
From 700 to 899 Dedicated to top side package power generation instrument tag number
From 900 to 999 Dedicated to hull package power generation instrument tag number
The sequence number for HVAC (FFU 660) shall be assigned in sequence applying the below
rule:
Sequential Number Designation
From 001 to 499 Dedicated to top site HVAC instrument tag number
From 500 to 899 Dedicated to hull site fire and gas instrument tag number
From 900 to 949 Dedicated to hull package fire and gas instrument tag number
From 950 to 999 Dedicated to top side package fire and gas instrument tag number
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 13 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
5.1.9 Suffix
XXX: Alphanumeric code
The suffix code is written down at the end of identification item.
The alphabetic suffix code, starting from A, is dedicated to the duplication of an item which
fulfills the redundancy rules explained below.
The numeric suffix code, starting from one (1), is also used to dissociate similar functions on
the same loop.
The redundancy concerning the equipment (e.g., pumps, drums,…) is not considered for the
tagging of instrumentation devices. Thus, for two (2) redundant equipment on the same train
the instrumentation devices shall be identified with different sequential number.
The Redundancy here described characterizes two or more identical instrumentation devices
within the same train.
The suffix code used for redundancy shall be only used in the following cases:
When two or more identical instrumentation devices; same measure type, same control
functions are installed in the same equipment.
The instrumentation devices could have a different construction type, if they are
compliant with the precedent requirement (ex: ionic gas detector, Infra-red gas
detectors, point gas detectors).
The instrumentation could have different set points if they comply with the first
requirement (ex: Pressure safety valves with different exhaust pressure value).
When the suffix code is not used the relevant digit code is omitted.
Example 1: Redundant pressure safety valves pertain to sub facility 01(FPU), Unit 370,
train 1
Loop name Function
013701P001 013701PSV001A Pressure safety valve duty
013701P001 013701PSV001B Pressure safety valve spare
Example 2: Redundant Flow measures pertain to sub facility 01 (FPU), Unit 370
Loop name Function
013700F001A 013700FE001A Flow element (orifice plate)
013700F001A 013700FT001A Flow transmitter
013700F001A 013700FAL001A Low Flow alarm
013700F001B 013700FE001B Flow element (orifice plate)
013700F001B 013700FT001B Flow transmitter
013700F001B 013700FAL001B Low Flow alarm
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 14 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Measured
Sequential
Unit Code
Facility
Number
Variable
Train N°
Suffix
REFERENCE Ann1
STRUCTURE X X X N A N N N A
Redundant Pressure loops in FPU ‐ FFU 530 (Fresh water) Train1
5 3 0 1 P 0 0 1 A
EXAMPLE
5 3 0 1 P 0 0 1 B
Sequential
Functional
Function
Number
Facility
Train N°
Variable
Code
Suffix
Unit
Reference Annex 3
Structure X X X N A A A A A A N N N X X X
All the following examples pertain to FFU 530 (Fresh water) Train1
Pressure Transmitter, PressureController and pressure valve of Loop 5301P001
5 3 0 1 P 0 0 1
5 3 0 1 P T 0 0 1
Example 1
5 3 0 1 P I C 0 0 1
5 3 0 1 P V 0 0 1
Pressure Transmitter and Pressure Indicator 1 & 2 of Loop 5301P002
5 3 0 1 P 0 0 2
5 3 0 1 P T 0 0 2
Example 2
5 3 0 1 P I 0 0 2 A
5 3 0 1 P I 0 0 2 B
Pressure Transmitters and Pressure Indicators pertaining to the 2 redundant Loops 5301P003A and 5301P003B
5 3 0 1 P 0 0 3 A
5 3 0 1 P T 0 0 3 A
5 3 0 1 P I 0 0 3 A
Example 3
5 3 0 1 P 0 0 3 B
5 3 0 1 P T 0 0 3 B
5 3 0 1 P I 0 0 3 B
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 15 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Functional
Sequential
Measured
Number
Train N°
Variable
Function
Facility
Suffix
Code
Unit
Reference Annex 3
Structure X X X N A A A A A A N N N X X X
5 3 0 1 X 0 0 1
5 3 0 1 E S D V 0 0 1
5 3 0 1 E S D Y 0 0 1
ESDV001 5 3 0 1 Z S H 0 0 1
5 3 0 1 Z I H 0 0 1
5 3 0 1 Z S L 0 0 1
5 3 0 1 Z I L 0 0 1
5 3 0 1 X 0 0 2
5 3 0 1 B D V 0 0 2
5 3 0 1 B D Y 0 0 2
BDV002 5 3 0 1 Z S H 0 0 2
5 3 0 1 Z I H 0 0 2
5 3 0 1 Z S L 0 0 2
5 3 0 1 Z I L 0 0 2
5 3 0 1 X 0 0 3
5 3 0 1 S D V 0 0 3
5 3 0 1 S D Y 0 0 3
SDV003 5 3 0 1 Z S H 0 0 3
5 3 0 1 Z I H 0 0 3
5 3 0 1 Z S L 0 0 3
5 3 0 1 Z I L 0 0 3
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 17 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
The identification of motor instrumentation signals could not follow the equipment name
identification. An instrumentation sequential number, different of equipment identification, is
assigned to electrical users.
The function code used for electrical user, composed of by three (3) characters, are listed on
Annex 3 . (Electrical users/motors Function code list).
Measured
Unit Code
Sequential
Number
Function
Facility
Variable
Train N°
Suffix
Note
Reference Annex 3
Structure X X X N A A A A A A N N N X X X
3 9 0 M 0 0 5
3 9 0 M H S M 0 0 5 Main/Stand by selection ( Software command)
3 9 0 M H S H 0 0 5 A Remote Start command
Pump 3 9 0 M H S L 0 0 5 A Remote Stop command
013900PA001A 3 9 0 M X S 0 0 5 A Trip command
3 9 0 M Y L ‐ R 0 0 5 A Running Status
3 9 0 M Y A U 0 0 5 A Available signal/Unavailable alarm
3 9 0 M Y L R 0 0 5 A Remote control selection command
3 9 0 M H S H 0 0 5 B Remote Start command
3 9 0 M H S L 0 0 5 B Remote Stop command
Pump 3 9 0 M X S 0 0 5 B Trip command
013900PA001B 3 9 0 M Y L ‐ R 0 0 5 B Running Status
3 9 0 M Y A U 0 0 5 B Available signal/Unavailable alarm
3 9 0 M Y L R 0 0 5 B Remote control selection command
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 18 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
The fire and gas detectors / devices are identified according to the Fire zone and Fire area they
belong to. Refer to Annex 6 for Fire zone codes.
Measured
Sequential
Function
Fire Area
Number
Train N°
Variable
Facility
Code
Unit
Reference Annex 3
Structure X X X N A A A A A A N N N N N N
7 0 0 G 0 0 1
Gas detector 7 0 0 G D 1 0 2 0 0 1
in Fire Zone 1 7 0 0 G D I 1 0 2 0 0 1
Fire Area 102 7 0 0 G A X 1 0 2 0 0 1
Loop 001 7 0 0 G A H 1 0 2 0 0 1
7 0 0 G A H H 1 0 2 0 0 1
7 0 0 G 0 0 2
Toxic Gas detector 7 0 0 G T D 1 0 3 0 0 2
in Fire Zone 1 7 0 0 G D I 1 0 3 0 0 2
Fire Area 103 7 0 0 G A X 1 0 3 0 0 2
Loop 002 7 0 0 G A H 1 0 3 0 0 2
7 0 0 G A H H 1 0 3 0 0 2
7 0 0 S 0 0 1
Smoke Optical
7 0 0 S O D 1 0 4 0 0 1
in Fire zone 1
7 0 0 S A X 1 0 4 0 0 1
Fire Area 104
7 0 0 S A H H 1 0 4 0 0 1
Loop 001
7 0 0 U R 1 0 4 0 0 1
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 19 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
As the panels are usually installed into technical room, their identification code depends on
facility functional unit.
Whatever the type of cabinet, the sequential number is different for all cabinets.
Unit Code
Circuit type
Sequential
Functional
Number
Train N°
Facility
Code
Type
Suffix
Panel
Reference Annex 2
Structure X X X N A A A A A N N N A
ESD ANALOG JUNCTION BOX in FPU Unit 210 Train1
Example 2 1 0 1 N J T E 0 0 1 ‐
DIGITAL JUNCTION BOX DCS in FPU Unit 210 Train1
Example 2 1 0 I J T D 0 0 5 ‐
DCS Marshalling Cabinet IR (Instrument Room)
Example 9 7 0 J J 0 0 1 ‐
DCS System cabinet in IR
Example 9 7 0 J K 0 0 2 ‐
ESD Marshalling Cabinet in IR (Instrument Room)
Example 9 8 0 J J 0 1 2 ‐
ESD System cabinet in IR
Example 9 8 0 J K 0 1 1 ‐
Instruments mounted on the panels have their own tags. It does not refer to panel number.
The FFU Identification code is used to codify the localization of instrument devices. That is
used for panels, MCT frame, air manifolds and Control Room Instruments.
• if they receive signals from instruments belonging to a single functional unit, they are
assigned to that FFU.
• if they receive signals from instruments of different functional units they are assigned to the
control room FFU(970/980).
• if they receive signals from processing or generating functional units installed between the
field and the operations room, they belong to the FFU, which includes the equipment and the
instrument that generates or processes the signal.
• if they receive a signal from a FFU that conditions and/or validates only the signal generated
by a local instrument and does not perform other functions, they belong to the unit which
includes the instrument that generates the signal.
Sequential
Cable Type
Function
Number
Train N°
Suffix
Reference Ann 7
Structure X X X N A A A A A A A N N N X X X
Cable mesure IS for 510‐PT‐001 train1
Example 5 1 0 1 J C P T 0 0 1
Cable mesure non IS for 530‐FT‐004
Example 5 3 0 J C F T 0 0 4
Cable Power for 530‐FT‐004
Example 5 3 0 J P F T 0 0 4
When individual cable is connected to a field instrument, the sequential number shall be the
same as the sequential number of the instrument, when possible.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 21 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Panel Type Code
Functional
Circuit Type
Sequential
Cable Type
Number
Train N°
Facility
Suffix
Unit
ESD Multi cable for Junction Box
Example 2 1 0 N J C J T E 0 0 1
When multi core cable is connected to a junction box, the sequential number shall be the same
as the sequential number of the junction box, when possible.
Functional
Sequential
Sequential
Cable type
Panel type
Panel type
Train N°
Num ber
Num ber
Facility
Facility
num ber
Order
U nit
U nit
9 7 0 N J F J E 0 0 1 9 7 0 J D 0 0 1 0 0 1
9 7 0 N J C J M E 0 0 5 9 7 0 J M D 0 0 5 0 0 1
The first columns “Panel type + sequential number” represent the tag of the cabinet out.
The second columns “Panel type + sequential number” represent the tag of the cabinet in.
Order number is a numeric code, similar to a sequential number, to allow several multi core
cables between Panel A and panel B.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 22 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
AIR SUPPLY
MANIFOLD
Functional
Sequential
Number
Facility
Unit
Reference
Structure X X X A A A N N N
2 1 0 A S M 0 0 1
P: Pneumatic
Functional
Sequential
TRAIN N°
Number
Function
TUBING
Facility
Type
Suffix
Unit
Reference
Structure X X X N A A A A A A A N N N X
5 1 0 P S D V 0 0 1
The process tubing identification shall use the instrument tag number adding the following
letter to the function will comply with the following rule:
PC: Process
Functional
Sequential
TRAIN N°
Number
Function
TUBING
Facility
Type
Suffix
Unit
Reference
Structure X X X N A A A A A A A N N N X
5 1 0 P C A I T 0 0 1
Process Tubing identification shall be apply on tubing more than 10 meters length.
Sequential
Unit Code
TRAIN N°
Function
TUBING
Number
Facility
Suffix
Type
Reference
Structure X X X N A A A A A A A N N N X
5 1 0 H C S D V 0 0 1
5 1 0 H R S D V 0 0 1
Sequential
Number
ROOM
MCT
Reference Annex 4
Structure X X X A A A A N N N N
I E R J M C T 0 0 0 1
Telecom
Facility Functional
Equipment Type
Sub‐System
Telecom
Sequential
Number
Code
Code
Suffix
Unit
PA/GA system‐A loudspeaker with number 557 (by the number, it is installed in LQ, level 3)
Example 9 6 0 E Q N 5 5 7 A
The Facility Functional Unit code for Telecommunication is ‘960’ (Refer to reference document,
ref [2]).
The Telecom Sub-System is used to define the system to which the equipment belongs in The
Telecommunication system. It is one digit alphanumerical, as listed in the Annex 8.
The Telecom Equipment Type code is used to define the specific function of the equipment in
the Sub-System. It is two digits in alphabetical, as listed in the Annex 9.
The Sequential number is three digits numerical. Numbering sequence shall be distingushed
by the area/location of each equipment installed, as below:
The Suffix is one digit alphabetical, added for the identification of same type of equipment
installed in pararel (as usually used in redundancy configuration).
Telecom Equipment
Facility Functional
Unit Code
Sequential
Cable Type
Type Code
Number
Suffix
Individual cable to CCTV Camera number 019 located in topside
Example 9 6 0 T N F A M 0 1 9
When the Individual cable connected to a Telecom equipment, the cable tag shall follow the
tagging of destination telecom equipment. And then added with its cable type.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 26 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Telecom Sub‐System
Telecom Equipment
Loop Identification
Facility Functional
Unit Code
Sequential
Cable Type
Type Code
Number
Suffix
Reference Ann 7 follow the tagging of destination telecom equipment
Structure X X X A A X A A N N N A N N
Individual cable of PAGA system A to speaker 019 in loop 15
Example 9 6 0 T N F A M 0 1 9 A 1 5
Telecom Equipment
Facility Functional
Identification
Cable Order
Unit Code
Sequential
Cable Type
Type Code
Number
Suffix
Multipair cable, cable order 17, from PA/GA system A cabinet to Junction Box number 031
Example 9 6 0 T R E Q U 0 3 1 A 1 7
When the Multipair cable connected to a Junction Box, the cable tag shall follow the tagging of
destination Junction Box. And then added with its cable type and cable order number as shown
in the example above.
Telecom Sub‐System
Telecom Equipment
Facility Functional
Identification
Cable Order
Unit Code
Sequential
Sequential
Cable Type
Type Code
Number
Number
Suffix
Suffix
Reference Ann 7
Structure X X X A A X Q G N N N A X N N N A N N
Cable order 07, from LAN WAN Cabinet 015 to Distribution Cabinet 017
Example 9 6 0 T F G Q G 6 1 5 G 6 1 7 0 7
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 27 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
The Multipair cable identification shall consist of the ‘from cabinet tag’ and the ‘to cabinet tag’,
inserted with the cable type and cable order number. The ‘order number’ shall be used when
there are several cables connected between cabinets.
5.15.2 Terminal block for the cable from package cabinet to marshalling cabinet and there is
one cable between them
The terminal strip number shall be the same with package cabinet tag number.
5.15.3 Terminal block for the cable from package cabinet to marshalling cabinet and there are
several cables between them
Terminal strip number shall be “package cabinet tag number-the last number of the cable”.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 29 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
6 LABELLING PRINCIPLE
6.1 Instruments labeling
All instruments must have two labels, on the instrument itself and another screwed on the
support of the instrument.
The attached Label on the Instrument shall be made of an engraved stainless steel plate; the
letters shall be 5mm high, attached with SS316 tie wrap on the instrument.
The Label fixed on the support shall be made an engraved Traffolyte plate, the letters shall be
15mm high and the plate fixed with stainless steel screw on the instrument support.
All the Traffolyte plate shall be coloured depending on the system to which the instrument is
connected, according to the below table.
All Outdoor cables shall be tagged at the termination ends. Punched SS316L label attached
with stainless fasteners is used.
7 TABLE OF ANNEXES
Measured
Description
variable
A Analysis
B Burn/combustion/Flame
C Corrosion
D Density
E Voltage
F Flow rate
H Hand
G Gas
I Current
J Power
K Time
L Level
M Moisture/motor
O
P Pressure
Q Quantity
R Radiation
S Speed/frequency
T Temperature
U Multivariable
V Vibration/machinery analysis
W Weight/force
X Danger/safety/emergency/Miscellaneous/On_Off actuated valves
Y Event/state/presence
Z Position/dimension
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 32 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
A TELECOMMUNICATION EQUIPMENT
B NOT USED
C MISCELLANEOUS MECHANICAL EQUIPMENT AND FILTERS (Not Online) (Hvac Filters
Excluded)
D DRILLING AND COMPLETION EQUIPMENT
E ELECTRICAL EQUIPMENT
F HEATERS, FURNACES AND FLARING EQUIPMENT
G SANITATION, CONDITIONING, HEATING AND H.VAC. EQUIPMENT
H HEAT TRANSFER EQUIPMENT
I NOT USED
J INSTRUMENTATION AND AUTOMATION SYSTEM EQUIPMENT
K COMPRESSORS, BLOWERS AND NON "HVAC" VENTILATORS
L IDENTIFIED ON-UNE BULKS
M NON ELECTRICAL PRIME ENGINES AND MISCELLANEOUS
N SPECIFIC MAINTENANCE OBJECT
O NOT USED
P PUMPS
Q TELECOMMUNICATION EQUIPMENT
R VALVES
S SAFETY, ESCAPE AND FIRE-FIGHTING EQUIPMENT
T TANKS
U SUBSEA EQUIPMENT
V PRESSURE AND SEPARATOR EQUIPMENT
W STEEL OFFSHORE STRUCTURES AND FACILITIES
X MISCELLANEOUS
Y MATERIAL AND MISCELLANEOUS PRODUCT HANDUNG EQUIPMENT
Z INDUSTRIAL BUILDINGS AND STEEL STRUCTURES
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 33 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
JA Analysis equipment
JB Centralized control board (conventional and ancillary cabinet)
JC Local Control Board
JD Remote Control Board
JE Emergency shut down system equipment (ESD)
JF Fire and Gas detection equipment other than instruments listed in annex 3 and equipment
listed in class S
JG Not used
JH Host and personal computer, computer terminals
JJ Interface cabinet (optical or galvanic insulation/ intrinsically safe) /, marshalling cabinet
JK Logical Cabinet (Relay/PLC)/system cabinet
JL Alarm Panel/Mimic Panel
JM Metering and proving equipment, including weighing machines
JN Not used
JP Control panel (pneumatic and hydraulic)
JQ Thermocouple cable
JR Not used
JS Synoptic panel
JT Junction box
JU Supervision control and data acquisition (SCADA) equipment
JV Distributed process Control System equipment (DCS)
JW Well head Control Panel
JX Flare ignition panel
JY Miscellaneous instrumentation and automation equipment
JZ Extinguishing gas panel, Deluge panel, Firefighting panel.
AUTOMATION SYSTEMS
Note 1: Analysis (letter A as initiating variable). The letter “A” covers analyzers not described
by specific letters.
Note 2: Gas detection (letter G initiating variable), Gas detection instruments shall be named
using codes defined in annex 3.
Note 3: /
Note 4: /
Note 7: /
The number of codified functions shall be limited as much as possible to two. As a general rule,
it is recommended that the number of letters is limited, in order to indicate only the process
variable and the actual main function instrument. Alarm threshold shall not be considered as
an instrument, but shall be a part of the associated device, which generates the function.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 36 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Note:
Software tags are not mandatory; when these tags are automatically generated by ICSS
function block, the native ICSS tags shall be used.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 37 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Fire & Gas detector shall be named using the function Alarm Signalling
codes defined here after: Fire and Gas table
Detection type Detect Pre- Alarm Reset
Fault alarm
Gas detection
Gas detector (infrared, point) GD
TOXIC GAS (H2S) GTD
Beam Gas detector GBDT/
GAH GAHH /
(TRANSMITTER/RECEIVER) GBDR GAX
Catalytic gas detector GCD
(flammable gas including HYDROGEN )
Oxygen Gas Detector GOD GAL / /
Flame detection
Flame UV & IR and Imaging flame BED
detection
Flame IR (Infrared, Single and Multi BID BAX / BAHH /
frequency Infrared)
Flame UR BUD
Fire detection
Smoke Ionisation SID
/
Smoke Optical SOD UR
/
Smoke Combined SCD SAX SAHH
Early Warning Smoke Detection SAH
SAD /
System - Aspirating Smoke Detector
Heat Fixed Temperature Type
TFD
(Thermostatic, Fusible plug, Frangible /
bulb (Sprinkler))
Rate Of Rise Temperature TRD TR
/
Rate Compensated Temperature TRCD
/
TAX TAHH
Linear Heat Detector(heat sensitive
TCD /
cable) /
Low Temperature Detector For
TLD /
Liquefied
/
(Temperature sensor or Leak Detection
by Fibre optic)
Miscellaneous Fire & Gas alarms
Manual Alarm for fire HSB
/ /
Manual Alarm for Emergency Shutdown HXB
/ /
(ESD function, PSD/LSD functions)
UAX UAHH
Abandon Push Button HAB / /
Man Overboard Push Button HMOB / /
Alarm Status Beacon YL
/ /
Alarm Status Horn or Horn and Beacon YS YAX YAHH
/ /
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 38 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Code Description
P1 to P10 Module Portside
S1 to S10 Module Starboard side
PR Pipe Rack
US Utility Space
HD Hull Deck
FL Flare
HU Hull
AM Aft Machinery space
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 39 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Fire zones and fire areas shall be marked in a site plot plan.
Fire zone and fire area codes shall be added as an attribute to all fire and gas instrument (FFU
700), here below the list of fire zones and fire areas as per fire and gas detection philosophy.
┌───────── SERVICE
│ ┌───────────────── FUNCTION
│ │
P Power cable
B < 1000 V rated cables for normal or essential supply
G < 1000 V rated cables for emergency supply
H > 1000 V rated cables for normal or essential supply normal
L lighting circuit cables
V < 1000 V cables for safety system supply
C Control and cathodic protection electric cables
A signal alarm cables
C control cables
M measurement cables
P cathodic protection cables
Z not otherwise specified
J Instrumentation Cables
T Coaxial cables
C Instrumentation cables (alarm, status, control,
measurement,etc.)
F Fibre optical cables
R Thermocouple - Thermo-resistance measurement cables
Y Solenoid Valves cables
P Power supply cables
U Pulse or Frequency signals cables
Z Not otherwise specified
T Telecommunication cables
B Indoor Telephone signals/cables
E Ethernet Cable
O Outdoor Telephone signals/cables
C Coaxial cables
F Fibre optical cables
L Loudspeaker cable
M Multifunction cables
Q Beacon cables
P Power Supply cables
G GPS devices cables
N CCTV Cameras cables
X ACS and IDS device cables
Z Not otherwise specified
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 41 of 43
Wiring And Tagging Rules 03 EX-DE
Specification
Code Description
4 NAVIGATIONAL SYSTEM, includes Gyro, DGPS, Compass & Radar