JANGKRIK COMPLEX PROJECT

FLOATING PRODUCTION UNIT

EPCI-1

WIRING AND TAGGING RULES SPECIFICATION

Issued for Construction/INFO for


03 EX-DE 09/10/2015 M.W. Wibowo M. Huda Yuliwanto
ENI
02 EX-DE 13/08/2014 Issued for Construction M.W. Wibowo B. Hutajulu Yuliwanto
01 EX-DE 30/05/2014 Issued for COMPANY Approval M.W. Wibowo B. Hutajulu Yuliwanto
00 EX-DE 20/02/2014 Issued for COMPANY Review T.ElBkraoui M. Koumar C. Tarlé
Rev Validity
Number Status Date Description Prepared Checked Approved
Revision Index
Company logo and business name Project name Company Document ID
220801DIST13009
JANGKRIK
Eni Muara Bakau B.V. COMPLEX PROJECT Job N.
Contractor logo and business name Contractor Document ID
F12515-STC-000-INS-SPC-13009

Contract N. F12515
Facility Sub Facility Name Scale Sheet of Sheets
Floating Production Unit n.a. 1 / 43
Document Title Supersedes N.

WIRING AND TAGGING RULES SPECIFICATION Superseded by N.


Plant Area Plant Unit
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 2 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

Project / Initiative name Jangkrik Complex Project/Document Title


The purpose of this document is to define the minimum requirements for the instrument
ABSTRACT

identification and numbering, the instrumentation device tagging rules for the Jangkrik
FPU.

Document Verification

Prepared by Signature Date


contractor Prepared

M.W. Wibowo 09/10/2015

Checked by Signature Date


M. Huda 09/10/2015

Approved by Signature Date


Yuliwanto 09/10/2015

Checked by Unit Signature Date


Company
Checked

Checked by Unit Signature Date

Approved by Unit Signature Date


Approved
Company

Endorsed by Unit Signature Date


Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 3 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

REVISION List
00 Issued for COMPANY Review
01 Issued for COMPANY Approval
02 Issued for Construction
03 Issued for Construction/INFO for ENI

HOLD List
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 4 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

TABLE OF CONTENTS

1  PURPOSE .......................................................................................................... 6 
1.1  Project Background .......................................................................................... 6 
1.2  Scope and Purpose ........................................................................................... 6 
2  REFERENCE DOCUMENTS .................................................................................. 7 
2.1  Code and Standards ......................................................................................... 7 
2.2  ENI Standard Document ................................................................................... 7 
2.3  Project Document ............................................................................................. 7 
3  DEFINITION AND ABBREVIATIONS .................................................................. 8 
4  RESPONSIBILITY.............................................................................................. 9 
5  ITEM IDENTIFICATION SYSTEM (NUMBERING SYSTEM) .................................. 9 
5.1  General Criteria For Item Identification Implementation ............................... 10 
5.1.1  Prefix ............................................................................................................. 10 
5.1.2  Facility Code .................................................................................................... 10 
5.1.3  Sub Facility Code ............................................................................................. 11 
5.1.4  Facility Functional Unit (FFU) ............................................................................. 11 
5.1.5  Train N° .......................................................................................................... 11 
5.1.6  Measured Variable ............................................................................................ 11 
5.1.7  Function ......................................................................................................... 11 
5.1.8  Sequential Number ........................................................................................... 12 
5.1.9  Suffix ............................................................................................................. 13 
5.2  Instruments Identification ............................................................................. 14 
5.2.1  Loop Identification ............................................................................................ 14 
5.2.2  Instruments Identification ................................................................................. 14 
5.3  Operated Valves, Functions And Fire & Gas Devices ....................................... 15 
5.3.1  Operated ON/OFF Valves ................................................................................... 15 
5.3.2  Electrical Users/Motors ...................................................................................... 17 
5.3.3  Fire and Gas Detectors/Devices .......................................................................... 18 
5.4  Instrumentation And Automation Equipment ................................................. 19 
5.4.1  FFU Identification ............................................................................................. 19 
5.4.2  Circuit Type ..................................................................................................... 19 
5.4.3  Panel Type Code .............................................................................................. 20 
5.5  Individual Cable ............................................................................................. 20  
5.6  Multi Core Cables To Junction Boxes .............................................................. 21 
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 5 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.7  Multi Core Cables Between Cabinets ............................................................... 21 


5.8  Air Supply Manifold ........................................................................................ 22 
5.9  Pneumatic & Process Tubing .......................................................................... 22 
5.10  Hydraulic Tubing ............................................................................................ 22 
5.11  MCT Frame ..................................................................................................... 23 
5.11.1  MCT Field Code: ............................................................................................... 23 
5.12  Telecommunication Equipment Identification ................................................ 24 
5.13  Telecommunication Cable Identification......................................................... 25 
5.13.1  Individual Cable ............................................................................................... 25 
5.13.2  Cable in PAGA system ....................................................................................... 26 
5.13.3  Multipair Cable to Junction Box........................................................................... 26 
5.13.4  Cable Between Cabinets .................................................................................... 26 
5.14  Instrument Wire Marker Identification........................................................... 27 
5.14.1  Cable Termination in Instrument Field Device ....................................................... 27 
5.14.2  Cable Termination in Instrumentation and Automation Equipment ........................... 27 
5.15  Terminal Strip inside the ICSS Marshalling Cabinet ........................................ 28 
5.15.1  Terminal block for the cable from junction box to marshalling cabinet ...................... 28 
5.15.2  Terminal block for the cable from package cabinet to marshalling cabinet and there is
one cable between them ............................................................................................. 28 
5.15.3  Terminal block for the cable from package cabinet to marshalling cabinet and there are
several cables between them ....................................................................................... 28 
5.16  ICSS Wiring .................................................................................................... 29 
6  LABELLING PRINCIPLE ................................................................................... 30 
6.1  Instruments labeling ...................................................................................... 30 
6.2  Cables and Tubes labeling .............................................................................. 30 
7  TABLE OF ANNEXES ........................................................................................ 30 
ANNEX 1 - MEASURED VARIABLES LIST ......................................................... 31 
ANNEX 2 – INSTRUMENTATION EQUIPMENT TYPE ......................................... 32 
ANNEX 3 - FUNCTION CODE TABLES ............................................................... 34 
ANNEX 4 – ROOM LIST ................................................................................... 38 
ANNEX 5 - PLANT AREA IDENTIFICATION ...................................................... 38 
ANNEX 6 – FIRE ZONE CODES ......................................................................... 39 
ANNEX 7 – SERVICE AND FUNCTION OF CABLES ............................................ 40 
ANNEX 8 – TELECOMMUNICATION SUBSYSTEM .............................................. 41 
ANNEX 9 – TELECOMMUNICATION EQUIPMENT TYPE CODE ........................... 42 
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 6 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

1 PURPOSE
1.1 Project Background
Jangkrik Field (also abbreviated as JKK) is a gas discovery made in March 2009. It is
located about 70 km from the coast, in the Muara Bakau permit area, Makassar Strait,
offshore Borneo of Indonesia, at a water depth ranging from 250 to 500 m. Eni,
through its Indonesian subsidiary, operates the Muara Bakau PSC with a 55% interest,
in joint venture with GDF Suez, holding the remaining 45% interest.
To date, three exploration wells (Jangkrik-1, Jangkrik-2 and Jangkrik-3) have been
drilled. A Feasibility study, completed in July 2011, has led to the identification of the
most attractive concept for development of Jangkrik Field. The selected concept is
based on a subsea development with seven wells, full treatment facilities on a spread
moored FPU and export line to shore at Sapi landfall.

Jangkrik North East (also abbreviated as JNE), located at about 25 km NNE from JKK is
a recent gas discovery, made in July 2011, through the explorative well Jangkrik North
East 1. An appraisal well has been drilled in September 2011.

The concept defined during the FEED of the Concept Definition phase and confirmed for
the EXECUTION foresees:
 A Barge Shaped FPU performing Full Offshore Process and exporting treated gas
onshore near Sapi existing plant for tie-in of gas to the existing 42” existing
pipeline to Badak Plant and stabilised condensate to the 20” existing pipeline to
Senipah Plant. An additional tie-in to an existing 20” pipeline is foreseen to route
part of the produced gas to the domestic market;
 7 Subsea Wells for JKK tied back to the FPU (EP3 and EPCI-2 Contractor scope);
 4 Subsea Wells for JNE tied back to the FPU (EP3 and EPCI-2 Contractor scope);
 Export gas and condensate flowlines to shore (EPCI-2 Contractor scope);

Final destination of Jangkrik gas is the Bontang LNG Plant and local market.
Final destination of Jangkrik condensate is Senipah Plant.

1.2 Scope and Purpose


The purpose of this document is to define the minimum requirements for the
instrument identification and numbering, the instrumentation device tagging rules for
the plant.
A dedicated Numbering procedure for subsea will be issued for identification of subsea
equipment and instruments.
A Telecom’s equipment numbering procedure has to be used for identification of
telecom’s equipment.
These requirements shall be used throughout all steps of the Project and by all parties:
CONTRACTOR, SUB CONTRACTORS and VENDORS/SUPPLIERS
This document is issued from company specification. However some characteristics
have been reworked to be suitable to FPU plant.
Any conceptual deviations from “Item numbering” relevant to instrumentation discipline
and reported in this document, will be included in the project Numbering Procedure.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 7 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

2 REFERENCE DOCUMENTS
The following codes, standards, recommended practices, and guides shall be
interpreted as the minimum requirements applicable to the subject work, and no
statement contained in this specification shall be construed as limiting the work to such
minimum requirements. The latest editions of the documents listed shall govern all
work.

2.1 Code and Standards


Applicable reference codes and standards for the design and quality levels of the supply
shall be the latest edition of the following, including amendments:

International Society of Automation (ISA)

[1] ISA S5.1 - Instrumentation Symbols and Identification

2.2 ENI Standard Document


[2] 06215.DOC.GEN.SDS - Facility Functional Units
[3] 20198.COO.GEN.SDS - Item Numbering.
[4] 20189.COO.GEN.SDS - Technical project documents identification and classification.
[5] 06225.DOC.STA.PRG - Loop & Instrument List.

2.3 Project Document

・ 220801BGRSH45183 Basis of design and Functional requirements for FPU Detail


・ 220801DIST13013 General Specification For Instrumentation Installation
・ 220801DIST13011 General Specification For Instrument
・ 220801DFRB19400 Fire and Gas Detection Philosophy
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 8 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

3 DEFINITION AND ABBREVIATIONS


Definitions of terms used in the best practice are shown below:
Term  Definition 
Assembly  A general term that can indicate an unidentified association of the
components. 
ASM Air supply manifold
Cable Service and A unique code identifying different services and functions of electrical,
function code  control and instrumentation cab les (Annex 7).
Contractor  A first level supplier.
Company  Final client responsible for project and facility.
Component  A general term that can indicate equipment or a part of equipment. In
this case the identification is provided by the item tag or by the part
number of the part list of the item.
Device or Define in this specification all type of instrumentation devices; valves,
Instrumentation motor control signals, motor trip signals, sensors, transmitters,
device  cabinets, junction boxes
Equipment Used in this specification for describe a process equipment (pumps,
heaters, drums, tanks) Generally the equipment are defined on
equipment list.
Fire Zone code  Facility unique code for identification of areas relevant for installation of
Fire and Gas and Fire Fighting devices.
ID  Identification Tag 
IS  Intrinsically Safe 
Item A material that needs to be identified according to this best practice. 11
  types of items structures are defined according to characteristic of the
items: the term 'item number' indicates its whole identification code.
Loop A loop is a group of instrumentation functions and/or devices which
contributes to the same instrumented service
Ex: The Pressure loop P001 is made of transmitter PT001, controller
PIC001 and control valve PV001.
MCT Multi cable transit
Package  It is the identified assembly of identified items usually purchased on a
single contract order position.
Project  Financial effort for the realization of one or more facilities, or part or
phase of a facility
Skid  It is the identified assembly of identified items usually mounted on
single skid. 
SPI Smart plan instrumentation (Intools) Instrumentation data base/wiring
tool.
Tag  It is the tag on the item.
Train  Duplication of parts of a functional unit.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 9 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

4 RESPONSIBILITY
Project Engineering Teams shall have overall responsibility for tagging requirements in
project engineering, procurement, construction, commissioning phases within the
Company and contractors/Vendors.
Leaders and Discipline Specialists shall be responsible for ensuring that all the
instrumentation devices are numbered in accordance with this procedure whenever
item identification is required and for number uniqueness.
Sequential numbers range between Contractors shall be assigned by Company, if
required.
Sequential numbers range between Subcontractors shall be assigned by Contractors.

Contractors shall ensure that sequential numbers within their scope of work and their
own range are unique.

5 ITEM IDENTIFICATION SYSTEM (NUMBERING SYSTEM)

The identification system includes eleven (11) structures defined in the following paragraphs.
Each structure is dedicated to an item type that have specific hardware or functional
characteristics.

Hereinafter the list of the 11 structures reported:

1. Instruments identification,
2. Operated valves, functions and Fire & Gas devices,
3. Instrumentation and automation equipment,
4. Individual cables,
5. Multi core cables to junction boxes,
6. Multi core cables between cabinets,
7. Air supply manifold,
8. Pneumatic & Process tubing,
9. Hydraulic tubing,
10. MCT frame,
11. Telecommunication equipment identification,
12. Telecommunication cables identification,
13. Instrument wire marker identification,
14. Terminal Strip inside the ICSS Marshalling Cabinet,
15. ICSS Wiring
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 10 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.1 General Criteria For Item Identification Implementation

The general identification criteria outlined below is applicable to all items that need to be
identified for engineering, operation, maintenance, quality control or project management
needs.

Once an identification code is cancelled, it cannot be reused; it will be kept in the item list as
"cancelled item".

An identification string shall be only dedicated to one device.

The definition of the identification codes utilizes:

 A for alphabetic characters


 N for numeric characters
 X for alphanumeric characters

It is assumed that maintenance will not create tags in addition to those created by
engineering.
It is therefore a requirement for engineering to provide a tag population in accordance to
maintenance requirements.

When two or more identical instrumentation devices are installed in non-redundant purpose,
they must have different sequential numbers.

The tag shall be reported in documentation, instrumentation data base, reports and labels.

Prefix
  Facility Functional 
 Facility Code

Measured 

Sequential 
Function

Number
Train N°

Variable
Facility
 Code

 Code

 Code

Suffix
Unit
Sub
(1)

(1)

REFERENCE Ann 1 Annex 3


STRUCTURE X X X X X X X X X N A A A A A A N N N X X X

Note 1: Codes automatically implemented

5.1.1 Prefix
The Prefix is a term which is normally used to identify the Facility code, the Sub facilities code,
the Facility Functional unit code and the train number.
5.1.2 Facility Code
XXXX: Alphanumeric code
Facility: it's the code that identifies the plant.
It is assigned by COMPANY in order to guarantee the traceability of the project documents.

Note: The Facility code is not copy out in each following sections, but it has to be integrated
automatically in each code. The facility code will be the “Plant” code of SPI.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 11 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.1.3 Sub Facility Code


XX: Alphanumeric code
Sub facility Code: it's a code that identifies a part/section unit within the facility defined on
functional or geographic criteria, such as Floater, cluster, sea line. The code has 2 characters.
The code ‘01’ shall be used for the FPU.

Note: The Sub-facility code is not copy out in each following sections, but it has to be
integrated automatically in each code.
The sub facility code is the “Area” code of SPI.
5.1.4 Facility Functional Unit (FFU)
XXX: Alphanumeric code
The whole plant will be divided and identified in distinct functional units, according to the
Company Specification – Facility Functional Unit. The facility Functional unit is the unit which
the measured variable belongs. In the same loop if devices belong to different FFU , the loop
will be identified with the most relevant unit. Therefore the FFU of concerned devices will be
the same than the loop FFU.

The FFU is the first element to identify the item. This code is mainly used for loop, and
instrument tagging definition.

5.1.5 Train N°
N: Numeric code
Train defines the facilities allowing a process function. This notion is used on numbering
procedure when almost two trains are involved. If there is no train, the relevant code is
omitted.

Train code is numerical character.

Thus only the train number code differentiates the identical instrumentation devices installed
in two different trains.
5.1.6 Measured Variable
A: Alphabetic code

It allows the identification of loop type item.

The list of Measured variables and their codes are reported in Annex 1 (Measured variables
list). The First letter of Function code is generally identical to measured variable.
5.1.7 Function
AAAAA: Alphabetic code

The Function is an alphabetic code with a maximum of 5 characters, issued from the "ISA"
codification, whose list can be found in Annex 3 (Function code table).

Actuated valves and dampers identification shall be in accordance with this procedure.

On the other hand, manual valves without any instrumentation device shall be according
piping identification procedure.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 12 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.1.8 Sequential Number


NNN: Numeric code

Sequential Number shall be organised in a logical manner to reflect the process.


As far as possible, it shall be in a chronological order following the process flow way
identification.
For the same Facility, Sub-facility or FFU the sequential number could only be identical if the
Measure variable is different in the same train.
The sequential number shall be assigned in sequence applying the below rule:
Sequential Number Designation
From 001 to 499 Dedicated to top site instrument tag number

From 500 to 699 Dedicated to hull site instrument tag number

From 700 to 849 Dedicated to top side package instrument tag number

From 850 to 999 Dedicated to hull package instrument tag number


The sequence number for main power generation (FFU 470) shall be assigned in sequence
applying the below rule:

Sequential Number Designation

From 001 to 499 Dedicated to top site power generation instrument tag number

From 500 to 699 Dedicated to hull power generation instrument tag number

From 700 to 899 Dedicated to top side package power generation instrument tag number

From 900 to 999 Dedicated to hull package power generation instrument tag number
The sequence number for HVAC (FFU 660) shall be assigned in sequence applying the below
rule:
Sequential Number Designation

From 001 to 499 Dedicated to top site HVAC instrument tag number

From 500 to 999 Dedicated to hull HVAC instrument tag number


The sequential number for fire and gas (FFU 700) shall be assigned in sequence applying the
below rule:
Sequential Number Designation
From 001 to 499 Dedicated to top site fire and gas instrument tag number

From 500 to 899 Dedicated to hull site fire and gas instrument tag number

From 900 to 949 Dedicated to hull package fire and gas instrument tag number

From 950 to 999 Dedicated to top side package fire and gas instrument tag number
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 13 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.1.9 Suffix
XXX: Alphanumeric code
The suffix code is written down at the end of identification item.

The alphabetic suffix code, starting from A, is dedicated to the duplication of an item which
fulfills the redundancy rules explained below.

The numeric suffix code, starting from one (1), is also used to dissociate similar functions on
the same loop.

The redundancy concerning the equipment (e.g., pumps, drums,…) is not considered for the
tagging of instrumentation devices. Thus, for two (2) redundant equipment on the same train
the instrumentation devices shall be identified with different sequential number.

The Redundancy here described characterizes two or more identical instrumentation devices
within the same train.

The suffix code used for redundancy shall be only used in the following cases:
 When two or more identical instrumentation devices; same measure type, same control
functions are installed in the same equipment.
 The instrumentation devices could have a different construction type, if they are
compliant with the precedent requirement (ex: ionic gas detector, Infra-red gas
detectors, point gas detectors).
 The instrumentation could have different set points if they comply with the first
requirement (ex: Pressure safety valves with different exhaust pressure value).

When the suffix code is not used the relevant digit code is omitted.

Example 1: Redundant pressure safety valves pertain to sub facility 01(FPU), Unit 370,
train 1
Loop name Function
013701P001 013701PSV001A Pressure safety valve duty
013701P001 013701PSV001B Pressure safety valve spare

Example 2: Redundant Flow measures pertain to sub facility 01 (FPU), Unit 370
Loop name Function
013700F001A 013700FE001A Flow element (orifice plate)
013700F001A 013700FT001A Flow transmitter
013700F001A 013700FAL001A Low Flow alarm
013700F001B 013700FE001B Flow element (orifice plate)
013700F001B 013700FT001B Flow transmitter
013700F001B 013700FAL001B Low Flow alarm
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 14 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.2 Instruments Identification


This sub-chapter describes the identification criteria for instrumentation devices.

A loop is a combination of two or more instruments or control functions arranged in order to


measure or control the same process variable.

Each instrument is defined by its Loop and its Function.

5.2.1 Loop Identification


The loop is identified by the Measured Variable.
In case of devices of the same loop are installed on different units, the loop is assigned to the
unit where the transmitter is located.

The process loop identification is codified as follows:


Functional 

Measured 

Sequential 
Unit Code
  Facility 

Number
Variable
Train N°

Suffix
REFERENCE Ann1
STRUCTURE X X X N A N N N A

Redundant Pressure loops in FPU ‐ FFU 530 (Fresh water) Train1
5 3 0 1 P 0 0 1 A
EXAMPLE
5 3 0 1 P 0 0 1 B

5.2.2 Instruments Identification


The identification code of process instrument is as illustrated with examples below:
Measured 

Sequential 
Functional

Function

Number
 Facility 

Train N°

Variable
 Code

Suffix
 Unit

Reference Annex 3
Structure X X X N A A A A A A N N N X X X

All the following examples pertain to FFU 530 (Fresh water) Train1
Pressure Transmitter, PressureController and pressure valve of Loop 5301P001
5 3 0 1 P 0 0 1
5 3 0 1 P T 0 0 1
Example 1
5 3 0 1 P I C 0 0 1
5 3 0 1 P V 0 0 1
Pressure Transmitter and Pressure Indicator 1 & 2 of Loop 5301P002
5 3 0 1 P 0 0 2
5 3 0 1 P T 0 0 2
Example 2
5 3 0 1 P I 0 0 2 A
5 3 0 1 P I 0 0 2 B
Pressure Transmitters and Pressure Indicators pertaining to the 2 redundant Loops 5301P003A and 5301P003B
5 3 0 1 P 0 0 3 A
5 3 0 1 P T 0 0 3 A
5 3 0 1 P I 0 0 3 A
Example 3
5 3 0 1 P 0 0 3 B
5 3 0 1 P T 0 0 3 B
5 3 0 1 P I 0 0 3 B
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 15 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.3 Operated Valves, Functions And Fire & Gas Devices


5.3.1 Operated ON/OFF Valves
As per instruments, the Operated on/off valve is also defined by its Loop and its Function.
For all operated ON/OFF valves the loop code is identical, named X.
In case of different type of valves with the same prefix in the same Unit, a different sequential
number is assigned for each of them (see example below).

Example: Safety valves to sub facility 01 (FPU), Unit 530, train 1


Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 16 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

Functional

Sequential
Measured

Number
Train N°

Variable

Function
Facility

Suffix
Code
Unit
Reference Annex 3
Structure X X X N A A A A A A N N N X X X

5 3 0 1 X 0 0 1
5 3 0 1 E S D V 0 0 1
5 3 0 1 E S D Y 0 0 1
ESDV001 5 3 0 1 Z S H 0 0 1
5 3 0 1 Z I H 0 0 1
5 3 0 1 Z S L 0 0 1
5 3 0 1 Z I L 0 0 1

5 3 0 1 X 0 0 2
5 3 0 1 B D V 0 0 2
5 3 0 1 B D Y 0 0 2
BDV002 5 3 0 1 Z S H 0 0 2
5 3 0 1 Z I H 0 0 2
5 3 0 1 Z S L 0 0 2
5 3 0 1 Z I L 0 0 2

5 3 0 1 X 0 0 3
5 3 0 1 S D V 0 0 3
5 3 0 1 S D Y 0 0 3
SDV003 5 3 0 1 Z S H 0 0 3
5 3 0 1 Z I H 0 0 3
5 3 0 1 Z S L 0 0 3
5 3 0 1 Z I L 0 0 3
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 17 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.3.2 Electrical Users/Motors


As per instrumentation devices, the electrical users are also identified by its Loop and its
Function.
For all motors the loop code is identical, named M.

The identification of motor instrumentation signals could not follow the equipment name
identification. An instrumentation sequential number, different of equipment identification, is
assigned to electrical users.

The function code used for electrical user, composed of by three (3) characters, are listed on
Annex 3 . (Electrical users/motors Function code list).

Example 1: Lean MEG pump to sub facility 01 (FPU), Unit 390


Functional 

Measured 
Unit Code

Sequential
 Number
Function
 Facility 

Variable
Train N°

Suffix

Note
Reference Annex 3
Structure X X X N A A A A A A N N N X X X

3 9 0 M 0 0 5
3 9 0 M H S M 0 0 5 Main/Stand by selection ( Software command)
3 9 0 M H S H 0 0 5 A Remote Start command
Pump 3 9 0 M H S L 0 0 5 A Remote Stop command
013900PA001A  3 9 0 M X S 0 0 5 A Trip command
3 9 0 M Y L ‐ R 0 0 5 A Running Status 
3 9 0 M Y A U 0 0 5 A Available signal/Unavailable alarm
3 9 0 M Y L R 0 0 5 A Remote control selection command
3 9 0 M H S H 0 0 5 B Remote Start command
3 9 0 M H S L 0 0 5 B Remote Stop command
Pump 3 9 0 M X S 0 0 5 B Trip command
013900PA001B  3 9 0 M Y L ‐ R 0 0 5 B Running Status 
3 9 0 M Y A U 0 0 5 B Available signal/Unavailable alarm
3 9 0 M Y L R 0 0 5 B Remote control selection command
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 18 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.3.3 Fire and Gas Detectors/Devices


As all instrumentation devices, the fire and gas detectors and devices are also identified by its
Loop and its Function.

For all Gas detection, the first letter of function is G.


For all Flame devices, the first letter of function is B.
For all Smoke detection, the first letter of function is S.
For all Heat detection, the first letter of function is T.
Refer to Annex 3 for the detailed function codes of the Fire and Gas items.

The fire and gas detectors / devices are identified according to the Fire zone and Fire area they
belong to. Refer to Annex 6 for Fire zone codes.

The following code has to be used:


 Functional

Measured 

Sequential 
Function

Fire Area

Number
Train N°

Variable
 Facility

 Code
 Unit

Reference Annex 3
Structure X X X N A A A A A A N N N N N N

7 0 0 G 0 0 1
Gas detector  7 0 0 G D 1 0 2 0 0 1
 in Fire Zone 1 7 0 0 G D I 1 0 2 0 0 1
Fire Area 102 7 0 0 G A X 1 0 2 0 0 1
Loop 001 7 0 0 G A H 1 0 2 0 0 1
7 0 0 G A H H 1 0 2 0 0 1

7 0 0 G 0 0 2
Toxic Gas detector  7 0 0 G T D 1 0 3 0 0 2
in Fire Zone 1 7 0 0 G D I 1 0 3 0 0 2
Fire Area 103 7 0 0 G A X 1 0 3 0 0 2
Loop 002 7 0 0 G A H 1 0 3 0 0 2
7 0 0 G A H H 1 0 3 0 0 2

7 0 0 S 0 0 1
Smoke Optical
7 0 0 S O D 1 0 4 0 0 1
in Fire zone 1
7 0 0 S A X 1 0 4 0 0 1
Fire Area 104
7 0 0 S A H H 1 0 4 0 0 1
Loop 001
7 0 0 U R 1 0 4 0 0 1
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 19 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.4 Instrumentation And Automation Equipment

As the panels are usually installed into technical room, their identification code depends on
facility functional unit.
Whatever the type of cabinet, the sequential number is different for all cabinets.
 Unit Code 

Circuit type

Sequential 
 Functional

Number
Train N°
 Facility

 Code
 Type

Suffix
Panel
Reference Annex 2
Structure X X X N A A A A A N N N A

ESD ANALOG JUNCTION BOX  in FPU Unit 210 Train1
Example 2 1 0 1 N J T E 0 0 1 ‐
DIGITAL JUNCTION BOX DCS  in FPU Unit 210 Train1
Example 2 1 0 I J T D 0 0 5 ‐
DCS Marshalling Cabinet  IR (Instrument Room)
Example 9 7 0 J J 0 0 1 ‐
DCS System cabinet in IR
Example 9 7 0 J K 0 0 2 ‐
ESD Marshalling Cabinet  in IR (Instrument Room)
Example 9 8 0 J J 0 1 2 ‐
ESD System cabinet  in IR
Example 9 8 0 J K 0 1 1 ‐
Instruments mounted on the panels have their own tags. It does not refer to panel number.

5.4.1 FFU Identification


XXX: Alphanumeric characters

The FFU Identification code is used to codify the localization of instrument devices. That is
used for panels, MCT frame, air manifolds and Control Room Instruments.
• if they receive signals from instruments belonging to a single functional unit, they are
assigned to that FFU.
• if they receive signals from instruments of different functional units they are assigned to the
control room FFU(970/980).
• if they receive signals from processing or generating functional units installed between the
field and the operations room, they belong to the FFU, which includes the equipment and the
instrument that generates or processes the signal.
• if they receive a signal from a FFU that conditions and/or validates only the signal generated
by a local instrument and does not perform other functions, they belong to the unit which
includes the instrument that generates the signal.

5.4.2 Circuit Type


A: Alphabetic character

“I” is used for defining if Intrinsically Safe design.


“N” is used for defining if Not Intrinsically Safe design.

When there is no IS “N” has to be indicated.


Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 20 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.4.3 Panel Type Code


AAAA: Alphabetic code (to be consistent with function code, because both are used to cable
identification).
It is composed of four sub-field :
 The first, made of one alphabetic character, “J” describes Instrumentation and
Automation Equipment as per list in annex 2.( MAIN EQUIPMENT TYPE).
 The second, made of one alphabetic character, describes the type of equipment as per
list in annex 2 (ex: T for junction box).
 The third, made of one alphabetic character, defines the system which the equipment
belongs to, see list in annex 2. This sub-field is not mandatory; it is generally used for
junction boxes.
- Instrumentation and Automation Equipment
D Distributed Control System
E ESD System
F Fire and Gas System
M Metering System
Y Miscellaneous
It has to be noted that the second and third digits will match with the second digit of
the equipment list.
5.5 Individual Cable
The cable identification shall be as follows:
 Facility Functional
 Unit Code 

Sequential 
Cable Type

Function

Number
Train N°

Suffix

Reference Ann 7
Structure X X X N A A A A A A A N N N X X X

Cable mesure IS for 510‐PT‐001 train1
Example 5 1 0 1 J C P T 0 0 1
Cable mesure non IS for 530‐FT‐004
Example 5 3 0 J C F T 0 0 4
Cable Power for 530‐FT‐004
Example 5 3 0 J P F T 0 0 4

The cable type has to follow the table of annex 7.

When individual cable is connected to a field instrument, the sequential number shall be the
same as the sequential number of the instrument, when possible.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 21 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.6 Multi Core Cables To Junction Boxes


The multi core cable to junction box is codified using the junction box identification described
in the table .The structure is as follow:

Panel Type Code
 Functional 

Circuit Type

Sequential 
Cable Type

Number
Train N°
 Facility

Suffix
Unit 

Reference Ann 7 Ann 2


Structure X X X N A A A A A A A N N N A

ESD Multi cable  for Junction Box 
Example 2 1 0 N J C J T E 0 0 1

When multi core cable is connected to a junction box, the sequential number shall be the same
as the sequential number of the junction box, when possible.

5.7 Multi Core Cables Between Cabinets


The structure of the cable way identification code is the following:
Circuit type
Functional

Functional
Sequential

Sequential
Cable type

Panel type

Panel type
Train N°

Num ber

Num ber
Facility

Facility

num ber
Order
U nit

U nit

Ref. Ann 7 Annex 2 Annex 2


Structure X X X N A A A A A A A A N N N X X X A A A A A N N N N N N

9 7 0 N J F J E 0 0 1 9 7 0 J D 0 0 1 0 0 1

9 7 0 N J C J M E 0 0 5 9 7 0 J M D 0 0 5 0 0 1

The first columns “Panel type + sequential number” represent the tag of the cabinet out.
The second columns “Panel type + sequential number” represent the tag of the cabinet in.

Order number is a numeric code, similar to a sequential number, to allow several multi core
cables between Panel A and panel B.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 22 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.8 Air Supply Manifold


The instrument air supply manifold shall comply with the following rule:

 AIR SUPPLY 
MANIFOLD
 Functional

Sequential 
Number
 Facility

 Unit
Reference
Structure X X X A A A N N N

2 1 0 A S M 0 0 1

5.9 Pneumatic & Process Tubing


The pneumatic tubing identification shall use the instrument tag number adding the following
letter to the function will comply with the following rule:

 P: Pneumatic
 Functional

Sequential
TRAIN N°

 Number
Function
TUBING
 Facility

 Type

Suffix
 Unit

Reference
Structure X X X N A A A A A A A N N N X

5 1 0 P S D V 0 0 1

The process tubing identification shall use the instrument tag number adding the following
letter to the function will comply with the following rule:

 PC: Process
 Functional

Sequential
TRAIN N°

 Number
Function
TUBING
 Facility

 Type

Suffix
 Unit

Reference
Structure X X X N A A A A A A A N N N X

5 1 0 P C A I T 0 0 1
Process Tubing identification shall be apply on tubing more than 10 meters length.

5.10 Hydraulic Tubing


The hydraulic tubing identification will use the instrument tag number adding the following
letter to the function will comply with the following rule:

HC: Hydraulic for Control Line


Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 23 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

HR: Hydraulic for Return Line


Functional 

Sequential 
Unit Code

TRAIN N°

Function
TUBING

Number
 Facility 

Suffix
Type
Reference
Structure X X X N A A A A A A A N N N X

5 1 0 H C S D V 0 0 1

5 1 0 H R S D V 0 0 1

5.11 MCT Frame


The MCT (Multi Cables Transit) will comply with the following rule :

Sequential
 Number
ROOM 

MCT

Reference Annex  4 
Structure X X X A A A A N N N N

I E R J M C T 0 0 0 1

5.11.1 MCT Field Code:


AAAA: Alphabetic code
The first letter defines “the Main equipment type” as defined in Annex 2 ; J for
instrumentation.
The three others characters is defined as MCT (Multi Cable Transit).
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 24 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.12 Telecommunication Equipment Identification


The Telecommunication field devices and equipment have the identification code as follows.

Telecom             
  Facility Functional 

Equipment Type 
Sub‐System

Telecom    

Sequential 
Number
 Code

Code

Suffix
Unit

REFERENCE Ann. 8 Annex 9


STRUCTURE X X X X A A N N N A

PA/GA system‐A loudspeaker  with number 557 (by the number, it is installed in LQ, level 3)
Example 9 6 0 E Q N 5 5 7 A
The Facility Functional Unit code for Telecommunication is ‘960’ (Refer to reference document,
ref [2]).

The Telecom Sub-System is used to define the system to which the equipment belongs in The
Telecommunication system. It is one digit alphanumerical, as listed in the Annex 8.

The Telecom Equipment Type code is used to define the specific function of the equipment in
the Sub-System. It is two digits in alphabetical, as listed in the Annex 9.

The Sequential number is three digits numerical. Numbering sequence shall be distingushed
by the area/location of each equipment installed, as below:

No  Area  Sub area  TAG Sequence Number 


Lower Process deck  001 to 050 
Process deck  051 to 100 
Mezzanine deck  101 to 150 
Topside       Top deck  151 to 200 
1  (001 to 
400)  Upper deck  201 to 250 
E&I building  251 to 300 
Laboratory and Workshop  301 to 350 
Others  351 to 400 
Level Ground  401 to 450 
Level 1  451 to 500 
LQ           
2  (401 to  Level 2  501 to 550 
700) 
Level 3  551 to 600 
Level 4  601 to 650 
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 25 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

No  Area  Sub area  TAG Sequence Number 


LQ roof, telecom tower & helideck  651 to 700 
HULL MAIN DECK OUTDOOR  701 to 750 
AFT MS HULL MAIN DECK  751 to 800 
HULL          AFT MS DECK ‐1  801 to 850 
3  (701 to 
999)  AFT MS Double Bottom  851 to 900 
FWD MS DECK ‐1  901 to 950 
FWD MS Double Bottom  951 to 999 

The Suffix is one digit alphabetical, added for the identification of same type of equipment
installed in pararel (as usually used in redundancy configuration).

5.13 Telecommunication Cable Identification


5.13.1 Individual Cable
The Individual cable between cabinet/marshalling and telecom equipment or junction box and
telecom equipment shall be defined as follows.
Telecom Sub‐System

Telecom Equipment 
 Facility Functional
 Unit Code 

Sequential 
Cable Type

Type Code

Number

Suffix

Reference Ann 7 follow the tagging of destination telecom equipment


Structure X X X A A X A A N N N A

Individual cable to CCTV Camera number 019 located in topside
Example 9 6 0 T N F A M 0 1 9
When the Individual cable connected to a Telecom equipment, the cable tag shall follow the
tagging of destination telecom equipment. And then added with its cable type.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 26 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.13.2 Cable in PAGA system


PAGA system consist of loop configuration, the loop shall be identified with the ‘loop number’
as follows:

Telecom Sub‐System

Telecom Equipment 

Loop Identification
 Facility Functional
 Unit Code 

Sequential 
Cable Type

Type Code

Number

Suffix
Reference Ann 7 follow the tagging of destination telecom equipment
Structure X X X A A X A A N N N A N N

Individual cable of PAGA system A to speaker 019 in loop 15
Example 9 6 0 T N F A M 0 1 9 A 1 5

5.13.3 Multipair Cable to Junction Box


The Multipair Cable to Junction Box shall be identify as follows:
Telecom Sub‐System

Telecom Equipment 
 Facility Functional

Identification
Cable Order 
 Unit Code 

Sequential 
Cable Type

Type Code

Number

Suffix

Reference Ann 7 follow the tagging of destination junction box


Structure X X X A A X A A N N N A N N

Multipair cable, cable order 17, from PA/GA system A cabinet to Junction Box number 031
Example 9 6 0 T R E Q U 0 3 1 A 1 7
When the Multipair cable connected to a Junction Box, the cable tag shall follow the tagging of
destination Junction Box. And then added with its cable type and cable order number as shown
in the example above.

5.13.4 Cable Between Cabinets


Cable between Cabinets shall be identify as follows.
Telecom Sub‐System

Telecom Sub‐System
Telecom Equipment 
 Facility Functional

Identification
Cable Order 
 Unit Code 

Sequential 

Sequential 
Cable Type

Type Code

Number

Number
Suffix

Suffix

Reference Ann 7
Structure X X X A A X Q G N N N A X N N N A N N

Cable order 07, from LAN WAN Cabinet 015 to Distribution Cabinet 017
Example 9 6 0 T F G Q G 6 1 5 G 6 1 7 0 7
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 27 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

The Multipair cable identification shall consist of the ‘from cabinet tag’ and the ‘to cabinet tag’,
inserted with the cable type and cable order number. The ‘order number’ shall be used when
there are several cables connected between cabinets.

5.14 Instrument Wire Marker Identification


5.14.1 Cable Termination in Instrument Field Device
Wire marker identification for cable termination ends in field device as follows:
Structure: Instrument Tag Number / (Terminal Name)
Example: cable termination for instrument 013601PIT101
013601PIT101/(+)
013601PIT101/(-)

5.14.2 Cable Termination in Instrumentation and Automation Equipment


Wire marker identification for cable termination ends in instrumentation and automation
equipment as follows:
Structure: Instrument Tag Number / Terminal Block Name (Terminal Name)
Example: cable termination for instrument 013601PIT101 in junction box and
marshalling/system cabinet
013601PIT101/TB(1)
013601PIT101/TB(2)
013601PIT101/TBAI01(1)
013601PIT101/TBAI01(2)
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 28 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.15 Terminal Strip inside the ICSS Marshalling Cabinet


5.15.1 Terminal block for the cable from junction box to marshalling cabinet
The terminal strip number shall be the same with junction box number.

5.15.2 Terminal block for the cable from package cabinet to marshalling cabinet and there is
one cable between them
The terminal strip number shall be the same with package cabinet tag number.

5.15.3 Terminal block for the cable from package cabinet to marshalling cabinet and there are
several cables between them
Terminal strip number shall be “package cabinet tag number-the last number of the cable”.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 29 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

5.16 ICSS Wiring


ICSS wiring between each component in the cabinet use term “from/to”.
Example:
1. Cable from FTA to IOTA
From : +12R-XFTA-V21-TB1 in cabinet 019800JJ006
To : +4R-IOTA-V24-CN1 in cabinet 019800JK004
Cable no : +12R‐XFTA‐V21‐TB1/+4R‐IOTA‐V24‐CN1

2. Ethernet Communication Cable


From : +1F‐UCCP02‐COM1.2A in cabinet 017000JK001
To : +1R‐SW‐H21‐A‐PORT in cabinet 019800JV001
Cable no : +1F‐UCCP02‐COM1.2A/+1R‐SW‐H21‐A‐PORT
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 30 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

6 LABELLING PRINCIPLE
6.1 Instruments labeling

All instruments must have two labels, on the instrument itself and another screwed on the
support of the instrument.

The attached Label on the Instrument shall be made of an engraved stainless steel plate; the
letters shall be 5mm high, attached with SS316 tie wrap on the instrument.

The Label fixed on the support shall be made an engraved Traffolyte plate, the letters shall be
15mm high and the plate fixed with stainless steel screw on the instrument support.
All the Traffolyte plate shall be coloured depending on the system to which the instrument is
connected, according to the below table.

SYSTEM WHERE IS TEXT COLOR FIXED PLATE BACKGROUND


CONNECTED INSTRUMENT

ESD BLACK YELLOW

F&G BLACK RED

DCS BLACK WHITE

TELECOM FIELD EQUIPMENT BLACK WHITE

6.2 Cables and Tubes labeling

All Outdoor cables shall be tagged at the termination ends. Punched SS316L label attached
with stainless fasteners is used.

7 TABLE OF ANNEXES

Annex 1: Measured Variable list


Annex 2: Instrument equipment type
Annex 3: Function code Tables
Annex 4: Room list
Annex 5: Plant area identification
Annex 6: Fire & gas zone
Annex 7: Service and Function of cables
Annex 8: Telecommunication Subsystem
Annex 9: Telecommunication Equipment Type Code
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 31 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

ANNEX 1 - MEASURED VARIABLES LIST

Measured
Description
variable
A Analysis
B Burn/combustion/Flame
C Corrosion
D Density
E Voltage
F Flow rate
H Hand
G Gas
I Current
J Power
K Time
L Level
M Moisture/motor
O
P Pressure
Q Quantity
R Radiation
S Speed/frequency
T Temperature
U Multivariable
V Vibration/machinery analysis
W Weight/force
X Danger/safety/emergency/Miscellaneous/On_Off actuated valves
Y Event/state/presence
Z Position/dimension
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 32 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

ANNEX 2 – INSTRUMENTATION EQUIPMENT TYPE


Here after is reported a technical classification based on panel type and subtype.

 MAIN EQUIPMENT TYPE

A TELECOMMUNICATION EQUIPMENT
B NOT USED
C MISCELLANEOUS MECHANICAL EQUIPMENT AND FILTERS (Not Online) (Hvac Filters
Excluded)
D DRILLING AND COMPLETION EQUIPMENT
E ELECTRICAL EQUIPMENT
F HEATERS, FURNACES AND FLARING EQUIPMENT
G SANITATION, CONDITIONING, HEATING AND H.VAC. EQUIPMENT
H HEAT TRANSFER EQUIPMENT
I NOT USED
J INSTRUMENTATION AND AUTOMATION SYSTEM EQUIPMENT
K COMPRESSORS, BLOWERS AND NON "HVAC" VENTILATORS
L IDENTIFIED ON-UNE BULKS
M NON ELECTRICAL PRIME ENGINES AND MISCELLANEOUS
N SPECIFIC MAINTENANCE OBJECT
O NOT USED
P PUMPS
Q TELECOMMUNICATION EQUIPMENT
R VALVES
S SAFETY, ESCAPE AND FIRE-FIGHTING EQUIPMENT
T TANKS
U SUBSEA EQUIPMENT
V PRESSURE AND SEPARATOR EQUIPMENT
W STEEL OFFSHORE STRUCTURES AND FACILITIES
X MISCELLANEOUS
Y MATERIAL AND MISCELLANEOUS PRODUCT HANDUNG EQUIPMENT
Z INDUSTRIAL BUILDINGS AND STEEL STRUCTURES
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 33 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

 INSTRUMENTATION AND AUTOMATION EQUIPMENT SUB-TYPE (J)

JA Analysis equipment
JB Centralized control board (conventional and ancillary cabinet)
JC Local Control Board
JD Remote Control Board
JE Emergency shut down system equipment (ESD)
JF Fire and Gas detection equipment other than instruments listed in annex 3 and equipment
listed in class S
JG Not used
JH Host and personal computer, computer terminals
JJ Interface cabinet (optical or galvanic insulation/ intrinsically safe) /, marshalling cabinet
JK Logical Cabinet (Relay/PLC)/system cabinet
JL Alarm Panel/Mimic Panel
JM Metering and proving equipment, including weighing machines
JN Not used
JP Control panel (pneumatic and hydraulic)
JQ Thermocouple cable
JR Not used
JS Synoptic panel
JT Junction box
JU Supervision control and data acquisition (SCADA) equipment
JV Distributed process Control System equipment (DCS)
JW Well head Control Panel
JX Flare ignition panel
JY Miscellaneous instrumentation and automation equipment
JZ Extinguishing gas panel, Deluge panel, Firefighting panel.

 AUTOMATION SYSTEMS

D Distributed Control System


E ESD System
F Fire and Gas System
M Metering System
Y Miscellaneous
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 34 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

ANNEX 3 - FUNCTION CODE TABLES


 Function Code table for instrumentation devices (w/o F&G)
This section specifies the differences (in bolt and italic style) from the ISA Coding system and
the attributes of the fields left free by the ISA Code (Unclassified Variable).
For more details refer to the following identification letters table.

POSITION OF LETTER IN FUNCTION CODE


LETTER
1ST LETTER INITIATING SUBSEQUENT LETTERS-
2ND LETTER FUNCTION
VARIABLE FUNCTIONS
A Analysis (Note 1) Alarm (Note 5) Alarm
B Burner, Combustion, Blow down,
Flame
C Corrosion Control Control
D Specific Gravity, Density Differential, Interface, Differential, Interface,
Detector Detector
E Voltage Sensor, Primary Element
F Flow Rate Ratio
G Gas Detection (explosive or toxic) Gauge (local indicator) Gauge (local indicator)
(Note 2)
H Hand High (Note 5), Open,
Start/ON (Note 8)
I Current (Electrical) Indication Indication
J Power
K Time Control Station Control Station
Low (Note 5), Closed,
L Level Lamp
Stop/OFF (Note 8)
M Moisture, Electrical Motor (as prefix Middle, intermediate
to initiating variable) (Note 9)
N
O Orifice, Restriction,
P Pressure, Vacuum
Q Quantity Totalize, Integrate Totalize, Integrate
R Radiation, Record (Note 6), Reset Remote
S Speed, Frequency, Smoke detection Switch, Safety Switch, Safety
T Temperature Transmitter, Test Transmitter
U Multivariable, Multifunction Audible Local
V Vibration, Mechanical Analysis Valve Valve
W Weight, Force Well
X On/Off valves (Note 10), Sequence Automatic Control
Function
Y State, Event, Presence, Siren, State, event, Compute,
Beacon Convert
Z Position, dimension, Limit Switch
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 35 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

Note 1: Analysis (letter A as initiating variable). The letter “A” covers analyzers not described
by specific letters.

Note 2: Gas detection (letter G initiating variable), Gas detection instruments shall be named
using codes defined in annex 3.

Note 3: /

Note 4: /

Note 5: Alarm (letter A in second position)


For analogue measurement, the letter A will be associated with the letters “L” or “H”, “LL” or
“HH”.
Process functions shall normally be associated with the single modifying letters “L” or “H”.
Trip functions shall always be associated with the double modifying letters “LL” or “HH”.

Note 6: Record (letter R in second position)


The record function “R” is used only where this function is provided by an external recorder.
This code is implicit when it is performed by an automated system.

Note 7: /

Note 8: On/Off status (letter H&L as third or subsequent letters)


In case of valves or open/closed devices: H means open and L closed
In case of running machines: H means running and L stopped

Note 9: Electrical motors (letter M as initiating variable)


Tags of electrical users shall start with prefix M before initiating variable

Note 10: On/Off valves (letter X as initiating variable)


Tags of ON/OFF valves shall start with prefix X before initiating variable

The number of codified functions shall be limited as much as possible to two. As a general rule,
it is recommended that the number of letters is limited, in order to indicate only the process
variable and the actual main function instrument. Alarm threshold shall not be considered as
an instrument, but shall be a part of the associated device, which generates the function.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 36 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

 Electrical users/motors Function code list


Control and safety Motors data are named using the following Function codes:

Function Code Description Note


HSH Start command Signal/Alarm (software) (Note)
HSHL Start/Stop command Signal/Alarm (software) (Note)
HSL Stop command Signal/Alarm (software) (Note)
YLR Remote/Local selection Signal/Alarm (software) (Note)
HSM Main/stand by selection Command (Software) (Note)
HSA Auto/Manu command Command (Software) (Note)
HSR Reset signal Command (Software) (Note)
SIC Speed control set point Signal/Alarm (software) (Note)
XS Trip command Command (DO, Trip = 0)
YL-R Running status Signal/Alarm (software) (Note)
YAU UnAvailable status Signal/Alarm (software) (Note)
YXA Tripped status Signal/Alarm (software) (Note)
YAD Discrepancy status Signal/Alarm (software) (Note)
YA-F Alarm Fault Signal/Alarm (software) (Note)
II Current indication Signal
WI Power indication Signal
SI Speed indication Signal

Note:
Software tags are not mandatory; when these tags are automatically generated by ICSS
function block, the native ICSS tags shall be used.
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 37 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

 Fire and gas detectors and equipment Function code list:

Fire & Gas detector shall be named using the function Alarm Signalling
codes defined here after: Fire and Gas table
Detection type Detect Pre- Alarm Reset
Fault alarm
Gas detection
Gas detector (infrared, point) GD
TOXIC GAS (H2S) GTD
Beam Gas detector GBDT/
GAH GAHH /
(TRANSMITTER/RECEIVER) GBDR GAX
Catalytic gas detector GCD
(flammable gas including HYDROGEN )
Oxygen Gas Detector GOD GAL / /
Flame detection
Flame UV & IR and Imaging flame BED
detection
Flame IR (Infrared, Single and Multi BID BAX / BAHH /
frequency Infrared)
Flame UR BUD
Fire detection
Smoke Ionisation SID
/
Smoke Optical SOD UR
/
Smoke Combined SCD SAX SAHH
Early Warning Smoke Detection SAH
SAD /
System - Aspirating Smoke Detector
Heat Fixed Temperature Type
TFD
(Thermostatic, Fusible plug, Frangible /
bulb (Sprinkler))
Rate Of Rise Temperature TRD TR
/
Rate Compensated Temperature TRCD
/
TAX TAHH
Linear Heat Detector(heat sensitive
TCD /
cable) /
Low Temperature Detector For
TLD /
Liquefied
/
(Temperature sensor or Leak Detection
by Fibre optic)
Miscellaneous Fire & Gas alarms
Manual Alarm for fire HSB
/ /
Manual Alarm for Emergency Shutdown HXB
/ /
(ESD function, PSD/LSD functions)
UAX UAHH
Abandon Push Button HAB / /
Man Overboard Push Button HMOB / /
Alarm Status Beacon YL
/ /
Alarm Status Horn or Horn and Beacon YS YAX YAHH
/ /
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 38 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

ANNEX 4 – ROOM LIST

Room Code Description


CCR Central Control Room
IER Instrument Equipment Room
IR Instrument Room

ANNEX 5 - PLANT AREA IDENTIFICATION

Code Description
P1 to P10 Module Portside
S1 to S10 Module Starboard side
PR Pipe Rack
US Utility Space
HD Hull Deck
FL Flare
HU Hull
AM Aft Machinery space
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 39 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

ANNEX 6 – FIRE ZONE CODES


The Fire Zone is a plant area division dependent of Fire and Gas risk analysis.
The Fire Zones have been subdivided into several Fire Areas.

Fire zones and fire areas shall be marked in a site plot plan.

Fire zone and fire area codes shall be added as an attribute to all fire and gas instrument (FFU
700), here below the list of fire zones and fire areas as per fire and gas detection philosophy.

Fire zone Description Fire area identification


FZ-0: Fire zone 0 Hull Deck & Lower Process Deck From 001 to 099
FZ-1: Fire zone 1 Process Deck & above Process Deck From 101 to 199
FZ-2: Fire zone 2 Living Quarters, Helideck & Telecom area From 201 to 299
FZ-3: Fire zone 3 E&I Building From 301 to 399
FZ-4: Fire zone 4 Aft Hull Machinery Space From 401 to 499
FZ-5: Fire zone 5 FWD Hull Machinery Space From 501 to 599
FZ-6: Fire zone 6 Pipe tunnel From 601 to 699
FZ-7: Fire zone 7 Secondary Muster Area From 701 to 799
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 40 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

ANNEX 7 – SERVICE AND FUNCTION OF CABLES

┌───────── SERVICE
│ ┌───────────────── FUNCTION
│ │
P Power cable
B < 1000 V rated cables for normal or essential supply
G < 1000 V rated cables for emergency supply
H > 1000 V rated cables for normal or essential supply normal
L lighting circuit cables
V < 1000 V cables for safety system supply
C Control and cathodic protection electric cables
A signal alarm cables
C control cables
M measurement cables
P cathodic protection cables
Z not otherwise specified
J Instrumentation Cables
T Coaxial cables
C Instrumentation cables (alarm, status, control,
measurement,etc.)
F Fibre optical cables
R Thermocouple - Thermo-resistance measurement cables
Y Solenoid Valves cables
P Power supply cables
U Pulse or Frequency signals cables
Z Not otherwise specified
T Telecommunication cables
B Indoor Telephone signals/cables
E Ethernet Cable
O Outdoor Telephone signals/cables
C Coaxial cables
F Fibre optical cables
L Loudspeaker cable
M Multifunction cables
Q Beacon cables
P Power Supply cables
G GPS devices cables
N CCTV Cameras cables
X ACS and IDS device cables
Z Not otherwise specified
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 41 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

ANNEX 8 – TELECOMMUNICATION SUBSYSTEM


Code Description
A SDH (SYNCHRONOUS DIGITAL HIERARCHY), includes optical fiber,
transmission equipment and concentration equipment (multiplexer)
B TELEPHONE, includes private branch exchange (PABX), telephone,
commutators, and telephone cables.
C MTRS (MOBILE TRUNK RADIO SYSTEM), includes digital radio system
UHF (400 MHz or 800 MHz).
D IDS (INTRUSSION DISTRIBUTION SYSTEM), includes management and
transmission of data peripheral sensor cable.
E PA/GA (PUBLIC ANNOUNCE/GENERAL ALARM), includes amplifiers,
loudspeakers, and flashing beacons.
F CCTV (CLOSED CIRCUIT TV), includes cameras, monitors, and video
transmission system.
G LAN/WAN (LOCAL/WIDE AREA NETWORK: includes LAN switch, router,
IP-PBX, Firewall, Fiber and Ethernet cable)
H ACS (ACCESS CONTROL SYSTEM)
I DATA NETWORK
J ENTERTAINMENT SYSTEM, includes system for reception and diffusion
of satellite and terrestial TV and radio.
K LOS (LINE OF SIGHT), includes radio equipment and parabolic antenna
L METEOROLOGICAL SYSTEM
M NDB (NON-DIRECTIONAL BEACON)includes transceiver, control units,
antennas
N VHF-AM (VERY HIGH FREQUENCY-AMPLITUDE MODULATION), includes
two ways radio, control units, and antennas
O GENERAL RADIO SYSTEM
P VHF-FM (VERY HIGH FREQUENCY-FREQUENCY MODULATION), includes
two ways radio, control units, and antennas
Q MF/HF-SSB (HIGH FREQUENCY-SINGLE SIDE BAND), radio analogic
system, includes two way radio, control unit, antennas.
R SITE GATHERING FIBER OPTIC NETWORK, it includes converters for
transmission on optical fiber of scada, voice, cctv, and ids signal.
S HOT LINE
T INTERCOM
U NMS (NETWORK MANAGEMENT SYSTEM)
V RURAL RADIO SYSTEM
W SATELLITE SYSTEM
X VOICE RECORDING SYSTEM
Y PERSONAL TRACKING SYSTEM, MUSTER POINT CHECKING SYSTEM
Z MISCELLANEOUS
1 MASTER CLOCK
2 VESSEL TRACKING SYSTEM,
3 ELECTRICAL
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 42 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

Code Description
4 NAVIGATIONAL SYSTEM, includes Gyro, DGPS, Compass & Radar

ANNEX 9 – TELECOMMUNICATION EQUIPMENT TYPE CODE


Code Description Note
AA ACS EQUIPMENT
AB CONSOLE ACCESS PANEL
AC EXTERNAL TELEPHONE AND SET PORTABLE
AD DISTRIBUTION PANEL (MDF, IDF) AND FRAME PANEL
AE SWITCH HUB
AF FO CONVERTER
AG GPS EQUIPMENT, GYRO EQUIPMENT
AH SPLITTER
AI ROUTER
AJ EQUIPMENT RACK
AK AMPLIFIER
AL CONVERTER E1-ETHERNET
AM CAMERA
AN CCTV EQUIPMENT
AO VOICE GATEWAY
AP TV MONITOR
AQ E/O VIDEO CONVERTER
AR IDS CENTRAL EQUIPMENT
AS IDS PERIPHERAL EQUIPMENT
AT BADGE READERS
AU TURNSTILES
AV BADGES
AW WORKSTATION PC
AX SERVER, IP-PBX, FIREWALL
AY MULTIPLEXER, MULTISWITCH, COMBINER
AZ HELIDECK MONITORING EQUIPMENT: MRU (Motion
Reference Unit)
QA COMMUNICATION ANTENNA, TRANSCEIVER, VSAT
ANTENNA, UHF BDA
QB NON-DIRECTIONAL BEACON EQUIPMENT
QC TELEPHONE CONSOLE
QD MODEMS, MODULATOR
QE AERONAUTICAL AND RADIO STATION EQUIPMENT:
VHF FM, VHF AM, UHF and MF/HF Fixed stations
QF FIBER OPTIC EQUIPMENT (FO PATCH PANEL)
QG TELECOMMUNICATION CABINET
QH AIS EQUIPMENT
Revision Index Sheet of
220801DIST13009 Sheets
Rev Validity
Number Status
Eni Muara Bakau B.V. 43 of 43
Wiring And Tagging Rules 03 EX-DE
Specification

Code Description Note


QI RADAR EQUIPMENT, RACON
QJ MOBILE TRUNKED RADIO
QK DOOR FURNITURE
QL LOCAL AREA NETWORK (LAN)
QM INMARSAT SYSTEM
QN LOUDSPEAKERS
QO RADIO HANDSET
QP TELEPHONE EQUIPMENT
QQ FLASHING BEACON
QR RADIO LINK EQUIPMENT (LOS)
QS SATELLITE COMMUNICATION EQUIPMENT
QT TROPOSCATTER
QU JUNCTION BOX
QV VOICE INTERCOMMUNICATION SYSTEM (PAGA)
QW METEOROLOGICAL EQUIPMENT
QX TELECOM SOCKET, OUTLET: TELEPHONE/LAN
SOCKET, TV/RADIO OUTLET
QY ENTERTAINMENT SYSTEM: DVD PLAYER, BED HEAD
RADIO, DECODER, BLUE RAY PLAYER
QZ MISCELLANEOUS COMMUNICATION SYSTEM