Professional Documents
Culture Documents
Copyright
The copyright of this procedure, together with all confidential information contained herein is
the sole property of SEPCOIII Haveli Bahadur Shah 1230 MW Combined Cycle Power Plant.
It may be copied in full or in parts only by the Management / personnel and only for the
purpose of Company related activities. Disclosure and copying of any information contained
within this procedure to any person (s) outside the employee of company without written
permission/authorization of the Management Representative or Plant Manager is strictly
prohibited.
Page 1 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
Amendment Sheet
Section Amendment
Date Revision # Amendment Detail Signatures
Affected Approved by
Page 2 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
Table of Contents
2.0 REFERENCES....................................................................................................5
3.0 PREREQUISITE..................................................................................................5
6.0 PROCEDURE.....................................................................................................7
8.0 APPENDICES...................................................................................................11
Page 4 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
NOTE
Never put the vacuum pump or ejector in to service prior supplying the gland steam to the
turbine seals otherwise air will ingress through the seals, Dust particles can be the reason to
damage the seals
2.0 REFERENCES
CAUTION
It is the duty of every person who may be concerned with work on or adjacent to the System to make
themselves conversant with the Safety Rules and appropriate support documents. In addition all persons
have a general duty to be conversant with and to observe statutory requirements relating to any
activities with which they have an involvement.
3.0 PREREQUISITE
Page 6 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
Page 7 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
The following precautions and limitations apply specifically to the operation of the steam
turbine vacuum system.
In addition to the requirements for establishing Safety from the System.
It is fundamental that prior to work commencing the hazards present shall be
recognized, the risks assessed and the necessary control measures implemented to
reduce the risk to an acceptable level.
Exposed parts of all rotary equipment must be guarded properly.
Electrical and mechanical items of Plant and Apparatus are interconnected to form electro-
mechanical Systems, these Systems contain inherent Dangers. The Systems are designed so
that when they are in their normal operating mode, they may be operated without Danger if
safe working procedures and suitable equipment are correctly used.
Use caution when handling chemicals. Wear protective clothing and use a breathing
apparatus when handling high concentrations of chemicals.
Do not wear contact lenses when handling chemicals. Use rubber aprons, rubber
gloves and splash proof goggles or a face shield.
All personnel handling the system should be familiar with the following:
Equipment Operating Procedures.
Evacuation Procedures in emergency.
Leak/Spill Emergency Response Procedures
First Aid and Rescue Procedures
Location and use of Fire Fighting Equipment
Proper Use of Protective Clothing
Proper Use of Breathing Apparatus
Location of safety showers and eyewash stations
Prearranged Procedures for Emergency Medical Care
CAUTION
In addition to the items listed above, it is expected that every Operator use his experience,
technical knowledge, safety considerations, and industry acceptable techniques when operating
plant equipment.
Page 8 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
CAUTION
No persons shall be engaged in work activities unless they possess sufficient knowledge and/or
experience to avoid Danger, or are supervised as appropriate, having regard to the nature of the
work. They shall have received training for and be conversant with the roles they are going to
perform.
6.0 PROCEDURE
Operating liquid
Demin water is used as operating liquid. Operating liquid is continuously discharged
together with the compressed gas. Therefore, the liquid ring must be replenished
continually with fresh, cool operating liquid. In addition to its actual function of producing
the liquid ring, the operating liquid also has the task of dissipating the heat developed by
compression and seals the gap between the impeller and the port plates and, if necessary,
cools the inner parts of the shaft seal. This is why use should be made of Operating liquid
that is as cool as possible (e.g. water at 15 °C).
The operating liquid must be devoid of solids such as sand as otherwise extreme wear will
occur in the machine. Suitable filters or strainers must be fitted if the operating liquid
contains impurities. If there is a danger of calcium deposition precautions have to be taken
Page 9 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
for the operating water and the sealing water, e.g. water-softeners or ionic accelerators.
Shaft sealing liquid, demineralized water.
Temperature: Normally 21 °C (limit range 0 °C to 65 °C); or operating temperature at least 10
K, below boiling point. Pressure: 0.1 to 0.3 bar above discharge pressure.
START-UP:
When we start Function Group of Evacuation System both vacuum pump starts in parallel.
When motor switched on, and cooling water valve and system inlet valve opened, ELMO-F is
running, and after water ring established in the pump, the system turns into working
condition.
Hogging operation (all vacuum pumps operate parallel to reduce evacuation time)
In hogging operation, the air is extracted from the condenser into suction connection of all
the vacuum pumps via suction line and inlet butterfly valve (ISV1).
Steps for Operation of Working and Standby pump; - In this operation both the pumps are
working.
Initially suction isolation valve ISV1 (10MAJ81/82AA003) is in closed condition.
PT (10MAJ81/82CP003) will sense the condenser pressure in mbar.
Both the pump (working + Standby) will start.
PS (MAJ81/82CP001) (PS1) will sense the pressure 0.130 kg/cm 2 (abs)
For Condenser Vacuum pump. The same signal will detected by DCS as per set point
mentioned above.
After getting signals from DCS the solenoid valve will open and instrument air will directly
expose to actuator of inlet valve (10MAJ81/82AA003) (ISV1) and the inlet valve will open for
both the pumps (working + standby).
Inlet Valve (ISV1) pneumatically actuated shut off valve. Due to the actuation action of
actuator, the Inlet valve (10MAJ81/82AA003) (ISV1) will open for both the pumps (working
+Standby.
In hogging operation both the pumps (working + standby) remains working till the system
pressure reaches to the value of 0.180Kg/cm2 (abs) which will sense by the PT
(MAJ81/82CP003).
The stand-by vacuum pump will stop if the goes below the set point.
Page 10 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
The holding operation will start after achieving the condenser pressure 0.180 Kg/cm2 (abs)
in the condenser which sense by PT (MAJ81/82CP003)
In this operation only one vacuum pump is in operation. PT (MAJ81/82CP003) will send the
signals to DCS for stopping the stand by pump. In holding operation only one pump will run,
until the system pressure reaches up to 0.100 kg/cm 2 (abs). The single vacuum pump will
maintain the pressure 0.100 Kg/cm 2 (Abs) in the condenser system. If the system vacuum
pressure rises above 0.100 Kg/cm2 (Abs), which will sense by the PT (MAJ81/82CP003), will
send a signal through DCS to start the standby Pump.
CAUTION
When work is to be carried out on Plant, the primary means of achieving safety is by isolation from
the System(s) followed by draining, venting, purging and control of stored energy as appropriate,
except when the work requires the Plant to be energized. For these exceptions the means of
achieving safety is by the application of specialized Approved procedure.
CAUTION
Never stop the turbine gland steam seal supply at condenser full vacuum the cold air will ingress
through hot turbine gland seals, force cooling will happen causing rubbing of seals and finally
damage can accrue.
SHUT DOWN
1. Stop the driving motor (10MAJ81/82AH001) of vacuum pump (10MAJ81/82AP001).
2. Close inlet valve (10MAJ81/82AA003) to assure the needed starting condition.
3. Close the cooling water valve.
Page 11 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
After shutting down, pump (10MAJ81/82AP001) and separator (reach the water level
balance automatically by working liquid piping when you want to drain the pump, open all
the related connections.
Caution: For long time shutting down (1 month and/or longer), you must drain the pump.
NOTE
After the vacuum system has been stopped and condenser vacuum is almost been killed, the
gland steam supply and other system of gland steam can be put off.
Page 12 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
The active vacuum breaker function is reported at the operator station by an alarm. The
function remains energized until turbine speed drops to 50 % of the rated speed or until the
vacuum-breaking valve is closed manually.
Vacuum breaking valve moves automatically into a partial stroke position when:
• Partial vacuum break memory is set.
• Turbine rotor speed above 50 % of nominal speed.
• Backpressure in the condenser is below MAX1 (MAX1 = condenser pressure high alarm 0.2barA).
During shut down the following has to be supervised:
• Vacuum breaking valve opens and closes under the conditions described above.
• Sealing water system switched-on.
• Full vacuum break below 10 % nominal rotor speed
N/A
8.0 APPENDICES
8.1 APPENDIX-1 Pre start check list for valves line up.
8.2 APPENDIX-2 Pre start check list for instrumentation.
8.3 APPENDIX-3 Pre start check list for Electrical distribution.
APPENDIX-I
Page 13 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
APPENDIX II
Page 14 of 15
SOP FOR CONDENSER VACUUM SYSTEM
DOC. # SEPCOIII-HBS-OPR-SOP-29 Issue # 00 Issue Date: 26-05-2019
APPENDIX-III
Page 15 of 15