Professional Documents
Culture Documents
ELECTRICAL TESTS:
Measured Value in
Phase Remarks
Micro Ohm
R-R’ 11 OK
Y-Y’ 11 OK
B-B’ 14 OK
Applied voltage: 5 KV DC
3. TIMING TEST:
Signature: Signature:
Current in
Sequence R Y B
DC supply Amps
Close 51.80 51.80 51.90 2.79
Criteria range:
Closing time = 65(+7 -20) ms
Opening time = 48 (+6 -20) ms
5. BREAKER COUNDER: