You are on page 1of 1

Sound Insulation Prediction (v9 .0.

5)
Program copyright Marshall Day Acoustics 2017

- Key No. 3534


Margin of error is generally within Rw +/- 3 dB
Job Name: SE C H E AD Q U ART E R - RIY ADH
Job No.: ME C H . RO O M - L INING Page No.: 1 Notes: C onsiderable Flank ing Path
Date: 13 Sep 17 Initials:khalid A. All Joints, G aps and Penetrations
Shall be acoustically treated
File Name: insul

Rw 66 dB
D nTw 68 dB

ISO

STC 66
50 mm
275.0 mm O ITC 55

System description
AST M
Panel 1 : 1 x 200.0 mm Concrete (ρ:2340 kg/m3,E:11GPa,η:0.05)
Cavity: Steel stud (25g): Stud spacing 600 mm , Infill Arabian F ibreglass Insulation (16kg/m3) Thickness 50 mm (ρ:16 kg/m3, Rf:8400 Pa.s/m2 )
Panel 2 + 1 x 12.5 mm mm U SG BO RAL Gypsum Board (ρ:893 kg/m3, E: 6GPa, η:0.01, ps: 11.3 kg/m2, fc: 2815 Hz

Mass-air-mass resonant frequency =54 Hz

Panel Size 2.7x 4 m; Mass 487.6 kg/m2

frequency (Hz) R(dB) R(dB)


50 36
63 34 36
80 41
100 48
125 53 51
160 54
200 56
250 59 58
315 61
400 64
500 67 66
630 69
800 72
1000 74 73
1250 76
1600 78
2000 80 79
2500 79
3150 91
4000 95 94
5000 98

You might also like