MARY K. WEES
HDR Techserv, Inc., Omaha, Nebraska
229
not discussed in this paper owing to the special testing justments are made to the actual data, as required, to
criteria adhered to by regulatory agencies. result in a solid waste composition comparable to that
Private waste-to-energy contractors are willing to used to verify the performance guarantees. If after
guarantee plant performance as long as the solid waste initial acceptance testing of the plant a dispute arises
quality conditions on which the design is based do not over the performance, either party may have the option
vary. Typically, the throughput guarantee will be as of asking for a retest of the plant in order to check
sociated with a specific range of solid waste heating performance. Retesting is a very time consuming and
values, while the energy generation guarantee is ref expensive process. Furthermore, by the time the test
erenced to a specific solid waste heating value and is actually run, the waste in question will already have
composition (Le., moisture, combustibles, and inert been burned or the problem with the plant may have
materials). already been fixed, so that the retest will not have
Unless the plant experiences obvious equipment accomplished its purpose.
breakdowns and extended downtime, failure to meet As an alternative to this, the lower heating value
performance guarantees may be disputed as to the (LHV) of the waste can be used to reference perform
cause (solid waste quality or equipment efficiency). ance guarantees. Lower heating value is the higher
Taking samples of the solid waste and testing for the heating value less the heat loss from the moisture in
heating value in a laboratory raises several major con the flue gas resulting from the moisture in the solid
cerns regarding the question of whether a waste sample waste and the moisture from burning hydrogen in the
is representative of the entire waste stream. The num solid waste. During initial acceptance testing, all the
ber of samples required, the location of sampling (e.g., necessary data are taken to determine the higher heat
top, bottom or middle of the storage pit), individual ing value of the waste, including moisture in the stack
sample size tested, and potential impacts on moisture which is not required for lower heating value calcu
loss during collection, storage, and sample preparation lation but is required for the environmental testing.
all add uncertainty in determining the heating value. From this data, the lower heating value is calculated
Therefore, current industry practice is to use the actual and adjusted for comparison to the quality of the ref
combustion unit as a calorimeter for determining of erence composition waste. Using in-plant instrumen
the solid waste heating value. tation and some basic assumptions, as discussed below,
the lower heating value of the solid waste can be cal
culated at any time after initial acceptance testing by
reading the appropriate data and making the required
PERFORMANCE TESTING calculations. Also, if the plant uses a distributed con
American Society of Mechanical Engineers (ASME) trol system with a computer, this calculation could be
Performance Test Code 4.1-1964, reaffirmed in 1973, programmed on the computer and done continuously
for Steam Generating Units (pTC 4.1) has been used, to check future performance.
= Output + Losses - Credits amount of data to make the lower heating value cal
HHV culation. The following is a list of the minimum amount
Fuel Throughput
of data which would be required to be taken periodi
The output includes heat in the steam and boiler blow cally:
down water. The credits include sensible and latent (a) waste feed rate
heat in the heated combustion air (if applicable). The (b) superheated steam outlet rates (net after soot
losses include the sum of: (a) heat loss due to the blowing), temperatures, and pressures
combustibles in the total residue; (b) heat loss due to (c) feedwater rates, temperatures, and pressures
moisture in the flue gas; (c) heat loss due to the heat (d) boiler drum pressures
in the dry flue gas; (d) heat loss due to moisture in (e) boiler blowdown rates
the air; (e) heat loss in the residue; and (f) heat loss (f) turbine generator throttle flow, temperature, and
due to radiation and convection. pressure
During testing, all necessary data are taken to de (g) flue gas flows and temperatures at the econo
termine the higher heating value of the waste. Ad- mizer outlet
230
(h) CO2, O2, CO in the flue gas at the economizer the same as it was during initial acceptance testing,
outlet this may indicate a problem in the plant equipment as
(i) bottom ash, siftings, and fly ash quantities opposed to a degradation of the solid waste quality.
OJ barometric pressure
(k) ambient wet/dry bulb temperatures
(l) gross and net power output
(m) turbine exhaust pressure CONCLUSION
In addition, some basic assumptions must be made if The method of continuous monitoring as discussed
continuous monitoring is to work on a day-to-day ba herein, because several assumptions are included, is
sis. These assumptions include: (a) the amount of mois intended to be an approximate method of indicating
ture in the residue; (b) unburned combustible content performance problems which may result in a dispute
in the residue; and (c) unaccountable and radiation between contract parties and eventually lead to re
losses. The unaccountable losses can be set at the value testing of the plant. However, contract parties may
that was originally agreed upon during initial accept agree to use this method to adjust the operating service
ance testing; radiation losses can be determined from fee paid in future years of commercial operation. In
ASME PTC 4.1, Steam Generating Units-Power Test such a case, the assumptions would need further re
Codes. The information pertaining to residue requires fining, and performance guanantees would have to be
laboratory analysis, which cannot be done on a con referenced in terms of lower heating values. The
tinuous basis without adding unnecessary cost. There method has been proposed for use in this capacity in
fore, residue data can be assumed, based on results the Hennepin County, Minnesota, waste-to-energy
obtained during initial acceptance testing, and period project, which is currently scheduled to be tested and
ically updated by random residue analysis during com commercially operational in 1989.
mercial operation.
Plant performance can be continuously monitored
by keeping a running average of the calculated lower
heating value, the solid waste throughput, and the REFERENCES
energy output. This information can be compared with [1] The American Society of Mechanical Engineers. "Steam
the results obtained during the initial acceptance tests Generating Units-Power Test Codes." ASME PTe 4.1, 1964, re
and with the performance guarantees. By this com affirmed 1973.
[2] Becker, R., and Wees, M. K. "Acceptance Testing of Mass
parison, any decline in energy output or waste through Bum Waste-to-Energy Facilities." National Solid Waste Manage
put can be attributed to either the equipment in the ment Association Conference on Disposal Problems & Solutions,
plant or the variations in waste quality. For example, NSWMA, Boston, October 29, 1985.
[3] "Agreement between Hennepin Energy Resource Co., Lim
if the energy output falls during a given period, but ited Partnership and the County of Hennepin." Hennepin County,
the lower heating value of the waste remains nearly Minnesota, July 27, 1985.
231