Professional Documents
Culture Documents
THE A/E SHALL EDIT THE INFORMATION IN THIS DOCUMENT, REMOVE BRACKETS AND
CHANGE THE RED TEXT TO AUTOMATIC TEXT TO MATCH THE SENTENCE.
THE A/E SHALL VERIFY THAT SECTION TITLES REFERENCED IN THIS SECTION ARE
CORRECT FOR THIS PROJECT'S SPECIFICATIONS; SECTION TITLES MAY HAVE CHANGED.
PART 1 - GENERAL
0.1 SUMMARY
B. Provide Air Sampling Smoke Detection (ASD) system(s) for both open area detection and
HVAC return coverage using Air Sampling Smoke Detection System(s) as indicated in this
Specification and on the Drawings.
0.2 DEFINITIONS
ADJUST LIST BELOW TO MEET PROJECT REQUIREMENTS
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 2
AIR SAMPLING SMOKE DETECTION SYSTEMS
A. System shall consist of a detector assembly housing an integral aspiration fan, filter, laser based
detection chamber and control, output and supervision circuitry.
B. System shall consist of a piping or tubing distribution network that runs from the detector
assembly(s) to the protected area(s) and is supported by calculations from a computer-based
design modeling tool.
C. System shall consist of sampling points placed on the piping or tubing network within the
airstream of return air or transfer grilles and, where specified, make up air ducts at spacing as
specified herein and by Manufacturer’s guidelines.
D. For open area coverage system shall consist of sampling points placed on the piping or tubing
network at locations where smoke detectors are required by all applicable codes and Owner’s
Standards as indicated in this Specification.
E. In operation, the aspiration fan in the detector assembly draws air from sampling points in the
piping or tubing distribution network back to the detector assembly where it is analyzed for fire
products.
F. System shall include configurable alarm and trouble relay outputs for interface to other systems
where required.
A. System shall be complete in all ways. It shall include all engineering, and electrical installation,
all detection and control equipment, auxiliary devices and controls, alarm interface, functional
checkout and testing, training and all other operations necessary for a functional, UL listed and
FM Approved system.
B. System design, installation, commissioning and testing shall be in accordance with this
Specification, the Manufacturer’s guidelines and per all applicable codes and requirements of
the local Authorities Having Jurisdiction (AHJ).
C. All Air Sampling Smoke Detection devices and associated components shall be new, standard
products or the manufacturer’s latest design and suitable to perform the functions intended.
D. Air sampling network shall be designed and installed to monitor the total room for smoke
concentration, not simply an area within a larger space. This requires that air samples be
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 3
AIR SAMPLING SMOKE DETECTION SYSTEMS
continuously drawn from the ceiling, above ceiling, raised floor (if present), and from the return
air intakes serving the room when indicated on drawings.
E. Air sampling pipe networks at the ceiling, above ceiling, and the raised floors shall mirror each
other. This will facilitate response to an alarm as well as maintenance by the on-site work
force.
F. Detectors protecting areas less than 6000 square feet may be protected using combined
coverage systems Under certain restrictive circumstances the detectors can be designed to
cover, no more than three protected areas (above drop ceiling, ceiling, below raised floor) plus
HVAC return of a room. When protecting HVAC and one or more levels of detection, 50% of
a detectors airflow capacity shall be reserved for monitoring of the HVAC system return air
path serving the room.
H. Open area ceiling sampling points shall be oriented downward and shall be within one to four
inches below the underside of the ceiling above where the ceiling is smooth. For ceilings that
have beams, girders, solid joist or a waffle-like construction, etc. mount detectors in accordance
with the special provisions in NFPA 72®.
I. Sampling points shall be accessible for inspection and maintenance. A sampling point shall be
visible from the floor, installed in an area on the ceiling or slab that is free from obstructions for
a minimum of 18 inches on all sides, and located so that it can be reached from the floor by the
use of a ladder.
K. Sampling points shall be a minimum of three feet away from air supply diffusers.
L. Manufacturer’s specific FM approved software modeling tool which uses pipe network
parameters shall be used to predict performance of pipe network design(s). Each of the
following performance requirements shall be met:
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 4
AIR SAMPLING SMOKE DETECTION SYSTEMS
4. The Fire 1 target sample point sensitivity shall not exceed [1% VEWFD], [1.50%
EWFD] or [2.00% SFD] obsc/ft at each sampling point.
B. Sample point spacing for return air or transfer grille detection shall be based upon sampling
point distribution of a maximum of one (1) sample point per every four (4) square feet of grille
area. See manufacturer’s installation instructions for specific details.
C. Sampling pipe covering HVAC return air intakes shall standoff 3 to 6 inches from the grille in
order to avoid the low or negative pressure point directly at the grille surface. Furthermore,
sampling points covering return air intakes shall be directed 33 to 45° into the airflow and shall
not be placed outside of grille area. A means to disconnect the sampling pipe from return air
intakes shall be provided and based on Manufacturer’s guidelines. Mechanical standoff
fasteners used to support the sampling pipe network shall be fit for purpose. Plastic zip ties are
not permitted.
D. Where indicated on drawings, outside fresh air intake ducts shall each be monitored by
sampling points of a VEWFD ASSD system prior to filtration to monitor incoming air for
smoke. The sampling pipe network shall not be directly exposed to the outside environment.
Precautions shall be taken to ensure the ASSD system operates within its UL listed temperature
range and that condensation is prevented from entering the system (refer to Drawing for
details). Follow manufacture’s pipe network design guide for duct applications. Air Sampling
Smoke Detector(s) covering HVAC fresh air intake ducts shall be dedicated to the duct in
which they are monitoring. Detector(s) exhaust port shall pipe back into the fresh air intake
duct so as to maintain an equal pressure across detector inlet and exhaust port. These detectors
are supervisory inputs to the Fire Alarm Control Panel or BAS only and do not alarm the
building causing evacuation. Provide detailed drawing of proposed installation for approval to
the Architect/Engineer project manager prior to installation.
E. All sampling points shall be marked with the Manufacturer’s standard identification labels.
F. For open area detection, provide a test point at the end of each pipe run 4-feet above finished
floor for testing smoke transport time back to the detector assembly. Test point shall be
constructed using a vented end-cap. Provide necessary signage to indicate the purpose of this
test point. Provide a detail of this sampling point along with signage information for approval.
0.2 SUBMITTALS
A. Product Data:
B. Submit Manufacturer’s technical product data as a minimum, but not limited to, for the
following:
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 5
AIR SAMPLING SMOKE DETECTION SYSTEMS
f. Wiring diagrams.
g. Equipment ratings.
h. Description of system operation for each product and that the system meets or
exceeds specified requirements.
D. Shop Drawings:
1. Shop Drawings shall be prepared by persons with the following qualifications:
2. Trained and certified by Manufacturer in fire alarm and Air Sampling System
design.
a. NICET certified fire alarm technician, Level III minimum.
b. If required licensed or certified by the authorities having jurisdiction.
3. Information shall be submitted on 1/8" = 1'-0" scale building floor plans. Reproduction
of contract drawing will not be acceptable. The following information shall be included
in the shop drawings:
a.
Provide mounting details of air sampling smoke detectors, displays, power supplies
and other boxes to building structure, showing fastener type, sizes, material, and
embedded depth where applicable.
REVISE DRAWING NUMBER IN SUBPARAGRAPH BELOW BASED ON ACTUAL DRAWING
NUMBERS OF PROJECT.
b. Air sampling pipe, fittings and pipe details including pipe routing and method to
remove pipe section at the HVAC return air grille. Reference Drawing XXX for
details.
c. The following Calculations and Wiring Diagrams shall also be included on the
shop drawings:
d. Provide calculations for the battery stand-by power supply taking into
consideration the power requirements of all auxiliary components under full load
conditions. Include battery size calculations.
e. Show system components, including detectors and cabinets, locations, quantities,
and full schematic of system wiring showing conductor size, routings, quantities
and connection details.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 6
AIR SAMPLING SMOKE DETECTION SYSTEMS
A. Permit Approved Drawings: Working plans, prepared according to NFPA 72, that have been
approved by Authorities Having Jurisdiction. Include design calculations.
B. Maintenance data
C. Warranty information.
A. Manufacturer's Qualifications:
B. Firms regularly engaged in manufacture of Air Sampling Smoke Detection systems of types,
sizes, and electrical characteristics required, and whose products have been in satisfactory
use in similar service for not less than fifteen years.
1. The name of the manufacturer, part numbers and serial numbers shall appear on all major
components.
D. Contractor Qualifications:
1. All contractors involved with the design and installation of ASSD systems shall be very
experienced with the systems that they are designing / installing. A minimum of 5 years
experience in the installation of ASSD systems and a NICET level III fire alarm
technician on staff to supervise the design and installation is required.
2. The installing contractor shall be listed by the system manufacturer as being trained and
certified to model, design, install, program, test and maintain the ASSD system and shall
be able to produce a certificate stating such upon request.
3. The installing contractor shall maintain appropriate licensing and certifications from the
state in which the work occurs.
1. Installers of fire detection and alarm systems shall be trained and qualified by the system
manufacturer in the proper installation of the system per the occupancy use. System
testing technicians or others conducting system programming, certification, power up,
and system commissioning, shall be an accredited NICET Level II (or greater) fire alarm
technician to perform such work.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 7
AIR SAMPLING SMOKE DETECTION SYSTEMS
F. Materials and installation shall be in accordance with the latest revisions of the following codes,
standards and specifications, except where more stringent requirements have been specified
herein:
C. Record Drawings:
5. Parts list.
a. Circuit drawings, point-to-point wiring diagram, riser diagram and control
diagrams.
b. Sequence of Operation which includes detailed operation and control of each item
of equipment and a control sequence.
c. Final location of all devices related to the fire alarm system.
d. Show size and route of all conduits related to the fire alarm system.
E. Record all tests and system calibration using the Manufacturer’s standard commissioning form
for each and every ASSD system provided. A copy of these results shall be included in
close-out submittals and a copy made available to be left on site.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 8
AIR SAMPLING SMOKE DETECTION SYSTEMS
A. It is the Contractor’s responsibility to ensure on-time delivery of all materials and equipment
required for the Project. All materials furnished or incorporated in the Work shall be new,
unused, of best quality, and especially adapted for the service required; whenever the
characteristics of any material are not particularly specified, such material shall be utilized as is
customary in first class work of a nature for which the material is employed.
B. Contractor shall provide necessary means to properly stage and store all materials and
equipment until time of use or installation on the Project. Contractor shall be solely responsible
for materials and equipment stored on the Site; type and extent of security provided to be at
Contractor’s discretion. Coordinate all requirements with Owner.
C. Contractor shall be responsible for proper handling, rigging, and installing of all materials and
equipment for the Project.
D. Owner reserves the right to reject any materials or equipment that are not properly stored in
accordance with these specifications or the Manufacturers’ requirements.
0.4 WARRANTY
A. All ASSD system components furnished and installed under this contract, shall be guaranteed
against defects in design, materials and workmanship for the full warranty period which is
standard with the Manufacturer, but in no case less than one (1) years from the date of system
acceptance.
PART 7 - PRODUCTS
0.1 MANUFACTURERS
B. Manufacturer’s:
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 9
AIR SAMPLING SMOKE DETECTION SYSTEMS
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 10
AIR SAMPLING SMOKE DETECTION SYSTEMS
f. Detector(s) shall incorporate a flow sensor in each pipe inlet and provide staged
airflow faults. Detector units which permit disabling of flow sensors is not
permitted.
12. Detector(s) shall incorporate facilities to transmit the following faults:
13. Detector
a. Airflow
b. Filter
c. System
d. Zone
e. Network
f. Power
g. Urgent and Minor faults
h. Each detection unit shall store internally a minimum of 12,000 events in its history
buffer for future extraction and analysis of events and operational status.
14. Addressable detectors shall have four pipe inlets fitted with an integral scanning valve
mechanism to identify which sampling pipe is carrying smoke. The valve mechanism
shall:
C. Display Unit(s):
1) Reset
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 11
AIR SAMPLING SMOKE DETECTION SYSTEMS
2) Isolate
PART 8 - Display Unit shall be either integral to the detector or externally mounted next to its
corresponding detector or were designated on Drawings.
A. Programmers:
B. One Programmer module shall be required and shall be located within a detector or externally
mounted where designated on Drawing.
1. Programmer shall support the following features at a minimum:
D. Material for pipe and fittings shall be orange ¾” chlorinated polyvinyl chloride (CPVC) pipe.
The pipe shall be UL listed as an accessory for plenum use as per UL1887 standard.
1. Pipe interior shall be smooth bore.
2. The pipe shall be marked with the UL Listing information and marking requirements as
per NFPA 72.
3. All fittings shall be made with compatible ¾” CPVC pre-formed elbows, tees, couplings
and unions.
4. All joints in the sampling pipe must be air tight and made by using solvent cement,
except at entry to the detector.
5. Pipe shall be UL listed and FM approved for its intended use and with the system in
which it is connected to.
6. Mechanical pipe fasteners and hangers shall be approved for use with the CPVC pipe
material in which it is supporting. Fasteners and hangars shall allow pipe to freely slide
in and out to facilitate expansion and contraction of the material.
7. It shall be the installing contractor’s responsibility to confirm pipe material and mounting
methods selected meets this Specification, requirements of the local Authority Having
Jurisdiction and Manufacturer’s guidelines.
F. System shall be powered by from a UL1481 listed regulated supply of nominally 24Vdc.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 12
AIR SAMPLING SMOKE DETECTION SYSTEMS
A. The initial alarm threshold sensitivity setting at time of system commissioning shall be set and
based upon the following formulas for each ASSD system:
B. Both day and night alarm thresholds are to be programmed to the same settings.
J. Signals
REVISE SUBPARAGRAPHS BELOW TO MEET PROJECT REQUIREMENTS.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 13
AIR SAMPLING SMOKE DETECTION SYSTEMS
d. Actuation signal for release of fire suppression systems or HVAC shutdown when
indicated
e. Fire 1
j. Action / Prealarm
o. Alert
x. Urgent Fault
A.
To ensure that the earliest possible alarm for detected smoke is rendered with the fewest number
of false alarms. Each ASSD system shall be subjected to a 30-day minimum test before the
system is considered acceptable. During the period while the sensitivity verification test is
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 14
AIR SAMPLING SMOKE DETECTION SYSTEMS
being conducted, normal operations shall continue unaltered within the fire zone. The building
alarm shall be connected to the ASSD system, but alarms triggered by the system should not
activate the automatic suppression systems and/or fire department notification.
B. At the end of this 30-day period the Fire Alarm Contractor shall download each ASSD system’s
event log using the Manufacturer’s software and analyze the data providing for adjustments in
accordance with the Manufacturer’s recommended procedure for data analysis, settings
adjustment and compensatory measures should adjustment exceed minimum performance
requirements as outlined herein.
A. All piping and sampling points shall be labeled as per Manufacturer’s recommendation and per
NFPA 72, current edition, requirements.
A. General: All power and distribution shall meet the requirements of the Manufacturer,
applicable codes and standards.
B. The FIRE alarm level contacts for each zone will be tied into the building fire alarm control
panel for alarm annunciation. For an addressable ASSD, each zone will be assigned an
individual address that will appear at the building fire alarm control panel and at all remote
annunciator panels. The system will activate an alarm condition in the building fire alarm
system when the ASSD system FIRE 1 alarm level is reached.
PART 12 - EXECUTION
A. Comply with NFPA 72 and in accordance with the Manufacturer’s written instructions for
installation of Air Sampling Smoke Detection systems.
C. Detector assembly shall be mounted to a wall in the protected room at a height of approximately
48 to 60 inches to top of detector measured above finished floor.
1. Mounting location shall be a fully accessible and visible location.
2. Mounting or attachment to site equipment, cable trays, movable walls, other equipment
or equipment supports is not permitted.
3. Piping network insertion into the detector inlet shall not be glued.
4. Air Sampling Smoke Detector assembly shall be installed in accordance with this
Specification and the Manufacturer’s installation and instruction manuals.
5. Flexible tubing for termination of the sampling pipe network into detector inlet is not
permitted (refer to Drawing for details).
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 15
AIR SAMPLING SMOKE DETECTION SYSTEMS
6. Air Sampling Smoke Detector assembly shall be installed in accordance with this
Specification, the Manufacturer’s installation and instruction manuals.
7. Installation techniques shall be in compliance with the geographical seismic zone
requirements in seismic zones per the AHJ.
D. Pipe Mounting:
E. The pipe network shall be mounted as per the design and ASPIRE2 specifications. The
hardware used for mounting will depend upon the design and site requirements.
1. To minimize flexing the pipes shall be secured every 5 feet.
2. Pipes shall be suspended between 1 to 4 inches below the ceiling.
3. When installing a pipe network in areas subject to high temperature fluctuations allow for
the contraction and expansion of pipes.
4. Where expansion or contraction of pipes is likely either after installation or on a
continuous basis, do not place pipe clips adjacent to couplings and socket unions as these
may interfere with the movement of the pipe.
5. No bends are permitted within the first 18” from the detector inlet.
6. Piping shall be mounted as close to the ceiling as possible.
7. The routing of the piping network shall be coordinated with potential obstructions,
including cable trays, grounding bars, and HVAC ductwork.
8. All changes in direction shall be made with standard elbows or tees.
9. All joints shall be air-tight and made by using solvent cement, except at the entry to the
detector assembly. Refer to ASTM F402-88 standard practice for safe handling of
solvent cements, primers and cleaners used for joining thermoplastic pipe and fittings.
10. Flexible tubing for termination of the sampling pipe network into detector inlet is not
permitted (refer to Drawing for details).
11. All pipes shall be supported by mechanical hangers attached to the structure of the
building. Not more than one foot of pipe shall extend beyond the last hanger of each
sampling pipe. The final installation shall result in no noticeable deflection in the piping
network.
DELETE SUBPARAGRAPH BELOW IF NOT APPLICABLE.
12. Attachment of air sampling pipes to cable trays “gray iron” and telecommunications
equipment is prohibited.
13. Piping shall be labeled with the Air Sampling Smoke Detection system with
Manufacturer’s identification at least 20-foot intervals.
14. Placement of the sampling pipe shall take into consideration appropriate sampling point
locations and spacing.
15. All sampling pipe penetrations of fire-rated partitions shall be sealed with an
Underwriter’s Laboratory’s Listed and/or FM Global Approved through-penetration
firestop material.
16. Sampling pipe covering HVAC return air intakes or transfer grilles shall standoff 3-6
inches from the grille in order to avoid the low or negative pressure point directly at the
grille surface. Furthermore, sampling points covering return air intakes or transfer grilles
shall be directed 33° to 45° into the airflow and shall not be placed outside of grille area.
A means to disconnect the sampling pipe from return air intakes shall be provided and
based on Manufacturer’s guidelines. Mechanical standoff fasteners used to support the
sampling pipe network shall be fit for purpose. Plastic zip ties are not permitted.
17. Sample pipe serving return air grilles shall be fitted with a ¾” CPVC union to facilitate
removal of sample pipe from grille to access HVAC filters.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 16
AIR SAMPLING SMOKE DETECTION SYSTEMS
18. Sampling pipe serving outside air intake ducts shall not be directly exposed to the outside
environment. Precautions shall be taken to ensure the ASSD system operates within its
UL listed temperature range and that condensation is prevented from entering the system
(refer to Drawing for details). Furthermore, sampling points covering outside air intake
ducts shall be placed prior to filtration. Follow manufacture’s pipe network design guide
for duct applications. Provide detailed drawing of proposed installation for approval to
the Architect/Engineer project manager prior to installation.
19. Swarf and other debris accumulated in pipes during installation and assembly shall be
removed by negative airflow prior to connection to the detector.
20. Sampling pipe network shall be installed in accordance with this Specification and the
Manufacturer’s design manual.
1.
In areas with a suspended ceiling the sampling pipe network shall be installed above the
ceiling with remote sampling points extending through the ceiling using appropriate
lengths of 3/8 inch inside diameter capillary tubing attached to remote sampling points.
Remote sampling point locations shall align in center of ceiling tile where possible
provided spacing meets the requirements of this specification. Appearance shall be
uniform in terms of sampling point row alignment. Coordinate layout with T-Bar grid.
DELETE TEXT BELOW IF NOT APPLICABLE.
2. In areas designated on the Drawings, lower level sampling points shall extend from
sampling pipe network supported to the underside of the ceiling using lengths of 3/8 inch
diameter capillary tubing attached to remote sampling points. [Secure remote sampling
points to auxiliary iron using in an acceptable manner that ensures secure support but
allows future relocation. Sampling points shall reside within 1 to 6 inches of the
underside of ox iron approximately 9.2 feet above finished floor.]
3. The maximum length of the capillary tube shall be 26 feet.
4. Two additional feet of capillary tubing shall be provided for each drop to permit future
relocation of remote sampling points (not to exceed 26 foot limitation).
5. Remote sampling points shall be labeled with the Manufacturer’s standard identification
marking.
6. Capillary tube and attachment to sampling pipe network shall be that required by the
manufacturer.
1. It is permissible for a sampling pipe network to protect both the ceiling and return air
grilles provided individual pipe or a branched sampling pipe network is deployed and that
the area is serviced by the same HVAC system. Strict compliance with the
Manufacturer’s system design manual shall be given when applying a system in this
fashion.
0.2 IDENTIFICATION
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 17
AIR SAMPLING SMOKE DETECTION SYSTEMS
B. The Air Sampling Smoke Detection System Contractor shall draft and submit, to the Architect /
Engineer and the Owner’s Representative, for approval, a detailed Method of Procedure (MOP)
commissioning plan, per area, which outlines all commissioning activities and identifies each
activity and test, zone specific, necessary for a complete verification of the design and
operation prior to start of testing.
E. General testing:
F. All system and equipment devices shall function as required and designed.
a. Each detector unit circuit shall be tested for trouble by inducing a trouble condition
into the system.
b. Test wiring runs for continuity, short circuits, and grounds before system is
energized. Test and record resistance, current, and voltage readings as work
progresses.
c. Field tests shall be performed for all devices and functions of the ASSD system
(100%) prior to the performing a final test to be witnessed and accepted by the local
AHJ. All testing shall be coordinated with the Architect / Engineer and the Owner’s
Representative
G. Acceptance Tests:
H. Prior to final acceptance, the installing contractor shall provide complete operation and
maintenance instruction manuals as indicated in this specification Part 1, Closeout
Submittals and Documents. All aspects of system operation and maintenance shall be
detailed, including piping isometrics, wiring diagrams of all circuits, a written description
of the system design, sequence of operation and drawing(s) illustrating control logic and
equipment used in the system. Checklists and procedures for emergency situations,
troubleshooting techniques, maintenance operations and procedures shall be included in
the manual.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM
SECTION XXXXXX, PAGE 18
AIR SAMPLING SMOKE DETECTION SYSTEMS
1. Final Acceptance Test shall begin only when the Preliminary Test Report has been
approved.
2. As-Built Drawings and previous test results shall be available at the time of testing.
3. The installation shall not be considered accepted until identified discrepancies have been
corrected and test documentation is properly completed and received.
J. Upon completion of a successful test, the fire protection contractor shall so certify the system in
writing to Owner’s Representative.
1. Submit copy of test results in duplicate, after signed off by the AHJ, to the Architect /
Engineer and the Owner’s Representative.
K. Upon acceptance by the Architect / Engineer and the Owner’s Representative, the completed
system(s) shall be placed into service.
A. Train Owner's maintenance personnel to adjust, operate, and maintain Air Sampling Smoke
Detection Systems.
B. Prior to final acceptance, the installing contractor shall provide operational training to each shift
of Owner’s personnel. Each training session shall include ASSD system operation, trouble
procedures, supervisory procedures, auxiliary functions and emergency procedures.
EDIT ARCHITECT / ENGINEER NAME AND PROJECT NUMBER. MANUALLY ENTER IN DATE
AND TIME TO KEEP TRACK OF CHANGES, DATE SHALL NOT BE AUTOMATIC.
[Company Name and Project No. XXXXXX] Date: xx/xx/xx, 0:00 AM/PM