40800R1 Veolia-Servp Barr

Technical data
794 kWel; 480 V, 60 Hz; Natural gas, MN = 90

2)
Design conditions Fuel gas data:
Inlet air temperature / rel. Humidity: [°C] / [%] 30 / 90 Methane number: [-] 90
3
Altitude: [m] 100 Lower calorific value: [kWh/Nm ] 9,82
3
Exhaust temp. after heat exchanger: [°C] 120 Gas density: [kg/Nm ] 0,76
NOx Emission (tolerance - 8%): [mg/Nm3 @5%O2] 500 Standard gas: Natural gas, MN = 90

Genset:
Engine: CG132B-16
Configuration code: [-]
Speed: [1/min] 1800
Configuration / number of cylinders: [-] V / 16
Bore / Stroke / Displacement: [mm]/[mm]/[dm3] 132 / 160 / 35
Compression ratio: [-] 13
Mean piston speed: [m/s] 9,6
Mean lube oil consumption at full load: [g/kWh] 0,1

Generator: Marelli MJB 400 LC4


Voltage / voltage range / cos Phi: [V] / [%] / [-] 480 / 10 / 0,8
Speed / frequency: [1/min] / [Hz] 1800 / 60

Energy balance
Load: [%] 100 75 50
Electrical power COP acc. ISO 8528-1: [kW] 794 595 397
Engine jacket water heat: [kW ±8%] 447 364 272
Intercooler LT heat: [kW ±8%] 58 39 24
Lube oil heat: [kW ±8%]
Exhaust heat with temp. after heat exchanger: [kW ±8%] 424 348 258
Exhaust temperature: [°C ±25°C] 440 461 482
Exhaust mass flow, wet: [kg/h] 4378 3361 2337
Combustion mass air flow: [kg/h] 4231 3246 2255
Radiation heat engine / generator: [kW ±8%] 27 / 33 22 / 25 18 / 20
Fuel consumption: [kW+5%] 1896 1480 1051
Electrical / thermal efficiency: [%] 41,9 / 45,9 40,2 / 48,0 37,8 / 50,5
Total efficiency: [%] 87,8 88,2 88,3

1)
System parameters
Ventilation air flow (comb. air incl.) with ΔT = 15 K15K [kg/h] 23100
Combustion air temperature minimum / design: [°C] 10 / 30
Exhaust back pressure from / to: [mbar] 30 / 60
Maximum pressure loss in front of air cleaner: [mbar] 5
Zero-pressure gas control unit selectable from / to: 2) [mbar] 20 / 200
Pre-pressure gas control unit selectable from / to: 2) [bar] 0,5 / 10
Starter battery 24V, capacity required: [Ah] 286
Starter motor: [kWel.] / [VDC] 9 / 24
Lube oil content engine & extension / clean oil tank: [dm3] 480 / 360*
Dry weight engine / genset: [kg] 3090 / 8200

Cooling system
Glycol content engine jacket water / intercooler: [% Vol.] 0/0
Water volume engine jacket / intercooler: [dm3] 56 / 5
KVS / Cv value engine jacket water / intercooler: [m3/h] 29 / 14
Jacket water coolant temperature in / out: [°C] 78 / 88
Intercooler coolant temperature in / out: [°C] 45 / 50
Engine jacket water flow rate from / to: [m3/h] 29 / 50
Water flow rate engine jacket water / intercooler: [m3/h] 40 / 10 Page 1 / 1

Water pressure loss engine jacket water / intercooler: [bar] 1,8 / 0,5

3332013EA54789
1) See also "Layout of power plants": 2) See also Techn. Circular 0199-99-3017 *) optional 40800

Frequency band 25 31 40 50 63 80 100 125 160 200 250 315 400 500 630 800 1 1,25 1,6 2 2,5 3,15 4 5 6,3 8 10 12,5 16
LWA S
[dB(A)] 2
f [Hz] [m ]
3) 119,9
Air-borne noise 80,0 89,0 87,0 88,0 96,0 100,0 102,0 109,0 111,0 102,0 100,0 101,0 102,0 101,0 97,0 100,0 98,0 114,0 104,0 97,0 98,0 98,0 101,0 102,0 117,0 100,0 93,0 0,0 0,0 76
LW,Terz [dB(lin)] ±4dB(A)

Exhaust noise 4) 113,0 113,0 115,0 118,0 115,0 114,0 124,0 136,0 130,0 126,0 122,0 119,0 116,0 117,0 117,0 117,0 116,0 114,0 112,0 112,0 111,0 111,0 111,0 111,0 110,0 108,0 108,0 106,0 103,0
127,7 5)
15,2
LW,Terz [dB(lin)] ±3dB(A)
2
3) DIN EN ISO 3746 (σR0=±4 dB) 4) Measured in exhaust pipe (f ≤ 250Hz: ±5dB; f > 250Hz: ±3dB) LW: Sound power level S: Area of measurement surface (S0=1m ) 5) DIN 45635-11, Appendix A

PwrA_3.03r01_Dr0 Subject to technical changes 854, 12.03.2020