Dimensions
Unit: mm Dimension: 483(L)×170(W)×240 (H) Terminal F12
Terminal F5
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
9 .60 V 4 5 2.4 3 37 .8 27 2 .1 15 0 .7 9 3 .6 3 5 7 .8 1 3 9 .2 8 3 1 .6 8 2 6.2 9 1 7.3 2 1 5.6 1 8.2 6
1 0.0 V 4 3 9.3 3 21 .4 26 6 .5 14 8 .8 9 2 .3 8 5 6 .6 4 3 8 .5 6 3 1 .2 3 2 6.0 6 1 7.2 5 1 5.4 6 8.1 1
1 0.2 V 4 2 6.3 3 10 .1 26 2 .4 14 6 .5 9 1 .5 0 5 6 .0 4 3 8 .2 1 3 0 .9 1 2 5.8 9 1 7.1 0 1 5.3 0 7.9 5
1 0.5 V 3 8 2.8 2 86 .1 24 9 .8 14 2 .5 9 0 .3 8 5 5 .3 1 3 7 .8 7 3 0 .4 6 2 5.6 7 1 6.9 4 1 5.1 5 7.8 0
1 0.8 V 3 4 5.5 2 60 .9 23 0 .3 13 7 .8 8 9 .1 2 5 4 .8 5 3 7 .4 3 2 9 .4 1 2 5.5 5 1 6.8 7 1 5.0 1 7.7 2
1 1.1 V 2 9 5.0 2 33 .2 20 6 .5 13 2 .5 8 7 .0 1 5 2 .6 5 3 6 .7 0 2 8 .9 9 2 5.3 6 1 6.7 4 1 4.8 4 7.4 1
Storage characteristic
15 100
Supplementary charge required
0℃ (Carry out supplementary charge
before use if 100% capacity is
12 80 requires)
Capacity (%)
10℃
L ife E xp e cta ncy (years)
9
60 before use.
This supplementary charge will help
to recover the capacity and should
20℃ be made as early as possible.
40 40℃ 30℃
6
Supplementary charge may often
fail to recover the capacity.
The battery should never be left
20 standing till this state is reached
3
0
Supplementary charge and storage
0 2 4 6 8 10 12 14 16 18 20 22 24 guidelines
0 10 20 30 40 50 Storage Time (months)
Battery Temperature (℃)
12 6.0 4.0
Charge Voltage(V)
0.6 1.2 3 6 12 30 1 2 5 10 20 24
9 4.5 3.0 0 0
0 2 4 6 8 10 12 14 16 18 20 24 28 min Hr
Charge the batteries at least once every six months, ※ Every three months, recommend equalization charge for one time.
if they are stored at 25 o C.
Equalization charge method:
Charging Method:
Constant Voltage
Discharge: 100% rate capacity discharge.
-0.2Cx2h+2.4-2.45V/cellx24h,Max. Current 0.3C
Constant Current -0.2Cx2h+0.1Cx 12h Charge: Max. current 0.3CA, constant voltage 2.4-2.45V/Cell charge 24h.
Fast -0.2Cx2h+0.3Cx4h
※ Effect of temperature on float charge voltage: -3mV/℃/Cell.
Bolt M5 M6 M8 ※ Length of service life will be directly affected by the number of discharge
Terminal F3 F4 F13 F18 T25 T26 F8 F11 F12-1 F15 F5 F9 F10 F12 F14 F16 .
Torque
cycles, depth of discharge, ambient temperature and charging voltage.
6~7N-m 8~10N-m 10~12N-m
SHENZHEN RITAR POWER CO.,LTD. Address: Rm405,Tower C, Huahan Building,Langshan Rd16, Nanshan District, ShenZhen, 518057, China
URL:www.rit arpower.com Tel:+86-755-33981668 Fax:86-755-8347-5180 2012 - Version 1