You are on page 1of 33

AMCA

Publication 850-02
(R2011)

Industrial Process/Power Generation:


Heavy Duty Dampers for
Isolation and Control

AIR MOVEMENT AND CONTROL


ASSOCIATION INTERNATIONAL, INC.

The International Authority on Air System Components


AMCA PUBLICATION 850-02 (R2011)

Industrial Process/Power Generation:


Heavy Duty Dampers for Isolation and Control

Air Movement and Control Association International, Inc.


30 West University Drive
Arlington Heights, IL 60004-1893
© 2011 by Air Movement and Control Association International, Inc.

All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Chief Staff Executive, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Authority

AMCA International Publication 850-02 was adopted by the membership of the Air Movement and Control
Association International, Inc. on May 16, 2002. It was reaffirmed by the membership of the Air Movement and
Control Association International, Inc. on July 28, 2007, and on May 1, 2011.

Foreword

The Air Movement and Control Association International, Inc. (AMCA) is an international trade association
representing manufacturers of industrial and commercial fans, airflow control devices such as backdraft dampers,
louvers and dampers, airflow measurement stations, and acoustic attenuation devices.

This publication covers dampers such as are used in industrial process systems, and power generation facilities,
where flue gas or air is the primary medium. This publication contains base-line information on applications and
provides specification guidelines that may be supplemented by designers, specifiers and users to encompass their
specific needs.

Disclaimer

This manual has been prepared by the Air Movement and Control Association International, Inc. (AMCA). The
information contained in this manual has been derived from many sources and is believed to be accurate. Please
note that the recommendations contained herein do not necessarily represent the only methods or procedures
appropriate for the situation discussed, but rather are intended to present consensus opinions and practices of the
air movement and control industry which may be helpful, or of interest to those who design, test, install, operate or
maintain fan-duct systems. Thus, AMCA disclaims any and all warranties, expressed or implied, regarding the
accuracy of the information contained in this manual and further disclaims any liability for the use or misuse of this
information. AMCA does not guarantee, certify or assure the performance of any fan-duct system designed, tested,
installed, operated or maintained on the basis of the information provided in this manual.

Objections to AMCA Standards and Certifications Programs

Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding
its standards, certification programs, or interpretations thereof. For information on procedures for submitting and
handling complaints, write to:

Air Movement and Control Association International


30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.

or

AMCA International, Incorporated


c/o Federation of Environmental Trade Associations
2 Waltham Court, Milley Lane, Hare Hatch
Reading, Berkshire
RG10 9TH United Kingdom
RELATED AMCA STANDARDS

For Air Performance:

ANSI/AMCA Standard 210 Laboratory Method of Testing Fans for Aerodynamic Performance Rating

AMCA Standard 803 Industrial Process/Power Generation Fans: Site Performance Test Standard

For Sound:

AMCA Standard 300 Reverberant Room Method for Sound Testing of Fans

AMCA Standard 301 Methods for Calculating Fan Sound Ratings from Laboratory Test Data

For Balance and Vibration:

ANSI/AMCA Standard 204 Balance Quality and Vibration Levels for Fans

Industrial Process / Power Generation Series:

AMCA Publication 801 Industrial Process/Power Generation Fans: Specification Guidelines

AMCA Publication 802 Industrial Process/Power Generation Fans: Establishing Performance Using
Laboratory Models

AMCA Standard 803 Industrial Process/Power Generation Fans: Site Performance Test Standard

Fan Application Manual:

AMCA Publication 200 Air Systems

AMCA Publication 201 Fans and Systems

AMCA Publication 202 Troubleshooting

AMCA Publication 203 Field Performance Measurement of Fan Systems


TABLE OF CONTENTS

1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3. Terms And Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

4. Types Of Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

4.1 Control Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

4.2 Isolation Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5. Damper Leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

5.1 Leakage Containment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

5.2 Leakage Path And Leakage Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

5.3 Factors Affecting Actual Leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

5.4 Selecting A Damper To Meet Low To Zero Leakage Requirements . . . . . . . . . . . . . . . . . . . . .10

6. Thermal Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

6.1 Normal Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

6.2 Thermal Stresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

6.3 Leakage Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

6.4 Damper Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

6.5 Thermal Differential . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

7. System Gas Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

7.2 System Gas Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

8. Corrosion And Erosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

9. Control Range (See Figure 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

10. Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

10.1 Pressure Drop Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

10.2 Pressure Drop Equation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

10.3 System Effect On Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14


11. Damper Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

11.1 Mechanical/Thermal Stresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

11.2 Stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

11.3 Deflection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

11.4 Wind Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

11.5 Seismic Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

11.6 Connection To Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

12. Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

12.1 Pneumatic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

12.2 Electric . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

12.3 Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

12.4 Options And Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

13. Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

13.1 Location Of And Schedule For Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

13.2 Functional Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

13.3 Simulation Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

13.4 Test Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

14. Recommended Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

14.1 Louver Damper Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

14.2 Guillotine Damper Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

15. Sample Specification Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

16. Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20


AMCA INTERNATIONAL, INC. AMCA 850-02 (R2011)

Industrial Process/Power modulation. An actuator may be manually,


electrically, pneumatically or hydraulically powered.
Generation: Heavy Duty The output force of an actuator is delivered in either
a linear or a rotary direction.
Dampers for Isolation and
Control 3.3 Actuator torque. The rated torque capability of
an actuator.
1. Purpose 3.4 Airfoil (blade). A double-skinned damper
BLADE, the blade skins meeting at the leading and
The purpose of this publication is to provide basic trailing edges of the blade with no substantial
pertinent information in order to simplify protrusions external to either blade skin.
communications between damper manufacturers
and designers, specifiers and users of such 3.5 Area of restriction. The total cross-sectional
equipment. area of DAMPER components that are permanently
located within the gross FREE AREA provided for
2. Scope gas flow through the DAMPER frame. The restrictive
cross-sectional area of each component is
The scope of the products covered in this application determined by its position when the damper is fully
guide includes dampers that are used to control a open. Generally, in the full open position, a
flow of gas (be it a specific gas, a mixture of gas and component will present the smallest frontal area to
air, or air alone), or to isolate one section of a duct the direction of the gas flow.
system from another section of that system. The
scope narrows to those dampers generally described 3.6 Blade. In strict terms, the moveable component
as "heavy duty" or "severe service", because such within the DAMPER frame. The purpose of a blade is
dampers are normally used in applications where to restrict a gas flow for modulation (control), or for
extreme temperature, erosion and/or corrosion closure (isolation).
conditions exist.
3.7 Blade entry seal. In a GUILLOTINE DAMPER,
3. Terms and Definitions the sealing arrangement through which the damper
BLADE passes.
This section defines terms that have special meaning
or significance in damper applications and within the 3.8 Blade support. A structural member inside the
damper industry. Most are specific to the dampers frame of a GUILLOTINE DAMPER. The member
under discussion in this publication. For the reader’s supports a portion of the BLADE when the damper
convenience, terms that are defined in this section BLADE is in the closed position.
are shown in capital letters when used in the
definition of a related term. 3.9 Bonnet, open. The portion of a GUILLOTINE
DAMPER frame that supports the BLADE when the
3.1 Accessory. An accessory is an item purchased damper BLADE is in the open position. An OPEN
by the damper manufacturer and either mounted on BONNET does not have an enclosed blade.
the DAMPER at the factory or supplied with the
damper for field installation by others. An accessory 3.10 Bonnet, fully enclosed (or sealed). The
is generally an item used to enhance or improve the enclosed portion of a GUILLOTINE DAMPER frame
performance of a damper. An accessory may be an that supports the BLADE when the damper blade is
ACTUATOR, a SEAL AIR system, a PURGE AIR in the fully open position.
system, a limit switch, a flow sensor (or system),
positioning equipment, or some other item 3.11 Butterfly damper. A LOUVER DAMPER having
associated with powering, sensing or signaling. a round single BLADE.

3.2 Actuator. A mechanical accessory item attached 3.12 Control damper. A DAMPER which has the
to a DAMPER for the purpose of moving the damper purpose of modulating or regulating one or more gas
BLADES(s) to either the open position, the closed flow parameters such as PRESSURE DROP, rate of
position, or to an intermediate position to achieve low gas flow, or airflow distribution.

1
AMCA 850-02 (R2011)

3.13 Chain drive. An arrangement of chain and SEAL AIR SYSTEM to prevent LEAKAGE of high
sprockets for the purpose of bi-directional pressure upstream system gas when the damper is
transmission of torque to the BLADE(s) of a damper. closed.

3.14 Damper. A self-contained device for the control 3.24 Height. A dimensional reference to DAMPER
and/or regulation of gas flow from one portion of a size. In a GUILLOTINE DAMPER, height is the inside
duct system to another portion of that system; duct dimension parallel to the direction of the BLADE
consisting of a frame and one or more linked movement (draw). In a LOUVER DAMPER, height is
moveable BLADE sections. the inside duct dimension perpendicular to the axis
of the BLADE(s). See Figures 4 and 2, respectively.
3.15 Drive. See ACTUATOR; DRIVE SYSTEM.
3.25 Isolation. The restriction of system gas flow
3.16 Drive lifting force. Of a GUILLOTINE across the DAMPER. The extent of ISOLATION
DAMPER; the tensile force required to move the provided by a damper varies greatly with application
damper BLADE under specified conditions. requirements and the nature and type of DAMPER.
The extent of ISOLATION is usually expressed as
3.17 Drive system. The ACTUATOR and all LEAKAGE.
components through which force is transmitted to the
damper BLADE(s) for the purpose of positioning the 3.26 Isolation damper. A DAMPER having the
BLADE(s). primary function of ISOLATION.

3.18 Flow distribution. The pattern of gas flow 3.27 Leakage. The volume of system gas that can
variation in a duct, usually expressed in terms of gas pass through the various flow paths around the
velocity across a representative cross-section area of components of a closed DAMPER under a given set
the duct. of conditions. LEAKAGE may be expressed in terms
of Actual Cubic Meters per Second (ACMS) (Actual
3.19 Frame. Of a DAMPER, the external portion of Cubic Feet per Minute (ACFM)), kilograms (of gas)
the assembly that supports the BLADE(s), the means per hour (pounds per hour), Percentage of Normal
of attachment to the duct and provides the means of Airflow rate, or Percentage of Maximum Airflow rate.
attaching other specified ACCESSORIES.
3.28 Leakage area. The total area of the various flow
3.20 Free area. Of a DAMPER, the internal cross- paths between the component parts of a fully closed
section area of the DAMPER less the INTERNAL DAMPER.
RESTRICTION.
3.29 Leakage zero. A condition in which no system
3.21 Goggle damper. A DAMPER having a single gas passes from the upstream side of a duct system
sliding BLADE in which there is a cut-out area through a closed DAMPER to the downstream side of
matching the inside dimensions of the duct. The the duct system.
damper is open when the cut-out area is moved to a
position in line with the duct, and closed when the 3.30 Linkage. Of a DAMPER, includes the blade
solid portion of the BLADE is positioned in line with shaft lever arms and connecting bar assemblies
the duct. The overall construction is similar to that of between blades, which accept operating force
the GUILLOTINE DAMPER. (Note: The name transmitted from an ACTUATOR.
"goggle" originated with the first application of this
type of damper to a round duct.) 3.31 Load bar. See BLADE SUPPORT.

3.22 Guillotine damper. A DAMPER, also known as 3.32 Louver damper. A DAMPER having one or
a GATE damper, having a single, solid, sliding more BLADE(s) permanently in the gas stream; said
BLADE. The DAMPER is closed when the BLADE BLADE(s) may be rotated between the open and
slides completely into position over the duct cross- closed position or to some intermediate position.
section area; it is open when the BLADE slides See Figures 1 and 2.
completely out of the duct area and into the
BONNET. 3.33 Modulate. In a DAMPER, to vary the gas flow
rate or pressure drop, or both, across a DAMPER by
3.23 Guillotine damper, double blade. A changing the restrictive effect of the BLADE(s). This
GUILLOTINE DAMPER having two parallel blades change is brought about by altering the position of
which operate in tandem, and a separating air space the BLADE(s) within the damper frame. Also, the
(AIR CHAMBER) which may be pressurized by a effect of damper closure positioning to vary the

2
AMCA 850-02 (R2011)

system gas flow rate, flow velocity, or pressure; the between the mating surfaces of a closed damper.
action of the damper, damper controls and
ACTUATOR to maintain a predetermined set of flow 3.45 Seal air. Air introduced into the AIR CHAMBER
parameters such as pressure or temperature. of a DAMPER at a pressure higher than that of the
upstream system gas. SEAL AIR thus provides a
3.34 Normal operating conditions. Of a damper barrier to the passage of system gas from upstream
installation, the specific (or range of) pressure and of the damper to the downstream side. See Figure 6.
temperature at the damper when the system is
functioning within the planned productive operating 3.46 Shaft. In a LOUVER DAMPER, the supporting
range and conditions. structural element of the blade; also the component
about which the BLADE rotates and changes the
3.35 Operator. See ACTUATOR. BLADE attitude toward the gas stream. In a
GUILLOTINE DAMPER, the round bar or tube
3.36 Packing. Sealing material used to minimize or through which actuation force is transmitted between
eliminate LEAKAGE at a shaft penetration through a components of the DRIVE SYSTEM.
damper frame. It is contained in a STUFFING BOX
and retained by a packing gland that may be bolted 3.47 Shut-off damper. A DAMPER that is not
to or threaded into the body of the stuffing box. intended/used at any intermediate position between
fully open or fully closed; sometimes referred to as
3.37 Perimeter air sealed damper. A GUILLOTINE "on-off" service. Note: Neither the name nor the
DAMPER having a frame design which includes a expression denotes ISOLATION.
chamber around the duct and the BONNET. The
chamber must be pressurized by a SEAL AIR 3.48 Stub shaft. A short, non-continuous shaft that
SYSTEM. extends through, as applicable: the LINKAGE,
bearing, STUFFING BOX, or DAMPER frame and
3.38 Pressure drop. The static pressure loss across into the BLADE of a LOUVER or BUTTERFLY
a damper due to airflow resistance. Damper pressure DAMPER.
drop must be added to other system pressure losses
to obtain total pressure drop in the system. For more 3.49 Stuffing box. A chamber surrounding a shaft
complete information on pressure drop, see AMCA penetration through a DAMPER frame and into which
Publications 200 and 201. PACKING may be installed to provide a leakage-
resistant seal around the SHAFT.
3.39 Purge air. As compared to SEAL AIR that is
used for sealing, PURGE AIR is generally used to 3.50 Sprocket. A gear-like disk having teeth shaped
scavenge or displace gases from enclosed spaces to engage a drive chain for the purpose of converting
formed within the damper or within isolated spaces in actuator force to tensile force on the drive chain of a
a duct or system. GUILLOTINE DAMPER.

3.40 Quarter-turn damper. One that moves from 3.51 Throat seal. See BLADE ENTRY SEAL.
fully open to fully closed (or vice versa) with a 90°
rotation of the damper shaft. 3.52 Upset conditions. Those recognized potential
excursions of pressure or temperature beyond the
3.41 Rack and pinion. A damper DRIVE SYSTEM in NORMAL OPERATING CONDITIONS and usually of
which rotary effort applied to a toothed wheel causes short duration. A DAMPER subjected to upset
linear motion of a mating bar having a compatible conditions is usually required to sustain the upset
tooth form. See Figure 5. conditions and perform thereafter without inhibition of
normal function, or to specified functions under upset
3.42 Racking. The twisting of a DAMPER frame out conditions.
of its intended planar arrangement.
3.53 Width. A dimensional reference to DAMPER
3.43 Screwjack. A GUILLOTINE DAMPER DRIVE size; in a GUILLOTINE DAMPER, the duct inside
SYSTEM that uses the principle of the screw to dimension that is perpendicular to the direction of
change rotary motion into linear motion in applying BLADE movement. In a LOUVER DAMPER, it is the
opening/closing force. duct inside dimension parallel to the SHAFT axis.
See Figures 4 and 2, respectively.
3.44 Seals. In a DAMPER; any component located
on a DAMPER BLADE or FRAME and having the 3.54 Wire cable. In a GUILLOTINE DAMPER, a
purpose of limiting the amount of LEAKAGE AREA tensile force component consisting of woven strands

3
AMCA 850-02 (R2011)

of metal wire that are used to position the damper closed (NC). Through the use of a signal-and-
blade. actuation system, the damper blades move from their
normal position to a pre-set position, which is
3.55 Wire cable sheave. In a GUILLOTINE determined by the needs of the process being
DAMPER, a grooved wheel over which a WIRE served. The pre-set position may be adjustable. This
CABLE passes. variety of damper is also called a two-position
damper.
4. Types of Dampers
4.1.3 Modulating damper. A modulating (control)
Dampers used in industrial process/power damper is one that is capable of attaining and holding
generation (IP/PG) service are, as mentioned above, any position from full-open to full-closed. Actuation of
of heavy construction to meet heavy service needs. this damper depends on the needs of the process. It
This publication assumes that the reader is basically may be manually operated, or it may be operated
familiar with dampers for HVAC or light industrial with a signal-and-actuation system, in which case it
service and the general construction of such also requires a positioner with feedback capability.
dampers, so only terms and definitions unique to For a modulating damper, opposed blades provide a
IP/PG service will be fully explained. Basic better opportunity of achieving a near-linear
terminology and general damper construction is relationship between signal and flow rate.
given in AMCA Publication 502, Application Manual
for Louvers, Dampers and Shutters, and other 4.2 Isolation damper
special dampers are covered in AMCA Publication
503, Fire, Smoke and Ceiling Damper Application In a very real sense, an isolation damper is a special
Manual. kind of control damper. The name originates with its
application: to restrict gas flow across the damper to
Dampers used in Industrial Process or Power a specified maximum amount, compatible with the
Generation service are classified under two requirements of the process it serves.
headings: control or isolation.
Many isolation dampers are used for isolation only,
4.1 Control damper but there are many cases where an isolation damper
also performs a control function. A damper that is
A control damper is one that is used to vary the flow intended for dual use is almost always a multi-
rate of gas through a system. Variation of flow rate blade louver damper with opposed blades. For
through the damper is achieved by changing the isolation purposes only, a multi-blade louver damper
position of the damper blades, which physically with parallel blades, or a guillotine damper is used. A
restrict the gas flow. From the foregoing, one can tell guillotine damper is generally of heavy construction
that "control damper" is the functional name of a and has one or two blades. Each blade slides
multi-blade louver damper. The damper blades may through a heavy track in the damper frame, literally
be arranged to act in parallel or opposition, slicing through the gas stream as the blade moves
depending on system needs. (See Figures 1, 2, AND from the open position to the closed position.
3) It should be noted that gate or guillotine dampers
(See Figures 4 and 5) are NOT recommended for The degree of isolation attained by a given damper is
control purposes. determined by its inherent physical ability to restrict
flow and by additional measures that may be taken to
There are several different varieties of control enhance its flow-restricting ability. Thus isolation
damper. dampers are further classified as follows:

4.1.1 Balancing damper. A balancing (control) 4.2.1 Shutoff damper. A shutoff (isolation) damper
damper is used to balance the flow of gas in one duct restricts flow to some specified amount of leakage,
of a system of ducts. Balancing in this sense does which can approach zero. The actual amount of
not always mean equal flow rate, but rather an leakage allowed is determined by the needs of the
apportioning of the total flow rate so that each duct customer's process. The amount of leakage is then
conveys the correct percentage of the total flow. specified to the damper manufacturer, and the
Once the correct percentage of flow is determined, a damper is designed accordingly.
balancing damper is usually permanently "set", i.e.,
the damper blades are locked in position. 4.2.2 Zero leakage damper. A zero leakage
(isolation) damper is not used for control purposes
4.1.2 Pre-set position damper. A pre-set position and thus is either in the open position (for full flow) or
(control) damper is normally open (NO) or normally the closed position (zero leakage).

4
AMCA 850-02 (R2011)

PARALLEL BLADE ARRANGEMENT


ON-OFF

OPPOSED BLADE ARRANGEMENT


MODULATING

Figure 1 - Parallel Blade and Opposed Blade Arrangements and Operation

5
AMCA 850-02 (R2011)

BLADE END SEAL BOLT HOLES FOR ATTACHMENT TO DUCT FLANGE


FRAME
BLADE

LINKAGE

HEIGHT
STUB
SHAFT

DRIVE
SHAFT

WIDTH
BEARING AND
BLADE EDGE SEAL PACKING GLAND

Figure 2 - Louver Damper Details

6
AMCA 850-02 (R2011)

FLOW RATE vs. DAMPER OPENING

100

90 PARALLEL
BLADES
80

70
PERCENT OF FLOW RATE

60

50

40

30 OPPOSED
BLADES
20

10

0
0 10 20 30 40 50 60 70 80 90
DEGREES OPEN

Note: This figure is typical, only. The relative blade open angle versus percent of flow rate will vary with system
pressure.

Figure 3 - Graphic Performance of Parallel vs. Opposed Blade Dampers

7
AMCA 850-02 (R2011)

LIFTING HOLE

SPROCKET

BEARING
BONNET

CHAIN
BONNET
BRACING
HANDWHEEL
TORQUE
TUBE

BLADE
ENTRY
SEAL

ACTUATOR

FRAME
BLADE
HEIGHT

BLADE
SUPPORT
SEAT

BOLT HOLES
WIDTH FOR ATTACHMENT
TO DUCT FLANGE

Figure 4 - Guillotine Damper Details

8
AMCA 850-02 (R2011)

BLADE

RACK ELEMENTS
PINION (ENGAGED BY
(EXTERNALLY DRIVEN) PINION TEETH)

Figure 5 - Guillotine Damper Rack-and-Pinion Drive Details

OPPOSTED BLADES (IF REQUIRED) PARALLEL BLADES


FOR MODULATION ON-OFF

P1 P2 P3

SHUTOFF VALVE SEAL AIR (P2 = P1 + 500 Pa (2 in. wg) MINIMUM


(BUBBLE TIGHT SHUTOFF OR AIR
URGED ZERO LEAKAGE VALVE)

Figure 6 - Seal Air System

9
AMCA 850-02 (R2011)

The typical damper used in such applications almost 5.1.2 Ambient leakage. Ambient leakage is leakage
always requires that the damper seals be pressurized either into or from the system. In a louver damper,
to a level higher than that of the gas that is to be ambient leakage can occur though openings that
restricted. This pressurization is accomplished by a allow damper blade shafts to pass through the frame.
seal air system that consists of a fan and an isolation This leakage can be controlled through the use of
valve as the minimum components. (See Figure 6) packing glands or stuffing boxes around the blade
The damper seals are enclosed in a cavity and seal shafts at those points.
air from a fan is fed through an isolation valve into the
cavity around the seals. It is usually the case that A guillotine damper is less susceptible to ambient
some seal air does leak through to the leakage, but high positive pressure can result in
downstream side of the damper. ambient leakage.

There are certain cases that do NOT require the use 5.2 Leakage path and leakage rate
of seal air (or purge air) but instead require, in some
combination: In the above, references were made to a leakage
flow through an opening of some kind. Effective
a. A goggle damper having a blade that extends design and careful manufacturing will minimize the
outside the damper frame. This damper would be total leak path area.
applicable if leakage of system gas to the
atmosphere is acceptable. Any calculation for estimating the leakage rate should
include pressure differential across the closed
b. A vacuum-breaking chamber or draft-interrupting damper, the temperature of the gas, and the leak
device for the isolation of negative pressure. path area.

c. The availability of a nearby induced draft fan, to 5.3 Factors affecting actual leakage
the inlet of which a connection may be made
for the evacuation of the area around the seals. The operating parameters of the system will dictate
actual leakage. Variations in pressure, temperature,
5. Damper Leakage erosive/corrosive conditions, and normal wear and
tear can all cause changes in the leakage rate,
Damper leakage is a flow of gas past the closed usually an increase. Physical deformation due to an
damper blade(s). The extent to which leakage upset condition or some other cause can also result
becomes a consideration in a damper application in an increase in the leakage rate.
depends on the nature and temperature of the gas
being handled through the system, and sometimes it 5.4 Selecting a damper to meet low to zero
depends on the application itself. Once it is leakage requirements
determined that leakage is a major consideration, it is
then necessary to consider containment. It is important to choose the right damper for the
application. The choice is often directly affected by
5.1 Leakage containment considerations of safety, system requirements, and
economics. In choosing a damper for low-to-zero
If it is decided that leakage is a major consideration, leakage service, several options are available.
it is next necessary to determine whether it is
necessary to address system leakage, ambient 5.4.1 Low leakage damper. A low leakage damper is
leakage, or both of these types. usually required to meet allowable system and
ambient leakage conditions as described above. A
5.1.1 System leakage. System leakage is leakage low leakage damper may be a multi-blade louver
across the closed damper blade(s) that remains damper, or as allowable leakage rates approach
within the system ductwork. The extent to which zero, a guillotine damper may be more suitable.
system leakage is allowed is defined in actual cubic Much of the choice depends upon the suitability of
meters per second (Am3/s) or actual cubic feet per materials for the application.
minute (ACFM), at a given temperature and
pressure. An alternate definition of leakage may be 5.4.2 Zero leakage damper. In order to provide an
the specification of an allowable percentage of some isolated condition at some downstream location, two
specified flow rate, such as design flow, normal flow, dampers and a seal air chamber are used. As shown
or maximum flow, in addition to giving the in Figure 1, the personnel -safe system consist of:
temperature and pressure. If no reference flow rate
is given, the assumed flow rate is the normal flow. a. A louver damper on the upstream side. If this

10
AMCA 850-02 (R2011)

damper is also used for flow modulation, an 5.4.3.2 Heated seal air. Heated seal air may be
opposed blade damper is used, and seal air may required in those cases where it is necessary or very
leak to the upstream duct. desirable that any seal air leakage upstream be at or
above the dew point temperature of the upstream
b. A seal air chamber into which pressurized air is system gas to minimize the acceleration of corrosion.
introduced. Among the important factors to be considered in
determining whether heated seal air is to be used:
Pressurization is generally 500 Pa (2 in. wg)
higher than the upstream pressure, at operating a. Heated seal air may restrict or severely delay
temperature. entry of personnel into the downstream section
for work
c. A louver damper on the downstream side. This
damper is generally a parallel blade two-position b. The capital cost of a heated seal air system is
louver damper. greater

5.4.3 Seal air. Seal air is used to provide a c. Operating costs for such a system are higher
pressurized barrier of clean air so that work may be
done in the ductwork downstream of the seal air d. The needed equipment is larger and requires
chamber. The pressure of the seal air system relative additional space
to the upstream system pressure is critical. The
volume of seal air must be such that it can overcome e. Additional controls are required
any leakage out of the seal air chamber. The sizing of
the seal air source requires that the system f. Additional instrumentation is required to monitor
temperature and pressure be fully accounted for. the output of the heated seal air system
When a motor is involved, it must be properly sized
to account for possible system abnormalities. For 6. Thermal Considerations
these reasons, seal air source sizing is usually left up
to the damper manufacturer. In those cases where In industrial process/power generation damper
multiple dampers or seal air chamber are involved, a applications, temperature plays a very important role,
single source might be utilized. There are two general as indicated by the following.
approaches to seal air: ambient and heated.
6.1 Normal operating conditions
5.4.3.1 Ambient seal air. Ambient seal air is
provided as produced by the seal air source, at a The normal operating temperature range must be
pressure consistent with the system requirements. defined, as well as any upset temperature range over
Ambient seal air is generally provided at a which the damper must operate. Peak temperatures,
temperature that ensures that isolation conditions are rates of temperature change, frequency and duration
provided down-stream of the seal air chamber. It of upsets must be defined if the manufacturer is to
should be noted that ambient seal air may be below design the equipment properly. For upset conditions,
the dew point of the upstream system gas and could it should also be stated whether the damper is
have an accelerating effect on system corrosion. expected to operate properly once the system has
returned to the normal operating range.
When a guillotine damper requires seal air, ambient
air is used. It is recommended that the user specify 6.2 Thermal stresses
whether an intermittent or continuous supply of seal
air is required. Such requirements may be discussed It should be noted that damper equipment
with the damper manufacturer. Consideration should components are designed to withstand the thermal
be given to requirements for the needed frequency of stresses of the specified conditions as well as the
isolation, power consumption of the seal air source, mechanical stresses, exclusive of external load.
and the effect of ambient air leakage into the
upstream system. It may be advantageous to operate
6.3 Leakage operating temperature
the seal air system continuously to aid in minimizing
both condensation and duct accumulation around the
When leakage criteria are specified, the temperature
seals and in the bonnet.
or range of temperatures over which the leakage
criteria must be met must also be specified.
Ambient seal air is generally recommended unless
there is a compelling technical reason why it should
not be used.

11
AMCA 850-02 (R2011)

6.4 Damper insulation f) Condensate chemicals and their dew point


temperatures
If the damper is to be insulated after installation, that
fact must be made known to the damper It should be noted that damper pressure drop
manufacturer, along with the following: calculations must necessarily be based on the actual
system gas. If a gas other than the actual system
a. Type and thickness of insulation to be applied to gas is used for pressure drop calculations, this fact
the mating ductwork must be so stated in the equipment specification.

b. Type and thickness of insulation to be applied to


the damper by others 8. Corrosion and Erosion

6.5 Thermal differential The damper specification should include the


following with respect to corrosion and erosion:
If the purchaser has cause to be concerned that
thermal differentials may affect the damper or the a) Minimum materials of damper construction
duct structure, the thermal differential across the
damper frame and closed blade must be specified. b) Corrosion rates for the specified materials at
normal operating conditions, and also at the
7. System Gas Analysis operating condition that produces the highest
rate of corrosion
7.1 General
c) Erosion rates at the normal system gas
The composition of the gas being conveyed through velocity, and at 1.5 times the normal system
the duct system is important to two aspects of the gas velocity
damper. It affects the kind of damper selected or
chosen, and it has a strong influence on the materials d) Estimated percent operation at other than
selected to construct the damper. It is also necessary normal operating conditions
to define any transient elements that the damper may
be subjected to. The composition of the system gas e) Desired damper life in years
and transients, as well as any other system
parameters, is the responsibility of the specifier, and A damper design can include specified allowances
this information must be included with the damper for corrosion. Where the corrosion rate is not
specifications. specified, the damper vendor makes a reasonable
estimate of the corrosion rate, but cannot be held
While much of this information is available from the responsible for their accuracy. Damper components
designers of the system process, similar existing subject to corrosive/erosive attack are designed to
systems may also provide valuable operational include known or estimated allowances above what
information that will aid in developing equipment that is required for mechanical strength alone. Typical
will provide satisfactory service. When actual system design considerations are discussed in Section 11.
information is not available, estimated values should
be established for expected areas of concern.
9. Control Range (See Figure 3)
7.2 System gas characteristics
The range over which a damper can provide effective
An analysis of system gas analysis typically includes flow control or isolation cannot be determined solely
the following: from flow conditions and damper configuration.
Control range is also a function of the duct system
a) Chemical composition configuration and other variables that come into play
when the damper is operated. In general, it is usually
b) Pressure, temperature and density the case that the best control is ensured when
damper size is minimized by designing for the
c) Entrained particulate matter, if any highest allowable pressure drop. It is important to
understand that the relationship of flow to damper
d) Dispersed liquids, if any openings is a function of many parameters, and a
model of the complete system is usually necessary to
e) Flow rate determine such a relationship.

12
AMCA 850-02 (R2011)

The choice of damper type may be influenced by the 10.1.1 Initial assumptions. In order to set a starting
type of control needed or desired. An opposed-blade point for damper pressure drop, the following initial
louver damper has a broader, more linear control assumptions are made:
range that can be effectively utilized with appropriate
controllers. This characteristic makes the opposed- a. System gas flow is uniformly distributed across
blade louver damper a good choice for flow the cross-section of the duct (fully developed
modulation applications, since the flow profile turbulent flow), and there is sufficient length of
remains essentially parallel to the axis of the duct. A straight duct before and after the damper to
parallel-blade louver damper, through which gas flow ensure that the damper pressure drop is not
is directionally diverted by the operating damper magnified. The magnification of resistance, or
blades and has higher pressure drop loss, is more performance loss, due to poor inlet and outlet
suitable for on-off damper applications. conditions is known as system effect. System
effect detracts from the performance of any
Note: A damper used in close proximity to a fan is component in a duct system. For further
always a special case subjected to varying pressure information on System Effect and how it detracts
and effect on fan performance that influence fan from fan performance, see AMCA Publication
control. A control damper for such an application 201.
should be coordinated with the fan manufacturer.
b. The direction of system gas flow entering and
Flow stability will also affect the control range. A exiting the damper is normal to the true cross-
model test is usually required to determine the effects section of the duct at any point in the system gas
of stability on control range. stream.

Response time of the controls is important when flow c. Incompressible flow conditions exist; i.e.,
conditions fluctuate rapidly. adiabatic and isentropic.

10. Pressure Drop The reader should note once again that these
assumptions might not reflect the actual conditions in
As system gas passes through a damper, there is a a system. It is recommended, however, that the
system pressure loss, or drop, due to the resistance system be designed to ensure that the above
of the damper itself. Pressure drop has its least effect assumptions are valid. See also Section 10.3 below.
on system performance when the damper is wide
open. It is therefore necessary to establish some 10.2 Pressure drop equation
standard conditions for determining damper pressure
drop so that system designers obtain accurate The general form of the equation used to calculate
information on the equipment, and for the fair damper pressure drop will be a modified form of the
evaluation of equipment proposed by vendors. The Bernoulli equation:
first standard condition is that pressure drop is to be
based on the damper being in the wide-open ⎛ ρ ×V 2 ⎞
position. In the case of a guillotine damper, this ΔP = K ⎜ ⎟
means that the blade, as designed, will be fully ⎝ 2g ⎠
retracted from the gas flow.
Where:
10.1 Pressure drop calculations
ΔP = Pressure loss in Pa (in. wg)
A calculated pressure drop is often the first step in K = Loss coefficient relative to the specific damper
determining the actual duct system pressure drop design sample, a non-dimensional number
that is due to the presence of the damper. When gas ρ = Density of the flowing system gas in kg/m3
flow is not uniformly distributed, has eddy currents, (lbm/ft3)
has an angle of attack greater than zero or contains V = Average velocity across the entrance to the
material in two phases (i.e., entrained fly ash or damper in m/s (ft/min)
dispersed liquids), the calculated pressure drop may g = Gravitational constant, m/s2 (ft/s2)
not be equivalent to the actual pressure drop. The
following material should make the reader aware of The value of K is dependent upon a number of
not only the calculation steps involved, but also some geometric factors including the entrance and exit
of the assumptions attendant in damper pressure coefficients, skin friction, and reduction or
drop calculations so that pressure drop information enlargement of flow area. The value of K should be
can be reviewed in the proper perspective. determined by test per AMCA Standard 500-D, and

13
AMCA 850-02 (R2011)

determined to be valid for a certain range of flow rate, a. Bending: 60% of the material yield strength
temperature and pressure. In the absence of a K
factor determined by test, the value of K is taken as b. Torsion: 35% of the material yield strength
the appropriate value for a square-edged orifice for
the arithmetic average of the actual flow area. c. Shear: 50% of the material yield strength

The general pressure drop equation above is used to 11.1.1.3 Creep. The effects of creep shall be
determine only that loss due to the addition of the considered in the design when operating temperature
damper into the duct system and does not include the exceeds 427°C (800°F).
loss due to ductwork upstream or downstream of the
damper. 11.1.1.4 Distortion. Each component shall be
designed to avoid function-limiting distortion during
10.3 System effect on damper specified normal operating conditions or upset
condition.
The physical orientation of upstream and
downstream ductwork relative to the damper can 11.1.1.5 Specific function during upset. When the
seriously affect the flow pattern into and out of the equipment specification requires that the damper
damper. If the orientation of a system is not as perform a specific function during an upset condition,
described under the assumptions made above, the the design of the damper shall accommodate the
actual pressure drop across the damper can be much requirement.
greater than would normally be expected. Some of
the variations that can cause a magnification of 11.1.1.6 Compressive loads. A component subject
pressure drop include: to a compressive load shall be designed for the
capability to transmit that load without exceeding the
a. Sudden reduction or enlargement in cross- allowable buckling strength of the member using
section area appropriate safety factors.

b. Duct turns immediately adjacent to the damper 11.1.2 Drive system.

c. Secondary flow of system gas into the ductwork 11.1.2.1 Basis of size. The drive system shall be
immediately adjacent to the damper sized to operate at the normal operating conditions,
or at conditions as required in the equipment
Again, these variations are not covered by the specification.
pressure drop equation given in Section 10.2. See
also Section 11.2 for mechanical effects. 11.1.2.2 Actuator size. The drive system demand at
the specified normal operating condition shall be
11. Damper Design Considerations specified by the damper manufacturer. The actuator
must be sized so that its rated output exceeds the
A custom-engineered damper is designed to meet calculated damper demand by at least 50%.
the parameters given in the equipment specification
according to design guidelines which may vary 11.1.2.3 Drive train design. The drive train shall be
slightly among manufacturers, but which are designed to accept the maximum actuator output stall
generally as follows: torque without component failure.

11.1 Mechanical / thermal stresses CAUTIONARY NOTE: There is the potential for field
operating personnel to apply input force on a hand
11.1.1 Damper wheel such that components in the gear train and
other drive components can be permanently
11.1.1.1 General. Damper components should be damaged. Care must be exercised that the maximum
designed so that no load-bearing component stress recommended input force recommended by the
calculated by conventional analysis shall exceed the damper manufacturer not be exceeded.
yield strength of the selected material, given an
appropriate factor of safety. 11.1.3 Allowable stress on material. The allowable
stress on a material shall be determined based on
11.1.1.2 Safety factors. Unless more conservative material yield strength at the specified normal
values are specified, the appropriate safety factors to operating temperature unless otherwise specified.
be used are:

14
AMCA 850-02 (R2011)

11.2 Stability 11.6.2 Transmitted loads and damper support.


Where possible, no external loads should be
There is an additional result of System Effect when a transmitted through the damper. Any external load to
damper is involved. Uneven flow characteristics have be imposed on the damper shall be given in the
the potential to cause excessive localized loading on equipment specifications.
damper components. Therefore, the location of the
damper in the system should be chosen carefully by A guillotine damper requires special consideration, as
the system designer. If uneven flow characteristics the damper flanges adjacent to the blade entry side
are anticipated, the location of a damper should be are non-load bearing. Moment loads are of the
reviewed with the damper manufacturer so that the greatest concern.
design of the equipment may account for potential
instability or allow the damper manufacturer to It is preferable that a damper be supported from a
recommend beneficial modifications to the duct duct flange on or near a duct support, with expansion
system. joints installed to minimize wind load, thermal
expansion loading, and vibration.
11.3 Deflection
When a damper is to be installed at the base of a
The damper manufacturer shall determine limits of stack, the design shall account for the stack load and
deflection in damper components so as to ensure bending moment as given in the equipment
reliable free operation of the assembled damper and specifications.
performance with respect to leakage.
11.6.3 Blade protrusion. The purchaser shall
11.4 Wind load specify when it is or is not allowable for the damper
blade(s) to extend beyond the damper frame.
Unless otherwise agreed to or specified, the damper
design shall include and allowance for a wind load of 12. Actuators
1.44 kPa/m2 (30lbf/ft2).
The type of actuator to be supplied with the damper
For horizontal projections, the live load shall be as is defined in the equipment specification by the type
given in the equipment specifications. of power source the actuator shall utilize. The three
types of power source most commonly used are:
11.5 Seismic loading manual, electric, or pneumatic. The choice of power
source should take into consideration the operating
Most dampers are analyzed as part of the duct time, failure mode, frequency of damper operation,
system in which they are installed. Where seismic availability of the power source at the damper
analysis is required, upon award of the damper location, the size of actuator required, and the
contract the damper manufacturer shall supply detail amount of force and/or speed required. The choice of
drawings and bills of material to the purchaser to aid power source may require the trading off of some
in seismic analysis of the damper by others. features for others which are more desirable in the
specific application.
11.6 Connection to ductwork

11.6.1 Dimensional requirements. The damper Selection of an actuator may depend on the failure
shall be designed to mate with ductwork that is mode requirements (the desired reaction of the
square within 1/1000 of the diagonal and flat within damper upon loss of control signal or power):
the allowable compression range of the selected
damper/ductwork gasket. a. Damper to stop in last position on loss of control
signal or loss of power to actuator;
It should be noted that a racked (distorted) duct will
cause the damper frame to be non-planar when b. Damper to open (or close) on loss of power to
attached to the ductwork with the possible result of actuator;
excessive leakage or binding during operation. Out-
of-square ductwork may also produce the same c. Damper to open (or close) on loss of control
results. Ductwork quality should ensure alignment signal to actuator.
such that no forces are imposed on the damper as
the result of attachment.

15
AMCA 850-02 (R2011)

12.1 Pneumatic Torque overload device, to disconnect power if an


excessive motor demand occurs.
12.1.1 Rotary. Rotary vane actuators provide
double-acting motion and are directly coupled to the Positioner, to provide control of the drive shaft in
main drive shaft of the damper for operation at a 90° response to a signal from a remote control device.
angle.
Manual override for emergency operation of
Cylindrical actuators are directly coupled to the main dampers.
drive shaft of the damper and provide double-acting
motion through a lever crank, a Scotch yoke, or a 12.4.2 Pneumatic actuator. Options include the
rack-and-pinion connection. following:

12.1.2 Linear. Suitable for quarter-turn dampers, a Limit switches, to indicate the position of the
double-acting linear actuator may be used to operate damper blade(s) or to activate/deactivate indicator
at a 90° angle via a crank and clevis. signals;

Guillotine or slide-gate dampers may use a direct Positioner, to satisfy which require that the drive
cylinder drive or a rotary actuator with a screw drive shaft be moved to a position called for by a remote
or an intermediate chain drive. control device. The control signal may be 2.068 to
10.342 kPa (3 to 15 psi) instrument air, or a
12.2 Electric conventional electric control signal of 4 to 20 ma, or
1 to 5 V dc converted to 2.068 to 10.342 kPa (3 to 15
An electric actuator consists of a reversible electric psi) by a transducer.
motor that applies actuation force through a drive
system. Fail-safe features, to return the damper to a position
upon loss of power air or control signal. This feature
12.2.1 Rotary. Rotary actuation force is applied may be accomplished via a spring return to create
through the drive system's self-locking gears. When resistance inside an air cylinder, or by providing an
used with a quarter-turn damper, the actuator is accumulator tank to store enough air pressure for
ordinarily shaft mounted. On a guillotine damper, the one additional cycle of operation.
actuator delivers actuation force through a screw or
chain drive. Manual override for emergency stop of actuator; not
available on all pneumatic actuators.
12.2.2 Linear. Linear actuation force is supplied
through a drive system consisting of a screw, 13. Testing
intermediate chain drive, or gears.
Tests of prototype or production units may be
The output is self-locking. The output can be direct- requested for design proof or product acceptance.
coupled to the main drive shaft of the damper, or at a The nature of the tests, location of tests, test
90° angle through a crank or clevis. procedures to be followed, remedies, and
acceptance criteria should all be established
12.3 Manual beforehand with the damper manufacturer in order to
ensure that tests are satisfactory. It should be noted
A manual actuator may be either the hand lever type at the outset that tests that involve the simulation of
or the hand lever-geared type. Frequently used with service conditions are expensive. Since these tests
a guillotine or slide gate damper, actuation force is are conducted at the customer's expense, they
applied through arrangements of winch-and-chain, should be carried out on a selective basis.
winch-and-wire rope, rack-and-pinion, or revolving
screw with captive nut. 13.1 Location of and schedule for testing

12.4 Options and accessories A damper test is normally conducted at the damper
manufacturer's premises, and scheduling is usually
12.4.1 Electric actuator. Options include the optimized to minimize delays between damper
following: production and shipment. The manufacturer has the
necessary test facility and test personnel. No
Limit switch(es), located outside the damper or shipment cost or time is involved, all of which
inside the actuator, to indicate the position of the minimize the cost to the purchaser. Testing at another
blade(s) or to control power. location or to a schedule that involves delays usually

16
AMCA 850-02 (R2011)

result in additional cost to the purchaser. c) Operating Time (Cycle time, open-to-close, or
close-to-open)
When the physical size of the equipment precludes d) Loose Material Obstruction
testing at the manufacturer's facility, a mutually e) Rigid Material Obstruction
acceptable test location should be agreed upon. f) Deflection ______ mm (in.)
g) Seal Air Cavity Required?
13.2 Functional tests h) Seal Air Cavity Pressure

These tests are normally conducted by the 13.3.3 Guillotine damper with seal air system.
manufacturer as a standard procedure. Since there is a) Leakage
wide variation in the information obtained, the b) Pressure Drop at 100% open
damper manufacturer should be consulted to c) Operating Time (Cycle time, open-to-close, or
determine whether the manufacturer's standard tests close-to-open)
provide sufficient information for the job, or whether d) Loose Material Obstruction
additional tests are required. e) Rigid Material Obstruction
f) Deflection
Functional tests are usually performed on a g) Seal Air Cavity Required?
simulation basis, wherein the equipment is positioned h) Seal Air Cavity Pressure
with respect to flow and gravity just as it will be
installed, or with those factors taken into 13.4 Test detail
consideration.
The details for testing the performance parameters
Functional tests are intended to prove satisfactory listed above should be in accordance with the
operation of a damper in the "as-built" condition outlines given below. The data to be recorded during
unless special arrangements are made to subject the the test, the presentation of results, and criteria for
damper to simulated temperature, pressure, acceptance should be agreed upon before any test
contamination, or other special conditions during the commences:
test.
13.4.1 Leakage. Leakage volume through the
Satisfactory functional testing does not relieve the damper shall be measured when subjected to the
damper manufacturer of responsibility for satisfactory operating pressure differential and the damper is
operation when it is installed and subjected to service closed by the actuator mechanism. The observed
conditions. leakage volume shall be adjusted for service
conditions of temperature and pressure.
13.3 Simulation test
13.4.2 Pressure drop. Pressure drop tests shall be
If it is determined that a simulation test is required, conducted on the damper, size permitting. When
such testing should be discussed with the damper equipment size precludes such a test, a model test
manufacturer. The results of most of such tests, if per AMCA Standard 500-D shall be the preferred
performed, require interpretation because they do not alternate test.
duplicate all the conditions to which the damper is to
be subjected in service. The following is a list of 13.4.3 Operating time. The damper shall be cycled
damper candidates for simulation testing, and the from open-to-close, and close-to-open, and the time
performance parameters that may be included in in seconds for each recorded.
such testing:
13.4.4 Loose material obstruction. A material shall
13.3.1 Louver damper without seal air system. be selected which resembles the anticipated duct
a) Leakage deposit conditions. The material shall be placed in
b) Pressure Drop at design flow the damper and the damper shall be cycled.
c) Operating Time (Cycle time, open-to-close, or
close-to-open) 13.4.5 Rigid obstruction. A mutually acceptable,
d) Loose Material Obstruction reasonably solid obstruction shall be selected for the
e) Rigid Material Obstruction test. The obstruction shall be placed in the path of the
f) Deflection ______ mm (in.) damper blades and the damper shall then be cycled
from open to closed in advance of pre-set shutoff
13.3.2 Louver damper with seal air system. switches to confirm the capacity of the drive
a) Leakage mechanism and the strength of damper components
b) Pressure Drop at design flow when subjected to a solid obstruction.

17
AMCA 850-02 (R2011)

13.4.6 Seal air cavity pressure. The seal air cavity cycling of the equipment.
pressure test shall be conducted with the damper in
the "as-built" condition and without differential 14.1.3 Submittal drawings. Upon award of the
pressure across the damper. contract, complete detailed submittal drawings shall
be prepared and submitted by the manufacturer, per
13.4.7 Seal air cavity volume. The manufacturer an agreed upon schedule, to the purchaser for
shall provide calculations to seal air volume and approval. Submittal drawings must be approved
pressure tests to actual operating conditions. before the start of fabrication. The drawings shall
exhibit system design parameters, interface
13.4.8 Deflection. The damper shall be subjected to dimensions, and performance data on accessories
loading to simulate loading as given in the equipment such as limit switches and actuators, et al. The
specification. The load shall be applied to the damper submittal drawings shall include or have attached a
blade(s) or other damper components (as applicable) bill of materials identifying the major components of
designated, and the deflection measured and recorded. the equipment.

14. Recommended Specifications 14.1.4 Welding. All welding to be done shall be


based on applicable sections of the American
A clear and detailed specification of the damper Welding Society codes or the ASME Section IX
equipment to be supplied is an important first step in welding code.
ensuring that the desired equipment can be properly
quoted, built, tested, installed and operated to the 14.1.5 Construction
satisfaction of all concerned. The specification should
ensure that the responses received will be from 14.1.5.1 The louver damper shall be constructed of
companies with sufficient resources and experience materials which meet the minimum requirements
to manufacture, test and deliver equipment which will given in the Specified Service Conditions.
meet the equipment specifications.
14.1.5.2 The stress level in any component subjected
14.1 Louver damper specification to structural design loads shall not exceed the
following percentage values of the yield strength of
This recommended specification is intended to serve the selected material at the temperature given in the
as a guide for the design and manufacture of heavy Specified Service Conditions:
duty louver dampers for industrial process or power
generation applications. a) Bending: 60%
b) Torsion: 35%
14.1.1 Scope c) Shear: 50%

14.1.1.1 This specification covers the supply of a 14.1.5.3 Creep shall be considered in the design of
heavy duty louver damper for the Specified Service the damper when operating temperature exceeds
Conditions. 427°C (800°F). Creep rate shall be based upon 1%
at 100,000 hours. The allowable percentage of stress
14.1.1.2 The damper shall be manufactured as based on creep shall not exceed the allowable
specified under Construction and shall be supplied percentages given for yield strength.
with an actuator and necessary limit switches and
other components as required. Unless otherwise 14.1.5.4 The damper frame shall be rolled/formed
specified, the damper shall undergo functional testing structural channel. The frame shall be designed to
by the manufacturer prior to shipment. meet the mechanical requirements resulting from the
Specified Service Conditions and also for
14.1.2 Quality program transportation and installation. The unit shall be self-
supporting, with no external support or bracing
14.1.2.1 All work, including design engineering, required. The damper frame shall be designed with
material procurement, fabrication and shipment shall sufficient stiffness to preclude binding in induced-
be as agreed upon between the purchaser and the draft applications and to prevent excessive leakage
manufacturer. across the damper under the pressure/temperature
given in the Specified Service Conditions.
14.1.2.2 The supplier's plant shall be accessible
during all phases of manufacture of the equipment. 14.1.5.5 The blade structure shall not be permanently
The purchaser shall be notified at least ten (10) days distorted by exposure to the maximum temperature
prior to the manufacturer's final inspection and given in the Specified Service Conditions. Allowances

18
AMCA 850-02 (R2011)

shall be made for thermal expansion/contraction of 14.2.1.2 The damper shall be manufactured as
the blade/axle assembly. Thermal expansion/contraction specified under Construction and shall be supplied
shall be controlled and directed away from the side of with an actuator and blade drive mechanism [and
the damper where the drive system is located. complete seal air system] as required. Unless
otherwise specified, the damper shall undergo
14.1.5.6 The damper blades shall be linked external functional testing by the manufacturer prior to
to the damper frame. Linkage between blades shall shipment.
be designed so that no blade may operate
independently of the others. The linkage shall be 14.2.2 Quality Program
completed, tested and fixed in position at the
manufacturer's facility. 14.2.2.1 All work, including design engineering,
material procurement, fabrication and shipment shall
14.1.5.7 Bearings used in the damper shall be be as agreed upon between the purchaser and the
(ball/sleeve/roller) type. Bearing selection shall take manufacturer.
into account jobsite ambient conditions and also heat
conduction from the damper shaft to the bearing. 14.2.2.2 The supplier's plant shall be accessible
during all phases of manufacture of the equipment.
14.1.5.8 Stuffing boxes are (required/preferred/ The purchaser shall be notified at least ten (10) days
optional) shall be secured to the damper frame at prior to the manufacturer's final inspection and
each shaft clearance hole in the frame and shall be cycling of the equipment.
filled with material which is stable under exposure to
both the system gas and to the ambient conditions. 14.2.3 Submittal drawings. Upon award of the
The stuffing box shall be designed and constructed contract, complete detailed submittal drawings shall
so that packing may be renewed without the removal be prepared and submitted by the manufacturer, per
of linkage or other drive system components. an agreed upon schedule, to the purchaser for
approval. Submittal drawings must be approved
14.1.5.9 Seals at the blade edges and the blade ends before the start of fabrication. The drawings shall
are (required/not required/optional). The material exhibit system design parameters, interface
shall be suitable to withstand the Specified Service dimensions, and performance data on accessories
Conditions. such as limit switches and actuators, et al. The
submittal drawings shall include or have attached a
14.1.5.10 The actuator and all drive system bill of materials identifying the major components of
components shall be sized with a minimum safety the equipment.
factor of 50%, based upon the Power required to
operate the damper under the normal operating 14.2.4 Welding. All welding to be done shall be
conditions given in the Specified Service Conditions. based on applicable sections of the American
Welding Society codes or the ASME Section IX
14.1.5.11 The actuator mounts shall be furnished and welding code.
installed on the damper frame by the damper
manufacturer. 14.2.5 Construction.

14.2 Guillotine damper specification 14.2.5.1 The guillotine damper shall be constructed
of materials which meet the minimum requirements
This recommended specification is intended to serve given in the Specified Service Conditions.
as a guide for the design and manufacture of heavy
duty (personnel-safe) guillotine dampers for industrial 14.2.5.2 The stress level in any component subjected
process and power generation applications. to structural loads shall not exceed the following
percentage values of the yield strength of the
14.2.1 Scope selected material at the temperature given in the
specified service conditions:
14.2.1.1 This specification covers the supply of a
heavy duty (personnel-safe) guillotine damper for the a) Bending: 60%
Specified Service Conditions. b) Torsion: 35%

Note: If the personnel-safe features are not required, 14.2.5.3 The damper frame shall be rolled or formed
the [bracketed] phrases may be omitted. They are structural steel. The frame shall be designed to meet
included to provide the most comprehensive sample the mechanical requirements resulting from the
specification. Specified Service Conditions and also for transport

19
AMCA 850-02 (R2011)

and installation. The unit shall be self-supporting, 15. Sample Specification Checklist
with no external bracing or support required. The
damper frame shall be designed to support the The final purchase specifications for a damper are
extended blade, and to withstand the loads of the often an accumulation of diverse sets of documents.
drive system, and wind/snow loads. The accumulation will consist of purchase order
forms and related contractual papers. Each
14.2.5.4 If blade support(s) is(are) required to purchaser has its own set of special forms,
restrain the closed blade, it(they) shall be designed to standards, and operating procedures that might be
minimize pressure drop through the damper. included as contractual papers.

14.2.5.5 The blade shall be of single-thickness plate The information in these documents will include a
or an equivalent thermally-compatible structure. technical description of the damper and details of the
Blade deflection under any specified operating specific requirements of the installation. The
condition (blade extended, retracted, or partially information developed should be the result of a
open) shall not exceed the lesser of one-half the dialogue between the purchaser and the damper
thickness of the blade material or 1/360th of the manufacturer, initiated by a Request for Proposal or
blade width. Invitation to Bid (see sample form Section 15.1). The
manufacturer will respond (see sample form Section
14.2.5.6 The damper blade shall withdraw clear of 15.2), often with comments and suggestions for
the duct when in the open position. alternative equipment or options.

14.2.5.7 The bonnet shall be of the (open/closed) This section is intended to assist in that dialogue.
type. Form Section 15.1 may be copied and filled in, or
may be used as a checklist against a form preferred
14.2.5.8 Seals shall be designed and located on the by the purchaser.
damper to allow replacement without the need for
removing the damper from the duct. When completing form Section 15.1, the purchaser
should refer to and include copies of any proprietary
14.2.5.9 Flexible seals shall be of such design and specifications covering motors, actuators, surface
material to ensure proper spring retention and preparation, painting, and accessories, as applicable.
memory through the entire operating range from
ambient to Specified Service Conditions. Providing a completed form Section 15.1 (or its
equivalent) together with all the applicable data will
14.2.5.10 A seal air blower shall be provided and give the manufacturer the information he needs to
sized to provide 500 Pa (2 in. wg) pressure more than develop a complete, competitive and responsive
the differential pressure across the closed damper at proposal.
the Specified Service Conditions.
Form Section 15.2 may be used as a checklist to
14.2.5.11 A shut-off device with a suitable actuator ensure that the manufacturer's proposal is complete
shall be located between the seal air blower and the and responsive to the user's requirements.
damper to prevent reverse flow of flue gas through an
idle blower. 16. Installation Instructions
14.2.5.12 The damper blade shall be operated either To ensure that industrial process / power generation
by chain-and-sprocket(s), lifting screws, or rack-and- dampers operate satisfactorily it is essential that they
pinion. be properly installed. Before starting work on ANY
installation, the manufacturer's instructions should be
14.2.5.13 The damper operating drive system shall carefully reviewed and thoroughly understood. The
consist of a suitable power drive motor, sized for a manufacturer should be contacted and any difficulties
minimum safety factor or 50% based on the resolved before the installation work is started.
maximum power required to operate the damper
under the Specified Service Conditions.

14.2.5.14 Each component in the drive system shall


accept the running-stall output of the power drive
motor without failure.

20
AMCA 850-02 (R2011)

GENERAL INFORMATION

Request prepared by: Project Name or Code: Date:


____________________ ________________________ ______________________

Req’d submittal date: _______________________ Plant location: ______________________________

Proposal valid until: ________________________ Designated FOB point: _______________________

Return proposal to: Est. date of contract award: ___________________

________________________________________ Est. shipping start date: ______________________

________________________________________ Est. shipping end date: _______________________

________________________________________ Est. date for completion: ______________________

Available specifications (motor, accessory & paint specs, etc.): _____________________________________

_______________________________________________________________________________________

INSTALLATION AND SITE CONDITIONS

Barometric pressure: ______ (Pa/in. Hg) Maximum temperature: ______ (°C/°F) Wind load: ______ (N/m2)

or altitude: ______________ (m/ft) Minimum temperature: ______ (°C/°F) _______________(lbf/ft2)

DATA REQUIRED FOR EACH ITEM

Item identification: _____________ _____________ _____________ _____________

Quantity req’d: _____________ _____________ _____________ _____________

Type of damper: _____________ _____________ _____________ _____________

Width inside frame: _____________ _____________ _____________ _____________

Height inside frame: _____________ _____________ _____________ _____________

Maximum frame,
face-to-face: _____________ _____________ _____________ _____________

DAMPER ORIENTATION (Horizontal, vertical or stated angle from horizontal)

Width orientation: _____________ _____________ _____________ _____________

Height orientation: _____________ _____________ _____________ _____________

Figure 15.1 - Request for Quotation or Invitation to Bid (Page 1)

21
AMCA 850-02 (R2011)

DAMPER ORIENTATION (Horizontal, vertical or stated angle from horizontal) (continued)

Top or bottom entry


for non-horizontal
guillotines: _____________ _____________ _____________ _____________

Item identification: _____________ _____________ _____________ _____________

Sealing direction
(same as or opposite
to flow direction): _____________ _____________ _____________ _____________

MATERIAL MINIMUMS

Frame: _____________ _____________ _____________ _____________

Bonnet: _____________ _____________ _____________ _____________

Blade: _____________ _____________ _____________ _____________

Shaft: _____________ _____________ _____________ _____________

Seals: _____________ _____________ _____________ _____________

Type of bearings: _____________ _____________ _____________ _____________

DESIGN FLOW & LEAKAGE

Maximum flow rate,


ACMS or kg/hr;
ACFM or lbm/hr: _____________ _____________ _____________ _____________

Allowed gas leakage,


ACMS or ACFM at
normal differential
pressure and temp: _____________ _____________ _____________ _____________

Allowed gas leakage,


ACMS or ACFM to
atmosphere at normal
operating temperature
and pressure: _____________ _____________ _____________ _____________

TEMPERATURE AND PRESSURE SERVICE CONDITIONS

Maximum operating
temperature, (°C/°F) _____________ _____________ _____________ _____________

Normal operating
temperature, (°C/°F) _____________ _____________ _____________ _____________

Upset transient
temperature, (°C/°F) _____________ _____________ _____________ _____________

Figure 15.1 - Request for Quotation or Invitation to Bid (Page 2)

22
AMCA 850-02 (R2011)

TEMPERATURE AND PRESSURE SERVICE CONDITIONS (Continued)

Duration and frequency


of upset transient: _____________ _____________ _____________ _____________

Normal operating
pressure, (Pa/in. wg) _____________ _____________ _____________ _____________

Normal closed differen-


tial pressure, (Pa/in. wg)_____________ _____________ _____________ _____________

Item identification: _____________ _____________ _____________ _____________

GAS & DEPOSIT CONDITIONS

Gas analysis: _____________ _____________ _____________ _____________

Gas dew point temp-


erature, (°C/°F) _____________ _____________ _____________ _____________

Gas dust load,


(kg/m3/grains/ft3) _____________ _____________ _____________ _____________

Estimated depth of
duct deposit: _____________ _____________ _____________ _____________

Estimated tensile
strength of duct
deposit: _____________ _____________ _____________ _____________

Estimated shear
strength of duct
deposit: _____________ _____________ _____________ _____________

ACTUATOR AND ACCESSORY REQUIREMENTS

Type of actuator: _____________ _____________ _____________ _____________

Required operating
time (max or min): _____________ _____________ _____________ _____________

Limit switches (Y/N): _____________ _____________ _____________ _____________

Torque overload
protection: _____________ _____________ _____________ _____________

Manual override (Y/N): _____________ _____________ _____________ _____________

Heaters in motors or
Limit switch housing
(Y/N): _____________ _____________ _____________ _____________

Figure 15.1 - Request for Quotation or Invitation to Bid (Page 3)

23
AMCA 850-02 (R2011)

ACTUATOR AND ACCESSORY REQUIREMENTS (Continued)

Remote position
Indicator (Y/M): _____________ _____________ _____________ _____________

POWER SUPPLIES, ELECTRIC AND COMPRESSED AIR

Electric:
Volts, Phase, Hz. _____________ _____________ _____________ _____________

Plant air: (Pa/psi) _____________ _____________ _____________ _____________

Instrument air, (Pa, psi) _____________ _____________ _____________ _____________

Modulating control _____________ _____________ _____________ _____________

Figure 15.1 - Request for Quotation or Invitation to Bid (Page 4)

24
AMCA 850-02 (R2011)

GENERAL AND CONTRACTUAL INFORMATION

• Damper manufacturer • Reference to quotation request • Quotation submitted by

• Quote sent to attention of: • Issue date • Validity date limit of quote

• Manufacturer’s job reference • Purchaser’s reference • FOB point & shipping terms

• Surface finishes & paint specs • Contract terms • Price per item

• Statement of manufacturer’s compliance to quote request / invitation to bid

TECHNICAL DATA

MAJOR COMPONENT & MATERIAL SIZE ACTUATOR DATA

• Frame • Bonnet • Actuator make & model


• Motor power
• Blade • Shaft • Maximum stall torque
• Maximum stall torque
• Seals • Type of drive • Required torque including safety factors
• Operating times, seconds, from full closed
• Type of bearings to full open

SEAL AIR SYSTEM (if required) ACCESSORY ITEMS (if required)

• Fan make & model • Installed power • Limit switches:


--- Number & type
• Operating power: damper open, --- External mount or in actuator
damper closed and sealed • Motor heaters
• Positioners
• Seal air isolation device • Remote position indicators
• Seal air parameters:
--- Pressure at fan outlet
--- Required volume, including safety factor

SIZE AND WEIGHT OF ASSEMBLY PERFORMANCE INFORMATION

• Dimensions inside frame • Pressure drop (Pa/in. wg) added to system by


full-open damper at maximum flow rate
• Estimated overall dimensions
including accessories: • Guaranteed leakage rate at operating
--- Across closed damper
• Assembled weight --- To (or from) atmosphere

• Number of shipping pieces per damper,


including accessories

Figure 15.2 - Quotation Response Checklist

25
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
E-Mail : info@amca.org Web: www.amca.org

The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.

You might also like