Indoor Voltage Transformers: TJP 7.x
Indoor Voltage Transformers: TJP 7.x
TJP 7.x
Indoor voltage transformers
Fuses [A] 2
Description
The TJP 7.x epoxi insulated voltage transformers are casted Rated primary voltage ... 30/√3 kV; 33/√3 kV; 35/√3 kV
in epoxi resin and designed mostly for insulation voltages from Other primary voltages can also be supplied on request.
36 kV to 38,5 kV. Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy
Insulation voltages different from the above are to be the classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection
subject of an agreement between the manufacturer and the winding).
customer. Other secondary voltages can also be supplied on request.
If no a different value is required the transformers are Rated voltages for open-delta connection: ... 100/3 V; 110/3
manufactured with a overvoltage factor of 1.9 x Un/8 hrs. V- class 6P
One outlet of the primary winding, including the respective Other voltages for open-delta connection can also be
terminal is insulated from the earth to a level which supplied based on customer requirement.
corresponds to the rated insulation value. The other outlet Rated frequency ... 50 Hz; 60 Hz
of primary winding with its terminal is earthed during the Based on a discussion with the manufacturer the transformer
operation. Most of the transformers are equipped with two can also be provided with primary winding designed for two
secondary windings, the first one for either measuring or different primary voltages (with secondary side changeover).
protection purposes, the other for being connected into The transformers are manufactured conformably to the
an open-delta connection in a three-phase system. One requirements and recommendations of the following
terminal of each secondary winding and one of the open- standards and regulations: IEC, VDE, ANSI, BS, GOST and
delta connected terminals have to be earthed during the ČSN.
transformer operation.
The secondary windings are lead out into a casted-type
secondary terminal board. The secondary terminal board is
covered with a transparent plastic over which can be sealed.
The transformer can be mounted in any position. The
transformer body is fixed by using four screws, the bolted M8
earthing clamp is located on the transformer base plate. The
TJP 7.x transformers are equipped with a special fuse of 2 A
rated current. There are 2 versions of primary terminal – see
drawing TJP 7.1 - short terminal (for ZS 3.2) and TJP 7.2 -
long terminal (for Unisafe 36)
Dimensions
612 666
462 (150)
쏗100
쏗100
A
414
A
364
쏗
414
14
-P
364
쏗
g1
14
6
-P
M8
g1
6
74
M8
40
22
74
182 180 55 96
40
22
203 250
4
182 180 55 96
20
203 250
4
20
14
A 4x
쏗
A
HUB18
쏗100
쏗84
225
250
쏗25
쏗100
225
250
쏗84
쏗25
A
쏗
300 14
HUB 18
383 300
7 HUB 18
642 383
696 54
a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated
transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings,
with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the
auxiliary (residual) winding.
2
Standard execution of the transformers
Primary Secondary voltage Residual winding
voltage,V voltage,V accuracy burden, VA voltage,V accuracy burden, VA
30000/√3 100/√3 0,2 10,15,25
30000/√3 100/√3 0,2 10,15,25 100/3 6P 50
3
1VLC000526 – Rev 2, en 2011, 01.15
Primary (HV) terminal
ABB s.r.o.
PPMV Brno
Videnska 117
619 00 Brno, Czech Republic
Tel.: +420 547 152 602
+420 547 152 614
Fax: +420 547 152 626
E-mail: info.ejf@cz.abb.com
www.abb.com
The data and ilustrations in this catalogue are not binding. We reserve the right to make
changes of the content, in the course of technical development of the product.