You are on page 1of 22

BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-63

CHAPTER 6
REINFORCEMENT, METAL AGCESSORIES, AND ANGHOR BOLTS

TMS 402 CODE COMMENTARY

6.1 Reinforcement 6.1 Reinforcement


- -
When the provisions of this section were originally
developed in the late 1980s, the Committee used the 1983
edition of the ACI 318 Code as a guide. Some of the
requirements were simplified and others dropped,
depending on their suitability for application to masonry.
6.1.1 Embedment
Reinforcing bars shall be embedded in grout.
6.1.2 Size of reinforcement 6.1.2 Size of reinforcement
6.1.2.1 The maximum size of reinforcement 6.1.2.1 Limits on size of reinforcement are based
used in masonry shall be No. I I (M #36). on accepted practice and successful performance in
construction. The No. 11 (M#36) limit is arbitrary, but
Priestley and Bridgeman{l974) shows that distributed small
bars provide better performance than fewer large bars.
Properties of reinforcement are given in Table CC-6.1.2.
6.1.2.2 The diameter of reinforcement shall not 6.1.2.2 Adequate flow of grout necessary for
exceed one-half the least clear dimension of the cell, bond good bond is achieved with this limitation.
beam, or collar joint in which it is placed.
6.1.2.3 Longitudinal and cross wires of joint 6.1.2.3 The function ofjoint reinforcement is to
reinforcement shall have a minimum wire size of Wl.l (MW7) control the size and spacing of cracks caused by volume
and a maximum wire size of one-half the joint thickness. changes in masonry as well as to resist tension (Dickey
(1982)). Joint reinforcement is commonly used in concrete
masonry to minimize shrinkage cracking. The restriction on
wire size ensures adequate performance. The maximum wire
size of one-halfthe joint thickness allows free flow of mortar
around joint reinforcement. Thus, a 3/16-in. (4.8-mm)
diameter wire can be placed in a 3/8-in. (9.5-mm) joint.
Joint reinforcement is available in ladder type
(perpendicular cross wires) and truss fype (diagonal cross
wires). Where vertical reinforcement is present in a
masonry wall, location of the truss type joint reinforcement
may conflict with the vertical reinforcement.
6.1.2.4 Area of vertical reinforcement shall not
exceed 6 percent ofthe area ofthe grout space.

6.1.2.5 The nominal bar diameter shall not 6.1.2.5 This requirement is based on the
exceed one-eighth of the least nominal member dimension. research conducted by Soric and Tulin (1987).

6.1.3 Placement of reinforcement 6.1.3 Placement of reinforcement


6.1.3.1 The clear distance between parallel bars Placement limits for reinforcement are based on successful
shall not be less than the nominal diameter of the bars. nor construction practice over many years. The limits are intended
less than I in. (25.4 mm). to facilitate the flow ofgroutbetweenbars. Aminimum qpacing
between bars in a layer prevents longitudinal spliuing of the
6.1.3.2 In columns and pilasters, the clear masonry in the plane ofthe bars. Use ofbundled bars in masonry
distance between vertical bars shall not be less than one and
construction is rarely required. Two bars per bundle is
one-half multiplied by the nominal bar diameter, nor less
considered a practical maximum. It is important that bars be
than ltlzin. (38.1mm).
placed accurately. Reinforcing bar positioners are available to
conffol barposition.
TMS 402-16

TMS 402 CODE COMMENTARY


E'$
EG' 6.1.3.3 The clear distance limitations between
ld
lri bars required in Sections 6.1 .3.1 and 6.1.3.2 shall also apply
6E to the clear distance between a contact lap splice and
SE
$E
adjacent splices or bars.
aE 6.1.3.4 Groups of parallel reinforcing bars
Eo
F(J bundled in contact to act as a unit shall be limited to two
in any one bundle. Individual bars in a bundle cut off
within the span of a member shall terminate at points at
least 40 bar diameters apart.
6.1.3.5 Reinforcement embedded in grout shall
have a thickness of grout between the reinforcement and
masonry units not less than llq in. (6.4 mm) for fine grout
or lz in. (12.7 mm) for coarse grout.
I

6.1.4 Protectionofreirforcernent ...:-.....=6,*14;",.,fu*tedbnaf rcirfrrcga.r".mt


6.1.4.1 Reinforcing bars shall have a masonry 1r,i{'a;1!1'.i!1','.t1:t.
6.1.4.1 Reinforcing bars are raditionally not
cover not less than the following: l'1 offi for corrosion resistancg. The masonry cover retards
cOrypsion,of the stee[. Cover is measured from the exterior
(a) Masonry face exposed to earth or weather: 2 in. ,
(50.8 mm) for bars larger than No. 5 (M #16); lt/zin. ',i!" tlt l-,ffio
srnface ofthe reinforcement
in$er,@rirement applies. [t is measured to the
(38.1 mm) for No. 5 (M #16) bars or smaller. ';ffi,u*tridh,thC
r;,q@ qdqq,cf stimrpp or ties, if tansverse reinforcement
(b) Masonry not exposed to earth or weather: ltlzin. ii#1ffilffi 1'{f{g4 b,
: ffi4ror,ry cover includes the thickness of
(38.1 mm). ''mdisonry tmtts, mortai, and grout. At bed joints, the protection
for reinforcernent is the total thickness of mortar and grout
from the exterior of the mortar joint surface to outer-Lort
surface ofthe reinforcement or metal accessory.

The condition "masonry face exposed to earttr or weathef'


refers to direct exposure to moisture ihaogs (altemate wetting
and drying) and not just temperature changes.

,,11,l,I4blt GQS.li3rr Phys,te?|, prgmrties:of steel reinforcing wire and bars


:, t r-Io fifi. ' sb; in.zr' Perimeter, in.
iir;i,.,(g$lt'. . '.,r,{mr.n-i) ,(rnm) ,

: :,
'::;',:: :.: .:'::1. :,:

fi;011 (?,,1'1), 0.380 {e.71


10.0t? (x1.0) 0,fi$1 {11.8}
,,'#rCIt0 {i2.9}, ,0,$0.S,(12,9), ,

,':$!lW!l fi,58 , (14;9)


{l7i#) , :

:",ff,ii,W $l.S) 0.?85 (r9.9)

filfiiffi,,tit,li.: ; ,. ,,: ,,iii\ .::i.;i)| J:

,:', :
,:

:..

t|it,
.ll .ffi,iii11lj, ffi.!,fr|,iffifil,,,,: ',,sifl'(?1.0J' 1',1?g {29,9f i

ir Wffit$l,ttti;ii:
't:/friilr/!ffi
d:l?+ilit) Slzo (]79), 1.57t (39,9,j
liffi#EtffiEn i,lli , *#,a#"h:l
','jl l/li, :;itr.:t, ,,!'fi"[fi.L(2CI0*,, , : \,i9,1t61,,,1"$,,Pr:"9,I., t,,
ti'Wilfiitillf.##.t'Wli:, rffii,rotfi, i r
,.,$94 (2$4, ,: 2,frii*i6(59i8 ,:
i,,:ffiiffl, i:i, tfi,i:l#)ls fri#,:|i offi
0
(3s7) 2.74i9 (69.8),
Er, i#,i?W|$,\rtitt ii*;iuspi{? ,$}, {f r0}; ?, .t,;;, 2 (79.8).
11ffi;ffiiiffi,lW,Wntt i:*,llfrfl'{ ;.Y.1' ,I ,(645), 3;fri:M (90.0;,:',
',',t270'(30,-;fi) ,t,2? (g\g) 3.9e0 (r01)
':Noi;t ;,ffi3?I,, :l;410 (3$:r8) tr:.55 (1006) 4,$A (113)
.,,No1; ,,(tr1{#}6). :
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-65

TMS 402 CODE COMMENTARY

6.1.4.2 Longitudinal wires ofjoint reinforcement 6.1.4.2 Because masonry cover protection for
shall be fully embedded in mortar or grout with a minimum joint reinforcement is minimal, the protection of joint
cover of s/s in. (15.9 mm) when exposed to earth or weather reinforcement in masonry is required in accordance with
and I lz in. (12.7 mm) when not exposed to earth or weather. the Specification. Examples of interior walls exposed to a
Joint reinforcement shall be stainless steel or protected from mean relative humidity exceeding 75 percent are natatoria
corrosion by hotdipped galvanized coating or epoxy coating and food processing plants.
when used in masonry exposed to earth or weather and in
interior walls exposed to a mean relative humidity exceeding
75 percent. All other joint reinforcement shall be mill
galvanized, hot-dip galvanized, or stainless steel.

6.1.5 Development 6.1.5 Development


6.1.5.1 Development of bar reinforcement in 6.1.5.1 Development of bar reinforcement in
tension or compression The required tension or tension or compression From a point of peak stress in
compression reinforcement shall be developed on each side
-
reinforcement, some length of reinforcemsnt or anchorage
of the critical section by development length, hook, is necessary through which to develop the stress. This
mechanical device, or combination thereof. See Section development length or anchorage is necessary on both sides
6.1.9 for critical sections. of such peak stress points, on one side to transfer stress into
and on the other to transfer stress out of the reinforcement.
Often the reinforcement continues for a considerable
distance on one side of a critical stress point so that
calculations need involve only the other side; for example,
the negatiye moment reinforcement continuing through a
support to the middle of the next span.

Bars and longitudinal wires must be deformed.

6.1.5.1.1 Development length of bars 6.1.5.1.1 Development length of bars


grouted in clay masonry and concrete masonry The grouted in clay masonry and concrete masonry The
-
required development length of reinforcing bars shall be
-
clear spacing between adjacent reinforcement does not
determined by Equation 6- I , but shall not be less than 12 in. apply to the reinforcing bars being spliced. Refer to
(305 mm). Commentary 6.1.6. l. l. I for further inforrnation.

The factor K in Equation 6-l accounts for the beneficial

la =
o.Bdl f ,y (Equation 6-l)
effect of increased reinforcing bar cover and spacing in
KE delaying the onset of spliuing of the masonry leading to
pull out of the reinforcing bar. The 9dt limit on K is based
on studies by Schultz (2004,2005) as well as testing and
K shall not exceed the smallest of the following: the
subsequent analysis by the National Concrete Masonry
minimum masonry cover, the clear spacing between
Association (2009). NCMA (2009) recommended that K
adjacent reinforcement splices , and 9dt .
be limited to 8.8da, which is rounded to the cunent 9du
y : 1.0 for No. 3 (M#10) through No. 5 (M#16) bars; limit. When cover and spacing exceeds this amount,
splitting is not expected to occur and there is no benefit
y : 1.3 for No. 6 (M#19) through No. 7 (M#22)bars;
from additional cover or spacing.
and
The 50 percent increase in development length for
y : 1.5 for No. 8 (M#25) and larger bars. epoxy-coated bars does not apply to the t2 in. (305 mm)
minimum.
Development length of epoxy-coated bars shall be taken
as 150 percent ofthe length determined by Equation 6-1.

6.1.5.1.2 Development length of bars in 6.1.5.1.2 Development length of bars in


grouted AAC masonry The required development length grouted AAC masonry Development and lap splice
-
of reinforcement shall be determined by Section 6.1.5.1.1,
- conventional masonry are
detailing provisions for
and replac irg "f with f '* and K with K.,t..tc r{t Equation 6- I
' . calibrated to the masonry assembly strength, /'., which
^
Katc shall not exceed the smallest of the following: the includes the contribution of each constituent material (unit,
minimum grout cover, the clear spacing between adjacent grout, and mortar). Due to the low compressive strength of
reinforcement splices, and 9dt. AAC, however, the AAC masonry component is ignored
and the calibration is based on.f 's.
c-66 TMS 402-16

TMS 402 CODE COMMENTARY


tt(o
E(c' 6.1.5.1.3 Standard hooks Standard hooks in 6,1.5.1.3 Standard hooks In compression,
5o
E'i tension shall -
be considered to develop an equivalent hooks are ineffective and cannot be used-as anchorage.
6E embedment length, 1", as determined by Equation 6-2. Hooks
8E
rt shall not be used to develop bars in compression.
oE l": dt (Equation 6-2)
Eo
F()
13

6.1.5.2 Development of wires in tension


development length of wire shall be determined -The
by
Equation 6-3, but shall not be less than 6 in. (152 mm).
la:48 dt (Equation 6-3)

Development length of epoxy-coated wire shall be taken


as 150 percent of the length determined by Equation 6-3.

6.1.6 Splices
6.1.6.1 Splices of bar reinforcement
Reinforcement splices shall comply with Section 6.1.6.1.1,
6.1.6.1.2, 6.1.6.1.3, or 6. 1 .6.1.4.

6.1.6.1.1 Lop splices of bar reidorcement


6.1.6.1.1.1 The minimum length of lap
for bars in tension or compression shall be determined by
Section 6.1.5.1.1 for clay masonry and concrete masonry
and by Section 6.1.5. 1.2 for AAC masoffy, but not less than
12 in. (305 mm).
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-67

TMS 402 CODE COMMENTARY

6.1.6.1.1.2 For clay masonry and 6.1.6.1.1.2 An extensive testing


concrete masonry, where reinforcement consisting of No. 3 program conducted by the National Concrete Masonry
(M#10) or larger bars is placed transversely within the lap, Association (NCMA (2009)) and additional testing done by
with at least one bar 8 in. (203 mm) or less from each end Washington State University (Mjelde et al (2009)) show
of the lap, the minimum length of lap for bars in tension or that reinforcement provided transverse to lapped bars
compression determined by Equation 6-l shall be permitted controls longitudinal tensile splitting of the masonry
to be reduced by multiplying by the confinement factor, (, assembly. These transverse bars increase the lap
determined in accordance with Equation 6-4. The clear performance significantly, as long as there is at least one
space between the transverse bars and the lapped bars shall No. 3 (M#10) transverse reinforcing bar placed within 8 in.
not exceed 1.5 in. (38 mm) and the transverse bars shall be (203 mm) of each end of the splice. These bars must be
fully developed in grouted masonry. The reduced lap splice fully developed and have a clear spacing between the
length shall not be less than 36dn. transverse bars and the lapped bars not exceeding 1.5 in.
(38 mm). Testing also indicated that the lap length must be
) 7/
= I .0
6'd; ( Equation 6-4 ) at least 36dt or the effect of the transverse reinforcement is
minimal. As a result, this limit was applied to the lap length.
The testing also showed that even when more transverse
) 1A
Where;:{a_s1.9 reinforcement area is provided, it becomes significantly
d; less effective in quantities above 0.35 in.2 (226 mmz). Thus,
the transverse reinforcement area at each end of the lap, A,r,
A,, is the area of the transverse bars at each end of the
is limited to 0.35 in.z 1226 mrn2;, even if more is provided.
lap splice and shall not be taken greater than 0.35 in.2
(226 mm2).

6.1.6.1.1.3 Reinforcement spliced by 6.1.6.1.1.3 If individual bars in


noncontact lap splices shall not be spaced transversely noncontact lap splices are too widely spaced, an
farther apart than one-fifth the required length of lap nor unreinforced section is created, which forces a potential
more than 8 in. (203 mm). Noncontact splices are not crack to follow a diagonal line. Lap splices in clay masonry
permitted in AAC masonry. and concrete masonry may occur with the bars in adjacent
grouted cells if the requirements of this section are met.

6.1.6.1.2 Welded splices of bar reinforcement 6.1.6.1.2 Welded splices of bar


Welded splices shall have the bars butted and welded to reinforcement A full welded splice is primarily intended
-develop at least 125 percent of the specified yield streng"h,.f,,,
-
for large bars (No. 6 [M#19] and larger) in main members.
ofthe bar in tension or compression, as required. Welding shall The tensile strength requirement of 125 percent of specified
conform to AWS Dl.4/Dl.4M. Reinforcement to be welded yield strength is intended to ensure sound welding, adequate
shall conform to ASTM A706, or shall be accompanied by a also for compression. It is desirable that splices be capable of
submittal showing its chemical analysis and carbon equivalent developing the ultimate tensile strength of the bars spliced,
as required by AWS Dl.4lDl.4M. Existing reinforcement to but practical limitations make this ideal condition difficult to
be welded shallconform to ASTM A706, or shall be analyzed attain. The maximum reinforcement stress used in design
chemically and its carbon equivalent determined as required under this Code is based upon yield strengIh. To ensure
by AWS Dl.4lDl.4M. sufficient strength in splices so that brittle failure can be
avoided, the 25 percent increase above the specified yield
strength was selected as both an adequate minimum for
safety and a practicable maximum for economy.

When welding of reinforcing bars is required, the


weldability of the steel and compatible welding procedures
need to be considered. The provisions in AWS D1.4/D1.4M
Welding Code cover aspects of welding reinforcing bars,
including criteria to qualifo welding procedures. Weldability
of the steel is based on its chemical composition or carbon
equivalent (CE). The Welding Code establishes preheat and
interpass temperatures for a range of carbon equivalents and
reinforcing bar sizes. Carbon equivalent is calculated from
the chemical composition of the reinforcing bars. The
Welding Code has two expressions for calculating carbon
equivalent. A relatively short expression, considering only
the elements carbon and manganese, is to be used for bars
other than ASTM A706 material. A more comprehensive
c-68 TMS 402.16

TMS 402 CODE


t@
q(0
I
t>
r-r

EE
SE
$E
aE
EO
F(J

6.1.6.1.3 Mechanical splices of bar


reinforcement Mechanical splices shall have the bars
connected to -develop in tension or compression, as
required, at least 125 percent of the specified yield strength
of the bar.
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-69

TMS 402 CODE COMMENTARY

6.1.6.1.4 End-bearing splices 6.1.6.1.4 End-bearing splices Experience


6.1.6.1.4.1 In bars required for -
with end-bearing splices has been almost exclusively with
compression only, the transmission of compressive stress vertical bars in columns. If bars are significantly inclined
by bearing of square cut ends held in concentric contact by from the vertical, special attention is required to ensure that
a suitable device is permitted. adequate end-bearing contact can be achieved and
6.1.6.1.4.2 Bar ends shall terminate in
maintained. The lateral tie requirements prevent
end-bearing splices from sliding.
flat surfaces within 1 r/z degree of a right angle to the axis
of the bars and shall be fitted within 3 degrees of full
bearing after assembly.

6.1.6.1.4.3 End-bearing splices shall be


used only in members containing closed ties, closed
stimrps, or spirals.
6.1.6.2 Splices of wires in tension Wire 6.1.6.2 Splices of wires in tension
splices shall comply with Section 6.1.6.2.1, 6.1.6.2.2, or
6.1.6.2.3.
6.1.6.2.1 Lop splices of wires The 6.1.6.2.t Lap splices of wires
minimum length of lap for wires in tension shall be
determined by Equation 6-3, but shall not be less than 6 in.
(152 mm).
6.1.6.2.2 Welded splices of wires Welded 6.1.6.2.2 Welded splices of wires If
-
splices shall have the wires welded to develop at least 125 welded splices are required on a project, the contract
percent ofthe specified yield strength of the wire in tension. documents should speciry requirements or performance
criteria for the welding. If cold drawn wires are to be
welded, the welding procedures should address the
potential loss of yield strength and ductility achieved by the
cold working process (manufacturing) when such wires are
heated by welding. Machine and resistance welding, as
used in the manufacture of welded plain and deformed wire
reinforcement, are covered by ASTM A1064/AI064M and
by ASTM A95l for joint reinforcement.
6.1.6,2.3 Mechanical splices of wires 6.1.6.2.3 Mechanical splices of wires
Mechanical splices shall have the wires connected to
develop at least 125 percent of the specified yield strength
of the wire in tension.

6,1.7 Shearreinforcement 6.1.7 Shearreinfurcement


Shear reinforcement shall extend to a distance d from Design and detailing of shear reinforcement locations
the extreme compression face and shall be carried as close and anchorage in masonry requires consideration of the
to the compression and tension surfaces of the member as masonry module and reinforcement cover and clearance
cover requirements and the proximity of other requirements.
reinforcement permit. Shear reinforcement shall be
anchored at both ends for its calculated stress.

6.1.7.1 Horizontal shear reinforcement 6.1.7.1 Horizontal sheor reinforcement


6.1.7.1.1 Except at wall intersections, the end 6.1.7.1.1 In a wall without an intersecting wall
of a horizontal reinforcing bar needed to satisff shear at its end, the edge vertical bar is the bar closest to the end
strength requirements of Section 9.3.4.1.2 or Section of the wall.
11.3.4.1 .2 shall be bent around the edge vertical reinforcing
bar with a 180-degree standard hook.
TMS 402-16

TMS 402 CODE COMIIJ|IENTARY


tto
cl\ 6.1.7.1.2 At wall intersections, horizontal 6.l.7.l.2When the wall has an intersecting
Io
tl>
reinforcing bars needed to satisfy shear strength wall at its end, the edge vertical bar is the bar at the
requirements of Section 9.3.4.1.2 or 11.3.4.1.2 shall be intersection of walls. Hooking the horizontal reinforcement
6E bent around the edge vertical reinforcing bar with a 90- around a vertical bar located within the wall running
SE
sfL degree standard hook and shall extend horizontally into parallel to the horizontal reinforcement would cause the
aE
Eo
F()
the intersecting wall a minimum distance at least equal to reinforcement to proffude from the wall.
the development length.
6.1.7.1.3 Joint reinforcement used as shear 6.1.7.1.3 Wire reinforcement should be
reinforcement and needed to satisff the shear strength anchored around or beyond the edge reinforcing bar. Joint
requirements of Section 9.3.4.1.2 shall be anchored reinforcement longitudinal wires and wire bends are
around the edge reinforcing bar in the edge cell, either by placed over masonry unit face shells in mortar and wire
bar placement between adjacent cross-wires or with a 90- extensions can be placed in edge cell mortar or can extend
degree bend in longitudinal wires bent around the edge into edge cell groui. Both joint oinforrcment longitudinal
cell and with at least 3-in. (76-mm) bend extensions in wires and cross wires can be used to confine vertical
mortar or grout. reinforcing bars and grouted cells because wires are
@rtroped within a short length.
6.1.7.2 Stimtps
1"8 close to the compression
'ffiW.e11ffilW.fud,as
61$eriwiia[er'ar pqusible because near ultimate load,

6.1.7.2.1 The ends of single-leg or U-stimrps


shall be anchored by one ofthe following means:

(a) A standard hook plus an effective embedment of 0.5 la .


The effective embedment of a stimrp leg shall be taken (a) When a standard hook is used, A.5 lamust be provided
as the distance between the middepth of the member, between dl2 andthe point of tangency of the hook.
dl2, andthe start of the hook (point of tangency).
This provision may require a reduction in size and
spacing of web reinforcement, or an increase in the
effective depth of the beanr, for web reinforcement to
be fully effective.

(b) For No. 5 bar (M #16) and D3l (MD200) wire and (b) U-stimrps that enclose a longitudinal bar have
smaller, bending around longitudinal reinforcement sufficient pullout resistance in the tension zone of the
through at least 135 degrees plus an embedment of masonry.
0.33 la. The 0.33 la embedment of a stimrp leg shall
be taken as the distance between middepth of
member, dl2, and start of hook (point of tangency).

(c) Between the anchored ends, each bend in the continuous


portion of a fransverse U-stimrp shall enclose a
longitudinal bar.

6.1.7.2.2 Pairs of U stimrps or ties


placed to form a closed unit shall be considered properly
spliced when length of laps are 1.7 la.In grout at least 18 in.
(a57 mm) deep, such splices with A,frnotmore than 9,000 lb
(40030 N) per leg shall be permitted to be considered adequate
if legs extend the full available depth of grout.
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-71

COMMENTARY

0.33

See Section 6.1.7

Point of Tangency Point of Tangency

Section 6.1.72.1(a) Section 6.1.7.2.1(b)

Figure CC-6.1-1 * Anehorage ofU-stiy.1rq,1 {deforrned reinfurcing bars ond deformed wire)

TMS 402 CODE COM]I,IENTARY

6.1.7,3 Welded wire reinforcement 6.1.73 Welded wire reinfurcement Although


6.1.7.3.1 For each l.g of welded wire -
not often used in masonry construction, welded wire
reinforcement forming simple U-stimrps, there shall be reinforcement provides a convenient means of placing
either: reinforcement in a collar joint. See PCI (1980) for more
information.
(a) Two longitudinal wires at a 2-rn. (50.8-mm) spacing
along the member at the top of the U, or

(b) One longitudinal wire located not more than dl4 from
the compression face and a second wire closer to the
compression face and spaced at least 2 in. (50.8 mm)
from the first wire. The second wire shall be located on
the stimrp leg beyond a bend, or on a bend with an inside
diameter of bend at least 8da

6.1.7.3.2 For each end of a single-leg


stimrp ofplain or deformed welded wire reinforcement, there
shall be two longitudinal wires spaced a minimum of 2 in.
(50.8 mm) with the inner wire placed at a distance atleastdl4
or 2 in. (50.8 mm) from middepth of member, dl2. Outer
longitudinal wire at tension face shall not be farther from the
face than the portion of primary flexural reinforcement
closest to the face.

6.1.7.3.3 Longitudinal bent bars


-
Longitudinal bars bent to act as shear reinforcement, where
extended into a region of tension, shall be continuous with
longitudinal reinforcement and, where extended into a
region of compression, shall be developed beyond
middepth of the member, dl2.
c-72 TMS 402-16

TMS 402 CODE COMMENTARY


6.1.8 Standard hooks and bends for reinforcing 6.1.8 Standard hooks and bends for reinforcing
gE bars, stirrups, and ties bars, stimtps, and ties
Standard bends in reinforcing bars are described in
terms of the inside diameter of bend because this is easier
$E
oE
EO
to measure than the radius of bend.
F(J A broad survey of bending practices, a study of ASTM
bond test requirements, and a pilot study of and experience
with bending Grade 60 (Grade 420) bars were considered
in establishing the minimum diameter of bend. The primary
consideration was feasibility of bending without breakage.
Experience has since established that these minimum bend
diameters are satisfactory for general use without
detrimental crushing of grout.

6.1.8.1 Standard hooks shall be as described in


Table 6.1.8.
6.1.8.2 The diameter of bend measured on the
: " 6.1.8.2 The minimum 4 bar diameters bend for
inside of reinforcing bars, stimrps, and ties, shall not be less .the,bm sizes,'corirmomly'used for stimrps and ties is based
than values specified in Table 6.1.8. 'on acce1ited hdustry practice in the United States.

6.1.9 Emb edment offl exural reinforcement ' 6Jr9 ,' Embedment of Jlexural reinforcement
,:
:F;{*x+##r6,
-
illu$Sates the embedment requirements of
I -2'
fleiural reinforCement in a typical continuous beam. Figure
CC-6.1-3 illusffates the embedment requirements in a
rypical continuous wall that is not part of the lateral-force-
resisting system.

6.1.9.1 General 6.1.9.1.1 General

6.1.9.1.1Tension reinforcement is
permitted to be developed by bending across the neutral
axis ofthe member to be anchored or made continuous with
reinforcement on the opposite face of the member.
6.1.9.1.2 Critical sections for development 6,1.9.1.2 Critical sections for a typical
of reinforcement in flexural members are at points of continuous beam are indicated with a"c" or an 'ox" in Figure
maximum steel stress and at points within the span where CC-6.LA. Critical sections for a typical continuous wall are
adjacent reinforcement terminates or is bent. indicated with a "c" in Figure CC-6.1-3.
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-73

Table 6.1.8 Standard Hooks Geometry and Minimum lnside Bend Diameters for Reinforcing Bars,
Stirrups & Ties
Standard Bar Grade Bar Size Min. Extension Standard Hook Figures
Hook Type Inside
and Use Bend
Diameter
40 No.3 - No. 7 5dt 12 dt
90 Degree (M280) (M#10 -#22)
Hook - 50 or 60 No.3-No.8 6du 12 dt
Reinforcing (M#10 -#2s)
(M350 or
Bars
420)
50 or 60 No.9-No. 11 E
.9
(M350 or (M#29 - #36) 8dt 12 dt o
E
o)
420) x
I.IJ

40, 50,60 No.3 - No.5 4dt 6 dabut not


90 Degree (M280,350 (M#10 - #16) less than
Hook - or 420) 2-ll2 in. P.T. = Point of Tangency
Stimrps & (64 mm)
Ties 40 No.6 and No.7 5dt 6dt
(M280) (M#re - #22)
50 or 60 No.6 - No.8 6du 6du
(M350 or (M#le - #2s)
420)
50 or 60 No.9 - No.l I 8dt 6dt
(M350 or (M#ze - #36)
420)
40, 50,60 No.3 - No.5 4du 6dt
135 Degree (M280,350 (M# 10 - #16)
Hook - or 420)
Stimrps & 40 No.6 and No.7 5dt 6do
Ties (M#le -#22)
(M280)
50 or 60 No.6 - No.8 6dt 6dt
(M350 or (M#1e -#2s)
420)
50 or 60 No.9 - No.l I 8dt 6du
(M350 or (M#2e- #36)
420)
40 (M280) No.3 - No.7 5do 4 da but not
180 Degree (M#10 - #22) less than
Hook - 2-l12 in.
Reinforcing (64 mm)
Bars
50 or 60 No.3 - No.8 6do 4 da but not
(M350 or (M#10 -#2s) less than
420) 2-l12 in.
(64 mm)
50 or 60 No.9 - No.l I 8dt 4dt
(M350 or (M#29 -#36)
420)
c-74 TMS 402-16

COMMENTARY

sI Moment Capacity
of Bars a
SE
sE
oE Points of lnflection (P.1.)
EO
F(J
Moment Capacity
of Bars b

Moment

>/a-*

> d,1

Figure CC-6.1-2 Development offlexural reinforcement in a typical continuous beam


-

Figure CC-6.t-3 Development offiexural reinfurcement in a typical wall


-
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-75

TMS 402 CODE COMMENTARY

6.1.9.1.3 Reinforcement shall extend 6.1.9.1.3 The moment diagrams


beyond the point at which it is no longer required to resist customarily used in design are approximate. Some shifting
flexure for a distance equal to the effective depth of the of the location of maximum moments may occur due to
member or 72dt, whichever is greater, except at supports of changes in loading, settlement of supports, lateral loads, or
simple spans and at the free end of cantilevers. other causes. A diagonal tension crack in a flexural membsr
without stimrps may shift the location of the calculated
tensile stress approximately a distance d toward a point of
zero moment. When stimrps are provided, this effect is less
severe, although still present.

To provide for shifls in the location of maximum


moments, this Code requires the extension of reinforcement a
distance d or l2dt beyond the point at which it is theoretically
no longer required to resist flexure, except as noted.

Cutoff points of bars to meet this requirement are


illustrated in Figure CC-6.1-2.
When bars of different sizes are used, the extension should
be in accordance with the diameter of bar being terminated.
A bar bent to the far face of a beam and continued there
may logically be considered effective in satisffing this
section, to the point where the bar crosses the middepth of
the member.

6.1.9.1.4 Continuingreinforcement shall 6.1.9.1.4 Peak stesses exist in the


extend a distance /a beyond the point where bent or remaining bars wherever adjacent bars are cut off or bent in
terminated tension reinforcement is no longer required to tension regions. In Figure CC4.I-2 an 'k" is rsed to indicate
resist flexure as required by Section 6.1.5.1 or 6.1.5.2. the peak shess points remaining in continuing bars afterpart of
the bars have been ctrt off If bars are cut off as short as the
moment diagrams allow, these ssesses become the full design
sfress whichrequires a full embedment length as indicated. This
extension may exceed the length required for flexure.

6.1.9.1.5 Flexural reinforcement shall not 6.1.9.1.5 Evidence of reduced shear


be terminated in a tension zone unless one of the following strength and loss of ductility when bars are cut off in a
conditions is satisfied: tension zone has been reported in Ferguson and Matloob
(a) Shear at the cutoff point does not exceed two-thirds of: (1959). As a result, the Code does not permit flexural
reinforcement to be terminated in a tension zone unless
(i) the allowable shear at the section considered, when special conditions are satisfied. Flexure cracks tend to open
using Chapter 8; or, early wherever any reinforcement is terminated in a tension
(ii) the design strength in shear
at the section considered,
zone. If the skess in the continuing reinforcement and the
when using Chapter 9 or Chapter 11. shear strength are each near their limiting values, diagonal
tension cracking tends to develop prematurely &om these
(b) Stimrp area in excess of that required for shear is flexure cracks. Diagonal cracks are less likely to form where
provided along each terminated bar or wire over a shear stress is low. A lower steel stress reduces the
distance from the termination point equal to three- probability of such diagonal cracking.
fourths the effective depth of the member. Excess
stimrp area, A,,, shall not be less than 60 b,,.s6,.
Spacing s shall not exceed d/(B /3b).
(c) Continuous reinforcement provides double the area
required for flexure at the cutoff point and shear does
not exceed:

(i) three-fourths the allowable shear at the section


considered, when using Chapter 8; or,
c-76 TMS 402-16

TMS 402 CODE COMMENTARY


ttCN
G,
(ii) in shear at the
three-fourths the design strength
5o
lr> section considered, when using Chapter 9 or
6E Chapter I 1.
8E
rE 6.1.9.1.6 Anchorage complying with 6.1.9.1.6 In corbels, deep flexural
aE Section 6.1.5.1 or 6.1.5.2 shall be provided for tension members, variable-depth arches, members where the tension
EO
F(J reinforcement in corbels, deep flexural members, variable- reinforcement is not parallel with the compression face, or
depth arches, members where flexural reinforcement is not other instances where the steel stress, J, in flexural
parallel with the compression face, and in other cases where reinforcement does not vary linearly in proportion to the
the stress in flexural reinforcement does not vary linearly momenf special means of analysis should be used to
through the depth ofthe section. determine the peak stress for proper development of the
fl exural re inforcement.

6.1.9.2 Development of positive moment 6.1.9.2 Development of positive moment


reinforcement When a wall or other flexural member is reinfurcement flexwal memberis partofthe lateral-
-
part of the lateral-force-resisting system, at least 25 percent
-Wlrcna
fr,rce*esiffig qysteq loads great€r than those anticipated in
of the positive moment reinforcement shall extend into the l@$gn may cause reversal of moment at suppofis.. At. u
support and be anchored to develop the yield strength of the ,eo nce, some positive reinforcement is required to be
reinforcement in tension. anchfed.into the support. This anchorage assures ductility of
fui ,eveutofs ous overstress, such as from blast or
: Tlhe use , rrmfe reinforcqnent at lower sfiesses is
not mrfficient TIF full, anchorage requirement need not be
;$atisfid,sfrsinforcerent exceeding 25 percent ofthe total that
is provided at the support.

6.1.9.3 Development of negative moment 6.1.9.3 Development of negative moment


reinforcement reinforeement reinforcement must be properly
6.1.9.3.1 Negative moment
-Negative
anchored beyond the support faces by extending the
reinforcement in a continuous, resffained, or cantilever reinforcement la into the support or by anchoring of the
member shall be anchored in or through the supporting reinforcement with a standard hook or suitable mechanical
member in accordance with the provisions of Section 6.1.5. device.

6.1.9.3,2At least one-third of the


total Section 6.1.9.3.2 provides for possible shifting of the
reinforcement provided for moment at a support shall extend moment diagram at a point of inflection, as discussed under
beyond the point of inflection the greater distance of the Commentary Section 6.1.9.1.3. This requirement may
effective depth of the member or one-sixteenth of the span. exceed that of Section 6.1.9.1.3 and the more restrictive
governs.

6.2 Metal accessories


6.2
- Metal accessories -
6.2.1 Protection of metal occessories 6.2.1 Protection of metal accessories
Wall ties, sheet-metal anchors, steel plates and bars, and Corrosion resistance requirements are included
inserts exposed to earth or weather, or exposed to a mean because masonry cover varies considerably for these items.
relative humidity exceeding 75 percent shall be stainless steel or The exception for anchor bolts is based on current industry
protected from corrosion by hot-dip galvanized coating or practice.
epoxy coating. Wall ties, anchors, and inserts shall be mill
galvanized, hot-dip galvanized, or stainless steel for all other
cases. Anchor bolts, and steel plates and bars, not exposed to
earth, weather, nor exposed to a mean relative humidity
exceeding 75 percent, need not be coated.
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-77

TMS 402 CODE COMMENTARY


6.3 Anchor bolts 6.3 Anchor bolts
- -
Headed and bent-bar anchor bolts shall conform to the These design values apply only to the specific types of
provisions of Sections 6.3.1 through 6.3.7. bolts mentioned. These bolts are readily available and are
depicted in Figure CC-6.3-1.
6.3.1 Placement 6.3.1 Placement
Headed and bent-bar anchor bolts shall be embedded in Most tests on anchor bolts in masonry have been
grout. Anchor bolts of % in. (6.4 mm) diameter are permitted performed on anchor bolts embedded in grout. Placement
to be placed in mortar bed joints that are at least % in. limits for anchor bolts are based on successful construction
(12.7 mm) in thickness and, for purposes of application of the practice over many years. The limits are intended to
provisions of Sections 6.3, 8.I .3 and 9.1.6, are permiffed to be facilitate the flow of grout between bolts and between bolts
considered as if they are embedded in grout. and the masonry unit.

Anchor bolts placed in the top of grouted cells and bond Research at Portland State University (Rad et al
beams shall be positioned to maintain a minimum of % in. (6.4 (1998)) and at Washington State University (Tubbs et al
mm) of fine grout between the bolts and the mrlsonry unit or (2000) has esablishe&that'thep is no difference in the
% in. (12.7 mm) of coarse grout between the bolts and the prformance of an anchor bolt installed through a tight-
masonry unit. Anchor bolts placed in drilled holes in the face frtting hote in the face shell of a grouted hollow masonry
shells of hollow masonry units shall be permitted to contact unit aqd iq.$.oy,er;[iz# hole in tJre face shell of a grouted
the masonry unit where the bolt passes through the face shell, ksllow ,u* ',rlliif;,l,,,Therefore, the clear distance
but the portion of the bolt that is within the grouted cell shall rcq*fue ,fe,' Gs surround an anchor bolt is not
be positioned to maintaina minimum of %in. (6.a mm) offine nded,w,kr,e.. g bk passes through the face shell. See
grout between the head or bent leg of each bolt and the Fignre CG6.3-2.
masonry unit or Yz in. (12.7 mm) of coarse grout between the
head or bent leg of each bolt and the masonry unit. Quatit5r assuranee/quality control (QA/QC) procedures
should ensure that there is sufficient clearance around the
The clear distance between parallel anchor bolts shall bolts prior to grout placement. These procedures should
not be less than the nominal diameter of the anchor bolt, nor also require observation during grout placement to ensure
less than I in. (25.4 mm). that grout completely swrounds the bolts, as required by
Table 4 in TMS 602.

COMMENTARY

"L'Bolts
Hex Head

'J" Bolls
squareHead
o 8T
(a) Headed Anchor Bolts (b) Bent-Bar Anchor Bolts

Figare CC-6.3-l Anchor bolts


-
c-78 TMS 402-16

COMMENTARY
EP
5o
E'i
6E
$E
oE
EO
F(,

Min imum %in. (12.7 mm) for


coarse groutor Yein. (6.4nm) Anchor bolt
to;ri,,g,e grolrt
ffib& blt

Figure CC-6.3-2 Anchor bolt clearanie requirements for headed anchor bolts - bent-bars are similar
-

TMS 402 CODE COMMENTARY

6.3.2 Projected areafor axial tension 6.3.2 Projected oreafor axial tension
The projected area ofheaded and bent-bar anchor bolts Results of tests (Brown and Whitlock (1983); Allen et
loaded in axial tension, Apt, shall be determined by Equation al (2000)) on headed anchor bolts in tension showed that
6-5. anchor bolts often failed by breakout of a conically shaped
section of masonry. The area, Ap,, is the projected arei of
Ar, = nli (Equation 6-5) the assumed failure cone. The cone originates at the
compression bearing point of the embedment and radiates
The portion of projected area overlapping an open cell, at 45 degrees in the direction of the pull (See Figure
or open head joint, or that lies outside the masonry shall CC-6.3-3). Other modes of tensile failure are possible.
be deducted from the value of Ap, calculated using These modes include pullout (straightening of J- or L-bolts)
Equation 6-5. Where the projected areas of anchor bolts and yield / fracture of the anchor steel.
overlap, the value of Ap, calculated using Equation 6-5
shall be adjusted so that no portion of masonry is When anchor bolts are closely spaced, stresses within
included more than once. the masonry begin to become additive, as shown in Figure
CC-6.34. The Code requires that when projected areas of
anchor bolts overlap, an adjustment be rnade so that the
masonry is not overloaded. When the projected areas of two
or more anchors overlap, the anchors with overlapping
projected areas should be treated as an anchor group. The
projected areas ofthe anchors in the group are summed, this
area is adjusted for overlapping areas, and the capacity of
the anchor group is calculated using the adjusted area in
place of Ap. See Figure CC-6.3-5 for examples of
calculating adjusted values of Ap,. The equations given in
Figure CC-6.3-5 are valid only when the projected areas of
the bolts overlap.
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-79

COMMENTARY ER
[6
EE
,Tension Force Force
I lTension $E
n"sumed Conefor aE
Calculation of A*, =o
F(J
EquationGl

Conical
Failure
Surface

Figure CC-6.3-3 Anchor bok tensile breokout cone


-

Overlapping

Figure CC-6.3-4 Overlapping anchor bolt breakout cones


-
c-80 TMS 402-16

:COMIil.EilITARY
EO
EO
Apl at Top of Wall for Uplift
5o
tt>
6E
SE
rts
oE
Eo
F(J

For/6 Sz<2X
1-
x=;rlq(lu)' -,'

. A .(tt\
:. Apt =(2x +:zl-.,;(#-si,p) where0 = zarminl
. I
i" degrees
\tt )

;, a ot=
(lx + zI. {#[# * sm#], ,-h :,**{ffi}*,!sw

Figur e C { - 6. 3 - S r C*t eu, latioin, ofA,Si wq t e d'Y'ElsAs of Apt',ffi Y}qvg)


BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-81

TMS 402 GODE COMMENTARY

6.3.3 Projected area for shear 6.3.3 Projected areafor shear


The projected area of headed and bent-bar anchor bolts Results of tests (Brown and Whitlock (1983); Allen et
loaded in shear, Ar,, shall be determined from Equation 6-6. al (2000)) on anchor bolts in shear showed that anchor bolts
1Z1
often failed by breakout of a conically shaped section of
r trlb" masoruy. The area A* is the projected area of the assumed
"pu - ,l (Equation 6-6)
z failure cone. The cone originates at the compression bearing
point of the embedment and radiates at 45 degrees in the
The portion of projected area overlapping an open cell,
direction of the shear force towards the free edge of the
or open head joint, or that lies outside the masonry shall
masonry, thereby accounting for bolt edge distance (See
be deducted from the value of Ap, calculated using
Figure CC4.3-6). Edge distance is considered in the
Equation 6-6. Where the projected areas of anchor bolts
calculation of the projected area for shear, 1r, (Code
overlap, the value of Ap, calculated using Equation 6-6
Equation 6-6). No minimum edge distance is provided for
shall be adjusted so that no portion of masonry is
the placement of anchor bolts. Placement of all anchors,
included more than once.
including anchor bolts, must meet the minimum thickness of
gfout between the anchor and masonry units given in Code
Se$ion 6.3.1. Pryout (See Figure CC-6.3-7), masonry
crushing and yielding / fracture olthe anchor steel are other
possible faiture modes.
'Wh.n''th. projected areas of fwo or more anchors
overlap, the sheardesign of these anchors should follow the
safile prwedure as for the tension design of overlapping
anchors. See Commentary Section 6.3.2.

63.4 Effective embedment length -fo, headed


anchor bolts
The effective embedment length for a headed anchor
bolt, 16, shall be the length of the embedment measured
perpendicular from the masonry surface to the compression
bearing surface ofthe anchor head.

Figure CC-6.3-6 Anchor bolt shear breakout


-
c-82 TMS 402-16

TMS 402 CODE COMTIJIENTARY


E$
36
E'i 63.5 Effective embedment length for bent-bar 6.3.5 Effective embedment length -fo, bent-bar
6E anchor bolts anchor bolts
The effective embedment for a bent-bar anchorbolt,16, Tests (Brown and Whitlock (1983)) have shown that
$E the pullout strength of bent-bar anchor bolts correlated best
aE shall be the length of embedment measured perpendicular
=o
F(J from the masomy surface to the compression bearing with a reduced embedment length. This may be explained
surface of the bent end, minus one anchor bolt diameter. with reference to Figure CC-6.3-8. Due to the radius of the
ben4 stresses are concentrated at a point less than the full
embedment length.

Figure CC-6.i-7 Anchor bolt shesr pryout


-

Tension Force
t/r'
'/.F FrictionalResistane
&i-r+r..-**

.Normal
$treesm

Bolt Diameter,d6

BoltDiameter,d6

Figure CC-6.3-8 * ^Srress


distribution an bent-bar anchor b*rs
BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES AND COMMENTARY c-83

TMS 402 GODE COMMENTARY


6.3.6 Minimum permissible ffictive embedment 6.3.6 Minimum permissible effective embedment
length length
The minimum permissible effective embedment length The minimum embedment length requirement is
for headed and bent-bar anchor bolts shall be the greater of 4 considered a practical minimum based on [pical
bolt diameters or 2 in. (50.8 mm). construction methods for embedding anchor bolts in
masonry. The validity of Code equations for shear and
tension capacities of anchor bolts have not been verified by
testing of anchor bolts with embedment lengths less than
four bolt diameters.
6.3.7 Anchor bolt edge distance
Anchor bolt edge distance, /a", shallbe measured in the
direction of load from the edge of masonry to center of the
cross section of anchor bolt.
c-84 TMS 402-16

E, -f
E@
5c,i
rc, This page intentionally left blank
Oi-
o.9
SE
rt
aE
F(J
=o

You might also like