              1.1 Cable Trench 
S.No   DESCRIPTION  YES  No  N/A  REMARKS 
1   Check the location of cable trench asper drawing?            
2   Check the width & depth of trench as per drawing?            
3   Check the trench is free from unwanted material?            
Check for Sand bed below cable as per design.             
4  
To Check for bricks used in the trench as per design.            
5  
To check for danger tape used before backfilling the trench.             
6  
                                                             1.2   4 sq.mm & 6 sq. mm dc cable laying  
    S.No   DESCRIPTION  YES  No  N/A  REMARKS 

          1   Check for physical damage of the cables.             
          2   Check  cable  make,  size,  voltage  grade,  conductor  &             
insulation type as per design/specifications.  

          3   Cable tagging/ferrule for identification             

          4   Polarity check & separation in conduit              
          5   To check the Crimping of thimble & Locking             
of MC4 connector.  
          6   Conduit provided for mechanical & UV             
protection  

          7   To check for cable Free from sharp edges.             
          8   Uniform laying of cable & jointer fixing             

                                                          1.3 DC Cables from SCB to central inverter  
         DESCRIPTION 
Sr.No   YES   No   N/A  REMARKS  
1   Check for physical damage of the cables             
Check  cable  make,  size,  voltage  grade,  conductor  &             
2  
insulation type as per design/specifications    
Check cable route, depth &  width of the trench as             
3  
per drawings  
Check the Cable tagging as per design.              
4  
To check the IR Test before & after laying             
        5  
   Check cables shall be firmly and uniformly bedded in             
6   sand, free from stones, rocks or other hard formation to 
prevent cable sheath damage  
7   No twists, knots or kinks             
8   Adequate looping at the termination ends             
9   Check cables are resealed at the ends             
HDPE pipes  are  provided  as per  the  drawing  from  PV             
10  
module end to SCB termination ends  
11   Check for proper Dressing of the cables             
 
 
 
CONSTRUCTION QUALITY CHECKLIST  

                          CABLE LAYING & TERMINATION  
 
  
  
     1.4 Installation of LT & HT Power Cables :      

S.No   DESCRIPTION   YES   No   N/A  REMARKS  

1   Underground cables as per drawing/specifications:             
2   Check the cable size & make as per Specifications / SL             
3    IR Test for cable after laying             
4   Cable laid as per cable routing drawing             
   Check for the cable physical damages along the route             
5   ‐(Due to tray sharp edges and bends up to 
termination)  
6   Cable identification tags at termination ends             
7   Partition between LV & HV cables             
8   Check for Sand bed above cable as per cable route lay             
9   Check the Bricks laid above sand bedding             
Check  for  provided  pipes  at  road  crossing  and             
10   railways crossing (min. depth 1000mm)  

11   Identification provided at cable joints             
12   Cable Route markers provided             
  
  
  
                    1.5  Cables on trays :         

S.No   DESCRIPTION      YES  No  N/A  REMARKS 

1   Segregation & Dressing of power, control cables             

2   300mm clearance between power & control/comm. cable              

Spacing of clips, saddles & cleats as per drawing /            
3  
Specifications  
Trefoil arrangement for individual single core cable.              
4  
Adequate supporting provided at joints and             
5  
Terminations  

6   Cable ties fixed             

7   Identification of  tags fixed             

8   Bending radius of the cables as per specifications/IS             

9   Check for Earthing of cables & Glands             

10   Check for Sealing at the cable entries             

  
 
 
 
CONSTRUCTION QUALITY CHECKLIST  

                          CABLE LAYING & TERMINATION  
 
  
  
  1.6  Cable Jointing & Terminations Ends        

S.No.   DESCRIPTION      YES   No  N/A  REMARKS 

Cable Jointing & terminations done as per             
1  
manufacturers instruction manual  
Check torque tightness of the cable terminations at             
2  
Connection as per torque table.  
3   Check for Proper dressing of cable with adequate looping.             
Cable supporting arrangement (To avoid stress on            
4  
Terminal)  
5   Check for Phase sequence identification.             
6   Check for Earthing Connections provided.             
7   Check for Insulation sleeves at the termination ends.             
  
  
  
Observation/Comments:  

  
  
  
  
  