You are on page 1of 31

SIPROTEC 7SJ531

Numerical Line and Motor Protection


with Control Functions

Protection Systems
Catalog LSA 2.1.9
October 1997
SIPROTEC 7SJ531(Version V3.2) Protection systems
Numerical Page

Line and Motor Protection


with Control Functions Features 2

Description 3 to 6

Feeder control diagrams 7 and 8

Functions 9 to 15

Typical applications 16 to 19

Technical data 20 to 23

Selection and ordering data 24

Connection diagram 25

Dimension drawings
(in mm) 26

Technical specification 27

Index of catalogs 28

Conditions of sale
and delivery 28

Catalog LSA 2.1.9 ⋅ October 1997


 Siemens AG 1997
Supersedes: Catalog LSA 2.1.9 ⋅ 1997
Siemens LSA 2.1.9 ⋅ Oct. 1997 1
SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Features

■ Line protection ANSI IEC ANSI IEC

■ Overcurrent-time protec- 27 V<<, t ; V<, t 51N IE>>, t ; IE>, t ; IEp


tion, phase and earth-
fault protection, either P>; Q> 51BF CB I>, t
definite-time or inverse-
time (IEC or ANSI) 37 I< 55 cos ϕ<
■ Reverse interlocking 46 I2>>, t ; I2>, t 59 V>, t
■ Overload protection acc.
to IEC 255-8 47 phase sequence 64
monitoring V0>, t
■ Undervoltage and over- starting time
voltage protection 48 67N IEE>>, t ; IEE>, t
monitoring
■ Automatic reclosure
49 ϑ>, IEC 255-8 67 Idir.>>, t ; Idir.>, t
■ Sensitive earth-fault de-
tection 50 I>> 79 auto-reclosure
■ Circuit-breaker failure
protection 50N IE>> start inhibit
■ Directional overcurrent-
51 I>>, t ; I>, t ; Ip trip circuit monitoring
time protection

LSP2009f.eps
■ Directional comparison
protection
■ Unbalanced-load protec-
tion
■ Fault locator
■ Switch-onto-fault.
■ Motor protection
Fig. 1
■ Overcurrent-time 7SJ531 numerical overcurrent-time
protection protection (flush mounting housing)
■ Stator overload protec-
tion with 2 time constants
■ Starting time monitoring
(locked-rotor protection)
■ Start inhibit ■ Monitoring ■ Communication
■ Unbalanced-load protec- ■ Operational measured ■ IEC 870-5-103 interface
tion values to LSA/SCADA
■ Undercurrent detection. I, V, P, Q, Θ, f ■ PC with DIGSI
■ Transformer protection ■ Energy metering values ■ via modem.
Wp, Wq
■ Overcurrent-time protec- ■ Threshold values ■ Hardware
tion P >, Q >, cos ϕ< ■ Auxiliary voltages
■ Overload protection ■ Time metering of 24/48/60/110/125/
(IEC 255-8) operating hours. 220/250 V DC
■ Unbalanced-load protec- ■ Local control
tion. ■ Additional functions
■ Graphic display
■ Control ■ Trip circuit monitoring ■ Analog inputs
■ Parameter set change- 5 current transformers
■ 1 switching device via over 3 voltage transformers
the integrated operating ■ User-definable charac-
panel, 2 binary inputs, ■ Digital inputs/outputs
teristics for overcurrent- 11 binary inputs
DIGSI or LSA/SCADA time protection, direc- 5 alarm relays
■ The positions of up to 5 tional overcurrent-time 4 command relays.
switching elements are protection and direction-
shown on the graphic al earth-fault detection
display ■ Test OPEN and test
■ 22 feeder control dia- OPEN-CLOSE cycle
grams for single and du- (Trip contact testing)
plicate busbars for adap- ■ Fault recording
tation to the switching 8 fault event protocols
bay 8 fault oscillographic
■ Local-remote switching. recordings.

2 Siemens LSA 2.1.9 ⋅ Oct. 1997


Description

LSP2010f.eps

LSP2011f.eps
Fig. 2
Front view Rear view
(surface mounting housing) (flush mounting housing)

Application Design Improved measurement


The 7SJ531 is a numerical Within its compact design, the technique
combined control, protection unit contains: With the use of a powerful mi-
and monitoring device. As a • All components for analog cro-processor and numerical
line protection device it is used value acquisition and nume- analog value conditioning and
for medium-voltage networks rical evaluation processing, the effect of high-
with low-resistance earthing, frequency transients and tran-
• Integrated keypad and gra-
solid earth (grounded), isolated sient DC components are
phic display with feeder con-
or compensated starpoint. It is largely suppressed.
equally suitable for radial net- trol diagram
• Indication and command out- The definite-time charac-
works fed from one side or for teristics measurement evalua-
open rings, as well as for puts
tes the fundamental compo-
lines fed from two sides or for • Binary inputs nent of the current (from a
closed rings. • Serial interfaces for parame- Fourier analysis). If inverse-
As a motor protection relay the terization and connection to time characteristics are cho-
7SJ531 is suitable for asyn- substation control and pro- sen there is a choice between
chronous machines of all sizes tection rms value or fundamental
and as back-up protection it is • Auxiliary voltage converter. calculation.
well suited for equipment The device can be supplied
requiring differential protection with two different housings. Reliable battery checks
such as lines, transformers or The housing for panel flush or
generators. The supplied battery serves to
cubicle mounting has rearside
back up the real time clock,
The integrated control functions connection terminals. The
the operational and fault indica-
allow control of the switching housing designed for panel sur-
tions as well as the fault record-
device via the integrated operat- face mounting is provided with ing in the event of power
ing panel, 2 binary inputs, two-tier terminals accessible supply failure. Its function is
DIGSI or LSA/SCADA. Various from above and below.
checked by the processor at
types of switchgear with sin- regular intervals. If the capacity
gle and duplicate busbar which Constant self-monitoring of the battery declines, an
contain a controllable switching alarm annunciation is iniciated.
Hardware and software are
device, are supported. A prophylactic exchange at
constantly monitored and irreg-
ularities immediately detected regular intervals is therefore
and signalled. This ensures a not necessary.
very high degree of safety, re-
liability and availability.

Siemens LSA 2.1.9 ⋅ Oct. 1997 3


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Description

Serial interfaces
(see Fig. 3) Star coupler Protection Protection Protection
device 1 device 2 device 255
The device is equipped with 7SJ531 7SJ531 7SJ531
two serial interfaces. The oper-
ating interface on the front pan-
el is suitable for the connec-
tion of a WINDOWS capable
PC. The DIGSI operating and
analysis software allows easy
setting, fault recording evalua-
tion and commissioning. The
system interface is an 820 nm
fibre-optic interface for linking
to the LSA 678 substation
Fig. 3
control and protection system Operating of protection devices with DIGSI
or a protection master unit
(protocol acc. to IEC 870-5-103).
DIGSI can also be connected
to the system interface. This is
useful if all devices of a substa-
tion are to be connected to a
PC via star coupler for remote
handling. It includes control, pa-
rameter setting, status indica-
tion reading and fault recording.
One 7SJ531 protection device
can either be connected di-
rectly to a PC or up to 255 de-
vices of a substation can be
controlled via a star coupler.
If star coupler and modem are
combined, the devices can be
accessed via telephone line.

Convenient settings
(see Fig. 4)
Using the integrated operating
panel and the graphic display,

LSP2014f.tif
the individual parameters can
be set by entering a code num-
ber under menu guidance or Fig. 4
by entering the direct ad- Parameter setting with DIGSI
dresses of individual parame-
ters. The PC program DIGSI
permits configuration and para-
meterization of the 7SJ531 in
advance on the PC. The stored
data can be loaded into the pro-
tection device via one of the in-
terfaces. They are stored in
non-volatile memories so that
setting values are retained
even if the power supply
should fail.
LSP2015f.tif

Fig. 5
Fault record of analog and binary traces

4 Siemens LSA 2.1.9 ⋅ Oct. 1997


Fault recording up to 5 sec Control via modem Operational measured val-
(see Fig. 5) DIGSI allows the user to ac- ues
The digitized values of the pha- cess the protection device via The following variables are dis-
se and earth currents as well modem. If the substation con- played under the menu item
as the line and zero sequence tains a star coupler, the opera- operational measured values:
voltages are stored in a fault re- tional and fault protocols, fault • Currents: IL1, IL2, IL3, IE, IEE
cording which may be initiated recordings and operational
• Voltages: VL1, VL2, VL3,V0, V12,
either upon pick-up or after the measured values of all protec-
V23, V31
trip command has been relea- tion devices of a substation
sed. can be conveniently loaded • Power: P, Q
from a remote PC. • Power factor cos ϕ
Furthermore, recording of
a fault event can be started via • Metering of both negative
a binary input, if an external Free assignment (marshal- and positive energy: Wp+,
protection device has tripped. ling) of inputs and outputs Wp-, Wq+, Wq-
For test purposes it can also The binary inputs not required • Frequency f.
be initiated via the integrated for position feedback, the out- • Temperature Θ
keyboard or via DIGSI. put relays and the LEDs can
The analog values recorded be independently assigned Threshold value monitoring
can be transferred to a PC according to user require- • Power: P>, Q>
where they can be convenient- ments. Up to 20 indications • Power factor cos ϕ<
ly analized and processed. If re- can be assigned to an output,
corded faults exceed the total up to 10 indications to an in- • Currents: IL1>,IL2>,IL3>,IE>,I<.
recording duration of 5 sec- put. For each input it may be
onds, the oldest fault recorded determined via settings whe- Remote control of parame-
is overwritten. ther it is to be active with or wi- ter set changeover
thout voltage. Via binary inputs, DIGSI,
Indications with time stamp LSA/SCADA or the integrated
Graphic display control panel the user may
The 7SJ531 provides detailed
switch between 2 different pa-
data for analyzing faults and During normal operation the
rameter sets. Thus, if the pow-
checking states during opera- diagram for the feeder shows
er system configuration is
tion. All the following indica- the position of the circuit-brea-
changed by switching actions
tions are protected against ker and of all other switching
it is possible to simultaneously
supply voltage failure. devices. A bar chart under-
adapt the settings of the pro-
• Real-time clock neath the feeder diagram dis-
tection devices.
As a standard a battery- plays the maximum line cur-
backed real-time clock is rent thus indicating the
capacity utilization of the User-defineable charac-
available and can be synchro- teristics
nized via a binary input or the feeder unit.
system interface. All events By simply pressing a key, 10 Instead of using the pre-de-
are recorded with a date and previously user-defined opera- fined inverse-time charac-
time tag. tional measured-values can be teristics acc. to IEC or ANSI
displayed simultaneously. For the user may define his own
• Fault indications
example the line currents, the tripping characteristics. For
As a rule, the eight most re-
active and reactive power as this purpose, up to 20 current-
cent faults are recorded. The
well as the metering values for time value pairs are available,
indications of the faults are
both active and reactive ener- which may be selected within
available with a resolution of a wide range and which allow
1 ms. gy.
a finely adjustable graduation.
• Operational indications In the case of a fault event, in-
Owing to the linear interpola-
All indications that do not im- formation such as picked-up
tion between the reference
mediately refer to a fault phases, stages or protective
points, only few points need to
(e.g. operating or switching functions which have tripped
be entered normally. Separate
actions), are stored in the or the fault duration can be
characteristics are available for
operational indication buffer shown on the display.
the phase overcurrent stage,
with a resolution of 1 ms. Furthermore, operational indi- for the earth overcurrent sta-
Memory depth: 60 indica- cations, fault event protocols ge, for the directional overcur-
tions. and all below-mentioned opera- rent stages of both earth and
tional measured values can be phase as well as for one of the
polled under the respective sensitive earth-fault stages.
menu item.
Circuit-breaker check as
commissioning aid
For checking the trip circuit the
circuit-breaker can be activated
via the 7SJ531. Either a TRIP
command or a TRIP-CLOSE cy-
cle can be started.

Siemens LSA 2.1.9 ⋅ Oct. 1997 5


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Description

Trip circuit monitoring


Vcv
One or two binary inputs can L+
be used for the monitoring of 7SJ531
the circuit-breaker trip coil in- Trip
cluding wiring. An alarm indica- BI 1 circuit
tion will be displayed if the cir- 7SJ531 faulty
or any TCo
cuit is interrupted. protective
relay
Control (see Fig. 7)
The 7SJ531 is suitable for use
R
in a medium-voltage bay with
single or duplicate busbar CLOSE OPEN
TCo Trip contact of the 7SJ531
which contains one control- Aux 1 Aux 2 BI Binary input of the 7SJ531
lable switching unit (circuit-bre- 52a 52b
TC Trip coil
aker or switch-disconnector).
TC Aux Circuit-breaker auxiliary contact
22 permanently stored feeder
CB R Bypass resistor
control diagrams are available 52
to adapt the device to the bay. Vcv Control voltage
They are displayed on the in- CB Circuit-breaker
tegrated graphic display. L− Circuit-breaker shown in closed condition
The state of the disconnectors
and circuit-breakers is obtained
via auxiliary contacts and com-
Tripping-circuit monitoring with one binary input
municated to the 7SJ531 via
two binary inputs each. In this
way it is possible to detect not
only the defined state CLO- Vcv
L+
SED or OPEN but also an inter-
mediate or fault position. 7SJ531
The 7SJ531 permits the acqui- BI 1
sition of up to five switching 7SJ531
devices. Of these the circuit- or any TCo
protective Trip
breaker can be controlled via relay circuit
the integrated control panel faulty
(code-word protected), two bi-
nary inputs, DIGSI or LSA/
SCADA (serial interface). BI 2
CLOSE OPEN
To select the switching authori-
ty there is a parameter „Switch- Aux 1 Aux 2
52a 52b
ing authority“ for enabling con-
trol command sources. The TC TCo Trip contact of the 7SJ531
positions „LOCAL“, „REMO- CB BI Binary input of the 7SJ531
52
TE“, „LOCAL and REMOTE“ TC Trip coil
and „DISABLED“ represent all
Aux Circuit-breaker auxiliary contact
combinations of the switching
authority. In addition to this L− Vcv Control voltage
permanent assignment, switch- CB Circuit-breaker
ing authorization can also be Circuit-breaker shown in closed condition
switched between „REMO-
TE“ and „LOCAL“ using a bi- Tripping-circuit monitoring with two binary inputs
nary input.
Every switching action and
change in circuit-breaker posi-
tion is logged in the operational
indication memory (memory
for up to 80 indications).
Command source, switching
device, cause i.e. spontaneous
change or command and the
result of a switching action are
recorded.

Fig. 6

6 Siemens LSA 2.1.9 ⋅ Oct. 1997


Feeder control diagrams

Circuit-breaker panel Circuit-breaker panel with busbar earthing

Q1/3,4 Q15/7,8 Q1/3,4


Q8/5,6 Q8/5,6

Q0/1,2 Q0/1,2

Circuit-breaker panel with measurement and Switch-disconnector panel


measurement earthing

Q6/9,10 Q1/3,4 Q0/1,2


Q5/7,8 Q8/5,6
Q01/3,4
Q0/1,2
Q8/5,6

Switch-disconnector panel and busbar earthing Circuit-breaker panel with duplicate busbar

Q15/7,8 Q0/1,2 Q2/7,8 Q1/3,4


Q8/5,6
Q01/3,4
Q0/1,2
Q8/5,6

Circuit-breaker panel with duplicate busbar Legend


Q.. Switching elements
I.,. Binary inputs

Q2/7,8 Q1/3,4

Q0/1,2

Q8/5,6

Withdrawable circuit-breaker panel with Withdrawable circuit-breaker panel with


feeder earthing feeder earthing and busbar earthing

Q1/3,4 Q15/7,8 Q1/3,4


Q0/1,2 Q0/1,2
Q1/3,4 Q1/3,4
Q8/5,6 Q8/5,6

Withdrawable circuit-breaker panel without Withdrawable circuit-breaker panel without


feeder earthing feeder earthing with busbar earthing

Q1/3,4 Q15/7,8 Q1/3,4


Q0/1,2 Q0/1,2
Q1/3,4 Q1/3,4

Fig. 7

Siemens LSA 2.1.9 ⋅ Oct. 1997 7


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Feeder control diagrams

Disconnector panel Disconnector panel with busbar earthing

Q1/3,4 Q15/7,8 Q1/3,4


Q8/5,6 Q8/5,6

Disconnector panel with measurement and Legend


measurement earthing Q.. Switching elements
I.,. Binary inputs

Q6/9,10 Q1/3,4
Q5/7,8 Q8/5,6

Sectionalizer panel with earthing for work Sectionalizer panel without earthing for work, left

Q1/3,4 Q10/5,6 Q1/3,4


Q15/7,8 Q16/9,10
Q0/1,2
Q0/1,2

Q1/3,4

Sectionalizer panel without earthing for work, right Sectionalizer panel without earthing for work, left,
with measurement

Q1/3,4 Q1/3,4

Q0/1,2 Q0/1,2 Q6/5,6

Q1/3,4 Q1/3,4

Sectionalizer panel without earthing for work, right, Sectionalizer panel with earthing
with measurement for work, left

Q1/3,4
Q0/1,2
Q6/5,6 Q0/1,2
Q01/3,4

Q1/3,4 Q15/7,8

Sectionalizer panel with busbar earthing and Sectionalizer panel with busbar earthing and
voltage transformer, type 1 voltage transformer, type 2

Q1/3,4 Q15/7,8 Q6/5,6 Q15/7,8 Q6/5,6 Q1/3,4

Q0/1,2 Q0/1,2

Q1/3,4 Q1/3,4

Fig. 7 (continued)

8 Siemens LSA 2.1.9 ⋅ Oct. 1997


Functions

Overcurrent-time protection Tripping characteristics of inverse-time overcurrent protection acc. IEC or BS 142
(ANSI 50, 50N, 51, 51N)
The function is based on pha-
se-selective measurement of
three phase currents and the
earth current. In addition to the
overcurrent stage there is a
high-set current stage both for
the phases and for the earth.
The high-set current stage al-
ways has definite-time a char-
acteristic. For the overcurrent
stages either definite-time or
inverse-time protection can
be selected. For each stage
the pick-up value and the delay
time (definite time) or the trip-
ping time (inverse time) is se- ç
lectable within a wide range. Fig. 8
Inverse
The following tripping charac-
teristics are available for inver-
se-time overcurrent protection: è
Fig. 9
Very inverse

014
. 13.5
t= ⋅Tp t= ⋅Tp
eI I j
p
0.02
−1 e I Ip j − 1

Inverse-time characteristics
acc. to IEC 255-3 or BS 142
• Inverse
• Very inverse
• Extremely inverse
• Long inverse

• t = tripping time in s
• I = measured current
• Ip = settable
threshold value ç
0.1 to 4 I/IN Fig. 10
Extremely
• Tp = time multiplier inverse
è
Fig.11
Long inverse

Note for Figs. 8 to 11


Scope of I/Ip from 1.1 to 20

80 120
t = ⋅ Tp t = ⋅ Tp
b g
I Ip
2
−1 bI I g − 1
p

Siemens LSA 2.1.9 ⋅ Oct. 1997 9


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Functions

Inverse-time characteristics
acc. to ANSI/IEEE
• Inverse
• Short inverse
• Long inverse
• Moderately inverse
• Very inverse
• Extremely inverse
• Definite inverse
• I squared T

ç
Fig.12
Inverse

è
Fig. 13
Short inverse

F 8.9341 I F 0.2663 I
t= GG + 017966
. JJ ⋅ D t= GG + 0.03393J ⋅ D
JK
H eI I j − 1 K H eI I j − 1
2.0938 12969
.
p p

• t = tripping time in s
• I = measured current
• Ip = settable
threshold value
0.1 to 4 I/IN
• D = time multiplier

ç
Fig. 14
Long inverse
è
Fig. 15
Moderately
inverse

Note for Figs. 12 to 19


Scope of I/Ip from 1.1 to 20

F 5.6143 I F 0.0103 I
t= GG I I − 1 + 218592JJ ⋅ D GG + 0.0228J ⋅ D
JK
He j
. t=
p K H eI I j − 1
p
0.02

10 Siemens LSA 2.1.9 ⋅ Oct. 1997


Switch-onto-fault protection
If the 7SJ531 detects a manu-
al close onto a fault, an instanta-
neous trip can be issued. If clos-
ing is effected via an external
switch - thus bypassing the
control function of the 7SJ531 -
this closing action must be
communicated to the 7SJ531
via a binary input. If the internal
control function is used (local-
ly, via binary input or via serial
interface) the manual-close
function is available without re-
quiring additional wiring.

ç
Fig.16
Very inverse

è
Fig. 17
Extremely inverse

F 3.922 I F 5.64 I
GG + 0.0982J ⋅ D GG + 0.0243J ⋅ D
JK
t=
H eI I j − 1
p
2 JK t=
H eI I j − 1
p
2

ç
Fig. 18
Definite inverse
è
Fig. 19
I squared T

F 0.4797 I F 50.7 ⋅ D+10.14 I


GG + 0.21359J ⋅ D
JK GG J
H e I I j JK
t= t=
H eI I j − 1
15625
. 2
p p

Siemens LSA 2.1.9 ⋅ Oct. 1997


11
SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Functions

Directional earth-fault detec- Directional overcurrent-time


tion (ANSI 64, 67G) protection (ANSI 67, 67N)
For isolated and compensated The directional detection in the
networks the 7SJ531 offers a 7SJ531 is phase-selective and
directional earth-fault detec- is carried out separately for
tion. The energy flow direction phase and earth faults. The sta-
in the zero sequence system ges for the directional detec-
is established on the basis of tion run parallel to the non-di-
the zero sequence current I0 rectional overcurrent stages
and the zero sequence voltage and can be set independently
V0. In networks with isolated of these with regard to the
starpoint the content of the re- pick-up values and the delay-
active current is evaluated, times. There are two stages
whereas in compensated net- for both phase and earth, the Correction = +15°
works evaluation is based on overcurrent stages having ei-
the active currents. Harmonics ther definite-time or inverse-
are efficiently suppressed by time characteristics while the
means of a powerful numerical high-set current stages always directional
filter. For particular network have a definite-time charac-
conditions, e.g. for high-resi- teristic. The directional overcur-
stance earthed networks with rent-time protection compri-
capacitive earth-fault current or ses the following features:
low-resistance earthed net- • Separate settings for phase-
works with ohmic inductive cur- to-phase and phase-to-earth
rents, the tripping charac- faults reverse forward
teristic can be rotated by ± 45
• Directional detection for pha- Fig. 20
degrees (see Fig. 20). Directional determination using cosine measurements
se-to-phase faults by means
Because of the low content of for compensated networks
of the short-circuit current
the active current in compensa- and the healthy phase-to-pha-
ted networks, it is recommen- se voltage
ded to connect the sensitive • Directional detection for
earth - current input to a core- earth faults on the basis of
balance current transformer
displacement voltage VE and
and to connect the V0 input to inductive
zero sequence current I0
an open delta winding. It is
also possible to evaluate the V0 • Evaluation of the displace-
voltage on the basis of the ment voltage either on the
three phase-to-earth voltages basis of the phase voltages
and to emulate the earth cur- or by using an open delta
rent by means of a Holmgreen winding
circuit. In general, this is quite • Voltage storage, if voltages reverse
sufficient for isolated networks. drop below the measuring
forward
The directional earth-fault de- limit.
tection can be operated with
the tripping option or in the
”annunciation-only” mode.
The following functions are im-
plemented: capacitive
• TRIP via displacement volt-
age VE
• Two definite-time stages:
Fig. 21
IEE>> and IEE> or alternative- Directional characteristic of the directional
ly a definite-time stage overcurrent-time protection
IEE>> and a user-definable
characteristic.
Each stage can be operated ei-
ther forward, reverse or non-di-
rectionally.

12 Siemens LSA 2.1.9 ⋅ Oct. 1997


Reserve interlocking on dou-
ble-end fed line
(cross connection)
This function is used for
selective protection of sec-
tions with infeed from both si-
des (e.g. segments of closed
rings), without the disadvanta-
geous delay of grading inter-
vals. The directional compari-
son protection is suitable if the
individual protection units are
not too far apart and if pilot wi- Faultde-
res are available for signal tection
transmission. In addition to the
directional comparison protec-
tion, which provides the main
protection, the directional gra- Blocking
ded overcurrent-time protec- Faultde- Fault detection of non-directional
tection
tion serves as a fully selective I> stage
back-up protection. If operated Direction of short-circuit
with signal transmission dur-
ing quiescent state an inter-
Fig. 22
ruption of the transmission is Directional comparison protection
signalled.
Undervoltage protection Automatic reclosure Fault locator
Voltage protection (ANSI 27) (ANSI 79) Indicates the distance to the
When phase-to-earth voltages To protect equipment against The 7SJ531 is equipped with fault location in kilometers or
are connected, either phase-to- undervoltage two stages with automatic reclosure. If the miles, or indicates the secon-
earth or phase-to-phase volt- definite-time delay are provid- fault is still present even after dary loop reactance. The fault
ages can be evaluated. The lat- ed. To prevent permanent the last reclosing cycle, lock- location can be evaluated ei-
ter remains unchanged in the fault detection after trip of cir- out is established. The possi- ther after drop-off, after a trip
event of an earth fault (isolated cuit-breaker, provided the volt- ble functions are: command or by triggering via a
or compensated networks). age transformers are located binary input. This means that
• 3-pole tripping
on the feeder side, the current the fault location can also be
• Separate settings for phase-
Overvoltage protection of the feeder can be evaluated evaluated when tripping is in-
to-phase and phase-to-earth
(ANSI 59) in the derivation of fault detec- itiated by another protection
faults
tion. device.
To protect equipment against • Multiple reclosure, rapid
overvoltage an overvoltage sta- Using a startup criterion, the auto-reclosure (RAR) and up
ge with a definite delay time pickup threshold can be chan- to nine delayed auto-reclosu-
has been integrated. In order ged for the duration of startup re cycles (DAR)
to achieve a reset when a feed- when a motor is connected.
This allows for the fact that dur- • Auto-reclose trigger depend-
er is tripped and the voltage ing on the stage selective
transformer is positioned on ing startup of the motor less
severe voltage dips can be tole- trip command, e.g.
the busbar side, the current of
rated than during rated opera- − high-set overcurrent stage
the feeder can be evaluated in
tion. phase
the derivation of fault detec-
− overcurrent stage phase
tion.
− high-set overcurrent stage
Breaker-failure protection earth
(ANSI 51BF) − overcurrent stage earth
If a fault is not cleared after a − corresponding directional
protective trip command, a short-circuit stages
further command can be releas- − unbalanced-load protection
ed by means of the breaker- • Option of blocking auto-
failure protection, for instance a reclosure via binary input
command which will affect the
• External triggering of auto-
circuit-breaker of an up-stream
reclosure
protective device. The breaker
failure is detected by the fact • Blocking of the directional
that current is still flowing in and non-directional high-set
the respective feeder after the overcurrent stages during
trip-command. As an alterna- the RAR cycle.
tive, the auxiliary contact feed-
back of the circuit-breaker can
be referred to.

Siemens LSA 2.1.9 ⋅ Oct. 1997 13


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Functions

Thermal overload protection


(ANSI 49)
Parameter Parameter
For the protection of cables or Set value Set value
machines, an overload protec- Time constant Time constant
tion with an alarm stage for tem- τ/min τ/min
perature and current is imple-
mented. The temperature is
determined using a thermal ho-
mogeneous body model (acc.
to IEC 255-8) that takes into ac-
count energy input to the
equipment and energy
output to the environment
and which constantly compen-
sates the temperature.
Thus previous loading and
load fluctuations are taken into
account.
Given constant current, the
tripping time t is calculated ac-
cording to the following form:

F I I −F I I
2 2

GH k ⋅ I JK GH k ⋅ I JK
pre

t = τ ⋅ ln N N

F I I −1 2

GH k ⋅ I JK
N
Fig. 23
Tripping charac-
• t = tripping time after begin- teristics for complete
ning of the overload memory without pre-
vious load and at
• τ =thermal time constant 90 % of previous load
• Ipre = pre-load current
• I = overload current
• k = k-factor (in accordance
with IEC 255-8)
• ln = natural logarithm Tripping characteristic
(see Fig. 23)

For the thermal protection of Unbalanced-load


motors (particularly of the sta- zone I2>
tor) an additional time constant
τ can be selected to ensure
that the thermal conditions are Unbalanced-load
zone I2>>
correctly established both Fig. 24
when the motor is running and Characteristic of the
unbalanced-load pro-
when it is at rest. tection function
The model automatically
works correctly, if the equip-
ment is operated within the lim- Unbalanced-load protection Applied to a motor, the unba-
its of the ambient temperature (ANSI 46) lanced-load protection serves
for which the producer has (see Fig. 24) to detect phase failures or un-
specified the maximum load- The unbalanced-load protection balanced loads which are due
ing current. Substantial varia- makes it possible to detect on to network unbalance, and to
tions of the ambient tempera- the HV side high-resistance protect the rotor against exces-
ture (e.g. the summer - winter two-pole faults as well as single- sive temperature rise.
- difference) can be accounted pole faults located on the For detection of the unbalan-
for via a second parameter set. LV side of a transformer e.g. ced load, the ratio negative-se-
with vector group Dy. Thus a quence current by rated cur-
back-up protection for high-re- rent is evaluated. There are
sistance faults is provided two definite-time stages.
which extends across the en-
tire transformer.

14 Siemens LSA 2.1.9 ⋅ Oct. 1997


Starting time monitoring
(ANSI 48)
The starting time monitoring
protects the motor against un-
duly prolonged start-ups,
which may occur if for instan-
ce too high load torques are
existant, if too severe voltage
dips occur when the motor is
being switched on or if the ro-
tor is blocked. An occurrance
of the latter type can be com- = start-up current
of the motor
municated to the 7SJ531 via a
= maximum per-
binary input, so that an instanta- missible starting
neous disconnection is effect- time
ed. The tripping time is current- = pick-up setting of
dependent. It is obtained function
according to the following
equation: Fig. 25
F I I ⋅t
=G
Characteristic of starting

H I JK
Start time monitoring
tTRIP Start max
rms

• tTRIP = tripping time


• IStart = starting current of
the motor
• tStart max = maximum permis-
sible starting time
• Irms = actual flowing current
(measured variable)

Using the above formula for


the tripping time, even prolong-
ed start-ups with reduced
voltage (and reduced starting
current) are correctly evaluat-
ed.

Start inhibit
If a motor is started too fre-
quently in succession, the ro-
tor, in particular the upper ed-
ges of the bars, can be subject
to thermal overloading. The
start inhibit permits starting of
the motor only if the rotor has
enough thermal reserve for a
complete start.

Emergency start Undercurrent monitoring


This function disables the start (ANSI 37)
inhibit via a binary input. In this This function permits detec-
case, the status of the thermal tion of a spontaneous current
replica is retained as long as drop-off which may occur due
the binary input is active. It is to reduced motor loading.
also possible to reset the ther- Thus it is possible to detect
mal replica to zero. shaft damage, no-load opera-
tion of pumps or blower failure.

Siemens LSA 2.1.9 ⋅ Oct. 1997 15


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Typical applications

Busbar protection
(Reverse interlocking)
The high-set stages of the pro- Supply feeder
tection devices can be blocked
via a binary input (NC or NO
contact). In this manner the
7SJ531 protection device pro-
vides a simple and fast protec-
tion for single busbars with sin-
gle-end infeed.

Relay 2
Relay 1

Relay 3
I>> block

TRIP TRIP TRIP TRIP

Fig. 26
Busbar protection by Fault location A: Tripping time TI>> Relay 1
reverse interlocking Fault location B: Tripping time t1 Relay 3
Backup time TI> Relay 1

Transformer protection
The high-set stage allows cur-
rent grading, the overcurrent
stages operate as a backup pro-
tection for the downstream pro-
tection devices and the over-
load function protects the
transformer against thermal
overload. Weak-current single-
pole faults on the low-voltage
side which appear on the high-
voltage side in the negative
phase-sequence system can
be detected by the unbalanced
- load function.

Fig. 27
Typical protection
of a transformer

16 Siemens LSA 2.1.9 ⋅ Oct. 1997


Motor protection
Stage I>> and IE>> can be
applied for short-circuit protec-
tion. For isolated networks the
sensitive earth-fault detection
function (IEE>>, V0>) can be
used. Protection is provided
for the stator against thermal
overload (ϑs>) and for the rotor
(I2>, starting-time monitoring,
start inhibit). Via a binary input Locked Starting-time Start
rotor monitoring inhibit
a locked rotor can be detected
and switched off. The under-
voltage function prevents start-
ing when voltage is too low,
the overvoltage function
averts damages of the insula-
tion.

Tachome-
Fig. 28 ter
Typical protection
of a high-voltage
asynchronous
motor

Line protection
Simple ring systems within
medium-voltage overhead sys-
tems can be protected as
shown in Fig. 29.
At the supply terminals an
auto-reclose can be employed;
the other devices are equipped
Automatic Automatic
with directional overcurrent- reclose reclose
time protection.

Fig. 29
Typical protection of
a medium-voltage
ring system

Siemens LSA 2.1.9 ⋅ Oct. 1997 17


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Typical applications

Standard connection
For earthed networks the
earth current is derived via the
Holmgreen circuit from the
phase currents. Version for panel surface mounting
Provided the premise
0.1 IN < Iearth < 1.5 Asecondary is Version for panel flush/cubicle mounting
met, the Holmgreen circuit
can be used.
The sensitive IEE transformer
has to be looped in the earth
current circuit. If the earth cur-
rent does not comply with the
a.m. premise a core-balance
current transformer according
to Fig. 30 is required.

Important! Earthing of cable shield at outgoing cable!


Fig. 30
Connection to Note: Switching of current polarity (parameter address 1101)
3 voltage trans- causes polarity reversal of current input IEE!
formers

Connection for compensat-


ed networks
The diagram shows the con-
nection of two phase-to-earth Version for panel surface mounting
voltages and the VE voltages of
the open delta winding and a
Version for panel flush/cubicle mounting
core-balance current transform-
er for the earth current.
This connection provides maxi-
mum accuracy in directional
earth-fault detection and should
be applied in compensated net-
works.

Fig. 31 Important! Earthing of cable shield at outgoing cable!


Connection of
a open delta Note: Switching of current polarity (parameter address 1101)
winding causes polarity reversal of current input IEE!

18 Siemens LSA 2.1.9 ⋅ Oct. 1997


Connection for isolated or
compensated networks only
If no directional earth-fault de-
tection is used, a connection
with two phase-current trans- Version for panel surface mounting
formers is sufficient. For the di-
rectional phase-overcurrent-
Version for panel flush/cubicle mounting
time protection the phase -
to-phase voltages detected by
two primary voltage transfor-
mers are sufficient.

Fig. 32
Connection to two
current and two voltage
transformers

Overview of connection types


Function Type of network Current connection Voltage connection
Overcurrent-time protection, (low-resistance) Holmgreen circuit, needed with –
phases/earth fault, non-directional earthed networks 3 phase-current transformers, earth
with core-balance current-transformers
possible
Overcurrent-time protection, isolated or compen- Holmgreen circuit, possible with –
phase fault, non-directional sated networks 3 or 2 phase-current transformers
Overcurrent-time protection, (low-resistance) Holmgreen circuit, needed with phase-to-earth connection or
phase fault, directional earthed networks 3 phase-current transformers phase-to-phase connection
Overcurrent-time protection, (low-resistance) Holmgreen circuit, needed with phase-to-earth connection
earth fault, directional earthed networks 3 phase-current transformers, core- needed
balance current transformers possible
Overcurrent-time protection, isolated or compen- Holmgreen circuit, possible with phase-to-earth connection or
phase fault, directional sated networks 3 or 2 phase-current transformers phase-to-phase connection
Sensitive earth-fault protection, isolated networks Holmgreen circuit, if 0.1 IN < earth 3 x phase-to-earth connection
sin ϕ measurement current < 1.5 A secondary, otherwise or phase-to-earth connection
core-balance current transformer needed with open delta winding
Sensitive earth-fault protection, compensated networks core-balance current transformers phase-earth connection with
cos ϕ − measurement needed open delta winding
Sensitive earth-fault protection (low-resistance) core-balance current transformers –
earthed networks needed

Siemens Lsa 2.1.9 ⋅ Oct. 1997 19


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Technical data

Input circuits Rated current IN 1 or 5 A


Rated voltage VN 100 to 125 V
Rated frequency fN 50 or 60 Hz
Thermal overload capability in voltage path, continuous 140 V
in current path, continuous 4 x IN
1s 100 x IN
Dynamic overload capability (half cycle) 250 x IN
Power consumption, voltage inputs Approx. 0.5 VA
current inputs at IN = 1 A Approx. 0.1 VA
at IN = 5 A Approx. 0.2 VA
Voltage supply
via integrated DC/DC converter Rated auxiliary voltage Vaux / permissible tolerance 24, 48 V DC / 19 to 56 V DC
60, 110, 125 V DC / 48 to 144 V DC
220, 250 V DC / 176 to 288 V DC
Max. ripple at rated voltage ≤ 12 %
Power consumption, quiescent Approx. 12 W
energized Approx. 23 W
Max. back-up time during loss of auxiliary voltage ≥ 50 ms for Vaux ≥ 110 V DC
Binary inputs
Number 11, for each switching device 1 pair
permanently assigned, the rest freely assignable
Voltage range 24 to 250 V DC
Current consumption independent of operating voltage Approx. 2.5 mA
Alarm/event contacts
Number of relays with 1 C/O contact each 4 (marshallable)
Alarm/event relay with C/O contact 1
Switching capacity make/break 20 W/ VA
Switching voltage 250 V AC/DC
Permissible current, continuous 1A
Command contacts
Number of relays with 1 NO contact each 2 (marshallable)
with 2 NO contacts each 2 (marshallable)
Switching capacity make 1 000 W/ VA
break 30 W/ VA
Switching voltage 250 V AC/DC
Permissible current continuous 5A
0.5 s 30 A
LEDs
Ready indication green 1
Fault indication red 1
Marshallable LEDs red 6
Serial interfaces
Operator interface non-isolated, on front panel
connection 9-way sub connector
baud rate 1 200 to 19 200 Bd
Potential-free interface for connection to a control centre
standard Protocol to DIN 19 244
baud rate 4 800 to 19 200 Bd
fibre-optic connection integrated FSMA connector for connection
to fibre-optic cables at rear side
optical wavelength 820 nm
permissible attenuation Max. 8 db
distance Max. 1.5 km
no character Switchable, supplied “light off“
Unit design
Housing, dimensions 7XP20, see dimension drawings
Weight flush mounting/cubicle mounting Approx. 9.5 kg
Degree of protection according to EN 60529 IP 51
Standards
DIN VDE 0435, Part 303 and IEC 255-5 or IEC 255-6 –
Insulation tests
High-voltage test 2 kV (rms), 50 Hz; 1 min or
alternatively 2.8 kV DC; 1 min
Impulse voltage test 5 kV (peak); 1.2/50 µs; 0.5 J;
3 positive and 3 negative shots
in intervals of 5 s

20 Siemens LSA 2.1.9 ⋅ Oct. 1997


Disturbance tests High-frequency test 2.5 kV (peak); 1 MHz; τ = 15 µs,
(1MHz test) 400 shots per second; duration 2 s
IEC 255-22-1, class III
Electrostatic discharge 8 kV (peak); 5/30 ns;
(ESD test) 10 positive discharges
IEC 255-22-2, class III
Electromagnetic fields Frequency 27 to 500 MHz; 10 V/m
(Radiated electr. magn. field test)
IEC 255-22-3, class III
Fast transient test 2 kV (peak); 5/50 ns; 5 kHz;
IEC 255-22-4, class III 4 mJ per impulse; 1 min per polarity
EMC tests, emission Conducted interference voltage, aux. voltage 150 kHz to 30 MHz
(type tests)
¨
Standard: 50081- (generic
CISPR 22, EN 55022, DIN VDE 0878 Part 22
Interference field strength
limit value class B
30 to 1000 MHz
standard)
CISPR 11, EN 55011, DIN VDE 0875 Part 11 limit value class A
Climatic conditions Permissible ambient temperature in service -5 to +55 °C
during storage -25 to +55 °C
during transport -25 to +55 °C
Humidity rating Annual average ≤ 75 % relative humidity,
on 30 days per year up to 95 % relative
humidity; condensation not permissible
Mechanical stress tests Permissible mechanical stress in service 10 to 60 Hz: 0.035 mm amplitude
IEC 68 Parts 2 - 6 60 to 500 Hz: 0.5 g acceleration
IEC 255 Part 21, 1
during transport 5 to 8 Hz: 7.5 mm amplitude
8 to 500 Hz: 2 g acceleration
Definite-time overcurrent Overcurrent phase I> / phase Idir.> I/ IN = 0.1 to 25, infinity
protection earth IE> / earth IE dir.> I/ IN = 0.05 to 25, infinity
non-directional/directional
High-set current phase I>> / phase Idir.>> I/ IN = 0.1 to 25
earth IE>> / earth IE dir.>> I/ IN = 0.05 to 25
Delay times 0 to 60 s or infinity
Tolerances
Current pick-up value ±5 % of set value
Time ±1% or ±10 ms
Reset time Approx. 30 ms
Inverse-time overcurrent Overcurrent phase Ip / phase Ip dir .> Ip/ IN = 0.1 to 4 / Ip dir. /IN = 0.1 to 4
protection earth IEp / earth IEp dir. > IEp/ IN = 0.05 to 4 / IEp dir. / IN = 0.05 to 4
non-directional/directional
High-set current phase I>>(definite time, ANSI 51) / I/ IN = 0.1 to 25
phase Idir. >>(definite time, ANSI 51)
earth IE>> (definite time, ANSI 51) / I/ IN = 0.05 to 25
earth IE dir. >>(definite time, ANSI 51)
Time multiplier tp 0.05 to 3,2 s and infinity
Pick-up value 1.1 x Ip
Characteristics according to IEC 255-4, Normal inverse, very inverse, extremely
Section 3.5.2 or BS 142 and ANSI C37 inverse, I/ Ip = 1 to 20, definite time char-
acteristic above 20 x Ip
Tolerances
Pick-up values I>>, IE>>, Ip, IEp 3 % of setting value
Delay time for 2 ≤ I/Ip ≤ 20 5 % of setting value
additionally 2 % current tolerance or 30 ms
Overvoltage protection Overvoltage V> 40 to 130 V
Delay time tu> 0 to 60 s and infinity
Tolerances
Voltage thresholds 3 % of set value
Delay times 1 % or 10 ms
Undervoltage protection Undervoltage V< 30 to 120 V
V<< 30 to 120 V
Reset ratio r 1.05 to 3
Delay time tu< 0 to 60 s and infinity
tu<< 0 to 60 s and infinity
Tolerances
Voltage thresholds 3 % of set value
Delay times 1 % or 10 ms

Siemens LSA 2.1.9 ⋅ Oct. 1997 21


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Technical data (continued)

Overload protection Factor k 0.1 to 4


Time constant τ 1 to 999.9 min
Alarm temperature ΘAlarm 50 to 100 %
Current alarm stage IAlarm 0,1 to 4 x I/ IN
Prolongation factor at stand-still 1 to 10
referring to time constant with
running engine, factor τ
Tolerances
Referring to k ⋅ IN 5 % class index acc. to IEC 255-8
Referring to trip time 5 % ± 2 s; class index acc. to IEC 255-8
Auto-reclose function Number of possible auto-reclosures, 3-pole 1 rapid auto-reclosure
up to 9 delayed auto-reclosures
Program for phase faults
Initiation possible with High-set O/Current I>>
Overcurrent DMT I >, IDMT Ip
directional stages, unbalanced-load protection
Program for earth faults
Initiation possible with High-set E/F IE>>
Overcurrent DMT IE >, IDMT IEp
directional stages, unbalanced-load protection
Action times 0.01 to 320 s and ∞
Dead time RAR 0.01 to 320 s
Dead times DAR 0.01 to 1 800 s
Reclaim time 0.5 to 320 s
Blocking times 0.5 to 320 s and ∞
Close command duration 0.01 to 32 s
Earth-fault protection Earth-fault detection with displacement voltage VE> 2 to 130 V
Faulted phase indication (only with directional option)
VPH-E < the faulted phase 10 to 100 V
VPH-E >the healthy phase 10 to 100 V
Measuring tolerance according to VDE 0435 part 303 ≤ 5 % of set value
(for sinusoidal quantites)
Directional determination
Measuring principle Active/reactive power calculation
Earth-faut current IEE>/IEEP (active and reactive) 3 to 1 600 mA
Angle correction for core balance current transformer 0 to 5° in 2 CT operating points
Adjustment of directional characteristic - 45 to +45°
Measuring tolerance according to VDE 0435 part 303 ≤ 10 % of set value
(for sinusoidal quantites)
Circuit-breaker failure protection Triggering threshold I> 0.04 to 1 x I/ IN
Delay time tbreaker-failure protection 0.06 to 60 s or infinity
Tolerances
Pick-up value 3 % of setting value
Delay time t 1 % of setting value or 20 ms
Unbalanced-load protection Setting range
Tripping stage I2>, I2>> in steps of 1% 5 to 80 % of IN
Time delays T(I2>), T(I2>>) in steps of 0.01 s 0 to 60 s
Lower function limit at least one phase current ≥ 0,1 x IN
Higher function limit all phase currents ≤ 4 x IN
Tolerances
Pick-up values I2>, I2>> current I/ IN ≤1.5 ±1 % of IN ±5 % of set value
current I/ IN >1.5 ±5 % of IN ±5 % of set value
Stage delay times T(I2>), T(I2>>) ±1 % or 10 ms
Starting time monitoring Setting ranges
for motors Start-up current of the motor Istart /IN 1 to 16
Pick-up threshold Istart en../IN 0.6 to 10
Permissible start-up time Tstart max. 1 to 180 s
Permissible locked-rotor time Tlock. rot. 0.5 to 120 s or ∞
Tolerances
Pick-up value 3%
Delay time t 5 % of setting value or 30 ms

22 Siemens LSA 2.1.9 ⋅ Oct. 1997


Start inhibit Setting ranges
for motors Start-up current referred to rated motor current IA/IB 3 to 10
Rated motor current, rated transformer current IB/IN 0.2 to 1.2
Max. permissible start-up time Tstart. max. 3 to 120 s
Rotor temperatur-delay time Tdelay 0 to 60 min
Max. permissible hot starts nh 1 to 4
Difference between hot and cold starts nc − nh 1 to 2
Prolongation factor for time constant 1 to 10
of rotor; stand still kτL
Fault location Output of fault distance in Ω secondary,
in km or mile line length
Start-to-measure command by trip signal or drop-off of fault detection
or by external command via binary input
Setting reactance per unit line length (secondary) 0.01 to 10 Ω/miles, 0.006 to 6.215 Ω/km
Measuring tolerances acc. to VDE 0435 part 303 ≤ 2,5 % of line length (without intermediate
sinusoidal quantities infeed) 30° ≤ ΦK ≤ 90° and VSC/VN ≥ 0.1
Fault recording Measured values i L1, i L2, i L3, i E, v L1, v L2, v L3, v E
Start signal Trip, fault detection, binary input, LSA/SCADA,
integrated operating panel
Recording duration Max. 5 s
Holding time Until fault-recording buffer full. New fault
entries overwrite the oldest recorded
faults.
Operational measured values Currents IL1, IL2, IL3, IE
Voltages VL1, VL2, VL3, V12, V23,V13, V0
Powers P, Q
Power factor cos ϕ
Energies Wp+, Wp-, Wq+, Wq-
Frequency f
Thermal replica Θ, ΘR
Measuring ranges 0 to 240 % IN
0 to 120 % VN
P, Q are represented if all voltages and cur-
rents are within the valid range.
CE-conformity, standards This product is in conformity with the directives of the Council of
the European Communities on the approximation of the laws of
the Member States relating to the electromagnetic compatibility
(EMC Council Directive 89/336/EEC) and concerning electrical
equipment for use within specified voltage limits (low-voltage
directive 73/23/EEC). The product conforms with the international
standard IEC 255 and the national standard DIN 57 435 part 303.
The relay is designed for use in an industrial environment acc. to the
EMC standard specification.
Conformity is proved by tests performed by Siemens AG in line with
article 10 of the Council Directives in accordance with the generic
standards EN 50081-2 and EN 50082-2 for the low-voltage directive.

Siemens LSA 2.1.9 ⋅ Oct. 1997 23


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Selection and ordering data

Designation Order No.

SIPROTEC 7SJ531 (Version V3.2) 7SJ531 –



o ooAo2 – ooAo
▲▲ ▲ ▲▲ ▲
Numerical line and motor protection with control functions
Rated current at 50/60 Hz
1A 1
5A 5

Auxiliary voltage Vaux for integrated DC/DC converter


24, 48 V DC 2
60, 110, 125 V DC 4
220, 250 V DC 5

Construction
Housing 7XP2030-1 for panel surface mounting without glass cover B
Housing 7XP2030-2 for panel flush mounting/cubicle mounting E
with Weidmüller terminals without glass cover

Languages
German/English 0
German/French 1
German/Polish 2

Function range
with wattmetric earth-fault detection, with auto-reclose 0
with wattmetric earth-fault detection, without auto-reclose 1
without wattmetric earth-fault detection, with auto-reclose 2
without wattmetric earth-fault detection, without auto-reclose 3

Serial system interface


without serial system interface A
with serial 820 nm fibre-optic module (FSMA connector) C

Directional overcurrent-time protection


without 0
with 1

Manual 7SJ531
German C53000 - G1100 - C114-1
English - G1176 - C114-1
French - G1177 - C114-1
Polish - G1155 - C114-1

DIGSI (Operating and analysis software 7XS5020 – oAA00



for numerical protection devices)

Operating languages
German 0
English 1
French 2

24 Siemens LSA 2.1.9 ⋅ Oct. 1997


Connection diagram

Version for panel surface mounting

Version for panel flush mounting/cubicle mounting

Alarm relay 1

Alarm relay 2

Alarm relay 3

Alarm relay 4

Malfunction
relay

Command
relay 1

Command
relay 2

Binary Command
input 1 relay 3
Command
Binary relay 4
input 2
Binary Binary
input 3 input 8

Binary Binary
input 4 input 9
Binary Binary
input 5 input 10

Binary Binary
input 6 input 11

Binary Power
input 7 supply

Fibre-optic interface connection


to the control unit

Fig. 33
Connection diagram

Siemens LSA 2.1.9 ⋅ Oct. 1997 25


SIPROTEC 7SJ531 (Version V3.2)
Numerical Line and Motor Protection with Control Functions
Dimension drawings (in mm)

Diam. 5 or M 4

Fibre-optic
interface

Front view Side view Panel cut out

Fig. 34
7SJ531 with 7XP2030-2 housing
for panel flush mounting/cubicle mounting

Cutout 20 x 60
(without paint)

Fibre-optic interface

Front view Side view Detail Z

Fig. 35
7SJ531 with 7XP2030-1 housing
for panel surface mounting with two-tier terminals

26 Siemens LSA 2.1.9 ⋅ Oct. 1997


Technical specification

The protective relays measur- The motor protection func- It must be possible to connect a
ed value processing must be tions must be suitable for core-balance current transform-
completely numerical, i.e. all asynchronous machines of all er for sensitive earth-fault
the way from sampling and di- sizes. Both overvoltage and detection. The phase and
gitizing of the analog values up undervoltage protection func- earth-fault characteristics
to the decision to trip the cir- tions for the motor must be must be directional. It must be
cuit-breaker. The protective de- available. The undervoltage possible to rotate the tripping
vice must feature complete protection should have two characteristic of the wattme-
galvanic and interference-free stages. The starting time tric earth-fault detection for
isolation of the internal proces- monitoring must take account particular network conditions.
sing circuits from the measur- of various starting currents. It A fault locator should indicate
ing und supply circuits of the must be possible to connect the distance to the fault loca-
system by means of shielded an external speed monitor to tion. Automatic reclosure
input, binary I/O modules and the protective device, in order should permit a number of
DC converters. to identify a locked rotor and to reclosing operations.
It must be possible to apply issue a non-delayed trip. The operational measured val-
the combined protection, con- The overcurrent-time protec- ues should include metered
trol and monitoring device in tion must be either definite- values for active and reactive
networks with different types time or inverse-time, separate- work done and operating hour
of neutral point earthing. Con- ly selectable for phase and count. It should be possible to
trol of the switchgear must earth faults. It must be possi- check individual operational
take place via the integrated ble to select from available measured values against set
operator panel, via binary in- characteristic curves (acc. to limits. It should be possible to
puts or via an operating and ANSI/IEEE and IEC) as well as select specific measured val-
analysis program. Telecontrol from an user-defined overcur- ues for indication in the graphic
of the protective device via rent-time characteristic. The in- display. The active and reactive
modem must be possible. verse-time overcurrent protec- power should be provided for
tion should be able to evaluate the LSA/SCADA.
either the fundamental current The internal battery should be
or the true rms value. checked at regular intervals by
the processor. If battery capa-
city drops, an alarm should be
initiated.

Siemens LSA 2.1.9 ⋅ Oct. 1997 27


Catalog Index Please contact your
Siemens representative

Catalog Index of the Protection and Substation Control

Title Designation Order No.

Measurement and Recording Systems


Fault Recorder OSCILLOSTORE SR 10.1 E50001-K4010-A101-A1-7600

Protective Relaying
7SJ41 Definite-Time Overcurrent Protection Relay LSA 2.1.10 E50001-K5712-A201-A2-7600
7SJ511 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.3 E50001-K5712-A131-A3-7600
7SJ512 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.4 E50001-K5712-A141-A3-7600
7SJ512 Numerical Feeder Protection LSA 2.1.30 E50001-K5712-A411-A1-7600
7SJ531 SIPROTEC Numerical Overcurrent Protection Relay LSA 2.1.9 E50001-K5712-A191-A4-7600
7SJ551 Multi-Function Protection Relay LSA 2.4.2 E50001-K5742-A121-A3-7600
7SJ600 SIPROTEC Overcurrent, Motor and Overload Protection LSA 2.1.15 E50001-K5712-A251-A2-7600
7SJ601 SIPROTEC Overcurrent Protection LSA 2.1.16 E50001-K5712-A261-A1-7600
7SA510 Distance Protection Relay (Version V3) LSA 2.1.17 E50001-K5712-A271-A1-7600
7SA511 Line Protection Relay (Version V3) LSA 2.1.11 E50001-K5712-A211-A2-7600
7SA513 Line Protection Relay (Version V3) LSA 2.1.12 E50001-K5712-A221-A1-7600
7SA518/519 Overhead Control-Line Protection Relay (Version V3) LSA 2.1.14 E50001-K5712-A241-A1-7600
3VU13 Miniature Circuit-Breaker LSA 2.1.8 E50001-K5712-A181-A2-7600
7SD502 Line Differential Protection with Two Pilot Wires LSA 2.2.1 E50001-K5722-A111-A2-7600
7SD503 Line Differential Protection with Three Pilot Wires LSA 2.2.2 E50001-K5722-A121-A2-7600
7SD511/512 Current Comparison Protection Relay (Version V3)
for Overhead Lines and Cables LSA 2.2.3 E50001-K5722-A131-A2-7600
7UT512/513 Differential Protection Relay (Version V3)
for Transformers, Generators and Motors LSA 2.2.4 E50001-K5722-A141-A2-7600
7SS5 Station Protection LSA 2.2.5 E50001-K5722-A151-A2-7600
Auxiliary Current Transformers 4AM50, 4AM51, 4AM52
and Isolating Transformers 7XR95 LSA 2.2.6 E50001-K5722-A161-A1-7600
7SN71 Transient Earth-Fault Relay LSA 2.3.2 E50001-K5732-A121-A1-7600
7VC1637 Earth-Leakage Monitor LSA 2.3.4 E50001-K5732-A141-A1-7600
7UM511 Generator Protection Relay (Version V3) LSA 2.5.2 E50001-K5752-A121-A2-7600
7UM512 Generator Protection Relay (Version V3) LSA 2.5.3 E50001-K5752-A131-A2-7600
7UM515 Generator Protection Relay (Version V3) LSA 2.5.4 E50001-K5752-A141-A2-7600
7VE51 Synchronizing Unit LSA 2.5.7 E50001-K5752-A171-A1-7600
7VK512 Numerical Auto-Reclose/Check-Synchronism Relay LSA 2.7.3 E50001-K5772-A131-A1-7600
Test Switch 7XV72 LSA 2.7.8 E50001-K5772-A181-A1-7600
7VP151 Three-Phase Portable Test Set (Omicron CMC56) LSA 2.6.1 E50001-K5762-A111-A2-7600
Centralized and Remote Control of Siemens Protection Relays (Overview)* LSA 2.8.1 E50001-K5782-A111-A1-7600
Operating and Analysis Software DIGSI V3* LSA 2.8.2 E50001-K5782-A121-A1-7600

Substation Control and Protection


Input/Output Unit 6MB522 LSA 1.1.1 E50001-K5701-A111-A4-7600
Input/Output Unit 6MB523 LSA 1.1.2 E50001-K5701-A121-A2-7600
6MB511/6MB512 Substation Master Unit 7SW511/7SW512 Relay Data Concentrator LSA 1.1.3 E50001-K5701-A131-A2-7600
6MB520/6MB521 Input/Output Units LSA 1.1.4 E50001-K5701-A141-A1-7600
6MB513/514 Compact Control Master Unit and Relay Data Concentrator LSA 1.1.6 E50001-K5701-A161-A1-7600
6MB5510 Station Control Unit LSA 1.2.1 E50001-K5701-A211-A2-7600
6MB552 Compact Remote Terminal Unit LSA 1.2.2 E50001-K5701-A221-A1-7600
6MB5530-0 Minicompact Remote Terminal Unit LSA 1.2.3 E50001-K5701-A231-A1-7600
6MB5530-1 Minicompact Remote Terminal Unit for Cable Shield Communication LSA 1.2.4 E50001-K5701-A241-A1-7600
6MB5540 SINAUT LSA COMPACT Remote Terminal Unit LSA 1.2.5 E50001-K5701-A251-A1-7600
6MB5515 Station Control Unit LSA 1.2.6 E50001-K5701-A261-A1-7600
Control in SINAUT LSA Substation Control and Protection LSA 1.4.1 E50001-K5701-A411-A1-7600
Status Indications in SINAUT LSA Substation Control and Protection LSA 1.4.2 E50001-K5701-A421-A1-7600
Analog Values in SINAUT LSA Substation Control and Protection LSA 1.4.3 E50001-K5701-A431-A1-7600
Metering in SINAUT LSA Substation Control and Protection LSA 1.4.4 E50001-K5701-A441-A1-7600
Voltage Control with Input/Output Units 6MB520/6MB521 LSA 1.4.5 E50001-K5701-A451-A1-7600
Network Synchronization with Input/Output Units 6MB520/521 LSA 1.4.6 E50001-K5701-A461-A1-7600
Operation with Two Control Master Units LSA 1.4.7 E50001-K5701-A471-A1-7600
Node Functions in SINAUT LSA Substation Control and Protection LSA 1.4.8 E50001-K5701-A481-A1-7600
System Management with the SINAUT LSA Substation Control and Protection System LSA 1.4.9 E50001-K5701-A491-A1-7600
LSADIAG - Testing and Diagnostics System for SINAUT LSA LSA 1.5.2 E50001-K5701-A521-A1-7600
Substation Control and Protection
LSACONTROL - Control and Monitoring LSA 1.5.3 E50001-K5701-A531-A1-7600
LSAPROCESS - Process Information Analysis LSA 1.5.5 E50001-K5701-A551-A1-7600
LSA 678 Standard Cubicle LSA 1.6.1 E50001-K5701-A611-A1-7600
* Information on additional equipment for 7SJ531

28 Siemens LSA 2.1.9 ⋅ Oct. 1997


Conditions of Sale and Delivery ⋅ Export Regulations
Trademarks ⋅ Dimensions
Conditions of Sale and Delivery

Subject to the
General Conditions of Supply The technical data, dimensions
and Delivery and weights are subject to
for Products and Services of change unless otherwise stated
the Electrical and Electronic on the individual pages of this
Industry and to any other catalog.
conditions agreed upon with The illustrations are for
the recipients of catalogs. reference only.
We reserve the right to adjust
the prices and shall charge the
price applying on the date of
delivery. En 1.91a

Export Regulations Trademarks Dimensions

In accordance with the present An export licence may however All product designations used All dimensions in this catalog
provisions of the German Export be required due to country- are trademarks or product are given in mm.
List and the US Commercial specific application and final names of Siemens AG or of other
Control List, export licences are destination of the products. suppliers.
not required for the products Relevant are the export criteria
listed in this catalog. stated in the delivery note and
the invoice regarding a possible
export and reexport licence.
Subject to change without notice.

Siemens online!

The Power Transmission and


Distribution Group can also be
found in the Internet:
http://www.ev.siemens.de

Responsible for
Technical contents:
Hans Heining-Triebs, Marko Zaherdoust,
Siemens AG, EV S V13, Nürnberg
General editing: Claudia Kühn-Sutiono
Siemens AG, EV BK T, Erlangen

Order No.: E50001-K5712-A191-A4-7600


Printed in Germany
KG K 1097 5.0 28 En 100184 6101/U652
Bereich
Energieübertragung und -verteilung
Geschäftsgebiet Sekundärsysteme
Postfach 4806
D-90026 Nürnberg

Siemens Aktiengesellschaft Order No.: E50001-K5712-A191-A4-7600

You might also like