CHECK & REVISE RECORD

No.: CBD-17-E05-EL-001

Package No. P01 Discipline EL Reviewed by

Design
Tower No. E05 FD Total pages.
Stage

Drawing No. Comments Reply/Revised


E18066- 1.There is no light under the mezzanine floor.
0105D-FD-
17-E05-EG-1-
GP-000-0

E18066- 1. There is no dewatering pump feeder


0105D-FD- routing system layout drawing.
17-E05-EG-1- 2. There is no installation height of the cable
GP-001-0 tray.
3. There is no main cable entrance location.
4. There is no cable tray support drawing.
5. There are no installation location of the
PP-PUMP panel and installation location
of pump control panel for make-up water
dewatering pump.

E18066- 1. Please give the cable types .


0105D-FD-
17-E05-EG-6-
GN-010-0

2. There is no motor control centers single


line diagram for dewatering pump.

Page 1 / 2 22-Apr-20
Package No. P01 Discipline EL Reviewed by

Design
Tower No. E05 FD Total pages.
Stage

Drawing No. Comments Reply/Revised


3. The smoke fan power is different between
E18066-0105D-FD-17-E05-EG-6-GN-
010-0 and E18066-0105D-FD-17-E05-
MH-1-RF-001.

4. There is no Grounding system diagram.


5. There is need to add Cell phone signal
amplifier.
6. There are no ELV system drawings for
CCTV,Access control.

Reviewer Reviewer’s Recheck


Date Date

Page 2 / 2 22-Apr-20