CDV 22, 62
Voltage Controlled Overcurrent Relay
1
CDV 22, 62
Type A relay changes its characteristic at Type B relay changes its characteristic at
60% normal voltage and is used when the 30% normal voltage and is used when the
generator neutral is solidly earthed. The alternator neutral is earthed via a resistor
undervoltage unit is connected between or a distribution transformer. The
phase and neutral and the relay operates undervoltage unit is connected between
for both phase and earth faults. two phases and the relay operates for
phase faults only.
2
CDV 22, 62
Customer Benefits
• Simple construction•
Easy accessibility.
• Drawout case.
GRID
3
CDV 22, 62
Thermal rating
Voltage coil:
Current coil: The continuous voltage ratings are as follows:
The maximum current ratings for 60°C rise in coil temperature Relay Nominal Voltage
are as follows : rating V setting V
Tap (A) Continuous Maximum Type A 63.5 76
rating (A) current for full 250 300
operating time Type B 110 132
on overload at
440 528
TMS 1.0 (A) Accuracy
1A relay 5A relay 1A relay 5A relay 1A relay 5A relay The relay conforms to error class index E 7.5 as per BS 142
0.5 2.5 0.9 4.5 14 70 and 7.5 as per IS 3231.
0.75 3.75 1.11 5.6 13 65
Frequency error
1.0 5.0 1.28 6.4 12 60
Temperature error
For an overload equal to four times the current setting,
the percentage timing errors at ambient temperatures
of +45°C and -5°C are respectively -3% and +4%.
4
CDV 22, 62
unit is 22A for 0.5 s at 0.2A tap and 92A for 0.5 s at 2.0A tap.
Other coil ratings are available on request.
Insulation Contact ratings
The relay meets the requirements of IS 3231IEC 2555 series C-2 kV for 1 minute.
Type of contact Make and carry for 0.5
Case
second
Relays are supplied in drawout cases suitable for flush mounting and are
finished eggshell black and tropicalised. The drawout feature considerably Single disc 2500VA with maxima of
simplifies maintenance and permits testing to be carried out easily and 10A and 660V ac or dc
quickly. A cradle-mounted isolating switch is provided which Two pairs of electrically 7500VA with maxima of t
automatically isolates the trip circuit when the cradle assembly is separate self or hand 30A and 660V ac or dc
withdrawn from the case for maintenance. This prevents any inadvertent reset (provided on the
tripping of the circuit breaker. The case is fitted with switches which auxiliary unit)
prevent opencircuiting of the current transformer circuits on withdrawal
of the relay unit from the case. A filter breather is fitted which equalises pressure inside and outside the case without admitting
dust.The triple pole relays are mounted in size 3D horizontal or vertical case, as required.
Figure 2: Typical external and internal connections for type CDV 62B relay with shunt
reinforcing unit in size 3D double ended vertical case
5
CDV 22, 62
* Add 76 mm for maximum length of terminal studs, alternatively, 29 mm for terminal screws.
The approximate gross weights given above are inclusive of carton mounting appendages and terminal
details.
The relays comply fully with the requirements of IS 3231 and are suitable for use in normaltropical
environments.
Information required with order
1. Type of relay
2. Current transformer secondary rating
3. Nominal voltage rating
4. Auxiliary voltage (for shunt reinforcing units)
5. Auxiliary contacts - self or hand reset
6. Case size
Figure 3 : Case and panel cut-out dimensions for case 3D vert drawout (all dimensions in mm)
6
CDV 22, 62