Alarm overzicht November 2018

Number Alarm Cause: Heat pump operation: Action: Type

1 Sensor fault Sensor not Calculated flow Proposal: Check the


BT1 connected/defective temperature is set to min sensor and its
calculated flow connections. See also
temperature the electrical wiring
diagram.

2 Sensor fault Sensor not Addition blocked. GM is Proposal: Check the


BT2 connected/defective calculated with sensor and its
(heating medium "condensor out" sensor. connections. See also
return) Even if "condensor out" the electrical wiring
sensor is missing, heating diagram.
is blocked.

VVM 500: 1. Using BT 3 if


its available. 2. If BT 3 is
not avaialable, BT63 will
be used.

3 Sensor fault Sensor not Compressor is blocked Proposal: Check the


BT3 connected/defective when hot water loading. sensor and its
(heating medium connections. See also
return) VVM 500: Let the heating the electrical wiring
medium pump go diagram.
according to the speed
that is chosen in the
menu 5.1.19= constantly

6 Sensor fault Sensor not Automatic reset Proposal: Check the


BT6 connected/defective sensor and its
(hot water, connections. See also
controlling) the electrical wiring
diagram.
VVM 500: Using
BT54

7 Sensor fault Sensor not Automatic reset Proposal: Check the


BT7 connected/defective sensor and its
(hot water peak) connections. See also
the electrical wiring
diagram.

8
10 Sensor fault: Sensor not GP2 switches to manual Proposal:
BT10 connected/defective speed if auto-control is - Check the sensor and
(brine in) selected. Automatically its connections.
resets when the sensor
has been running
correctly in 60 sec. GP2
returns to auto-control
led operation.

11 Sensor fault Sensor not Compressor blocked Proposal: Check the


BT11 connected/defective sensor and its
(condensor out) connections. See also
the electrical wiring
diagram.

12 Sensor fault Sensor not Supply sensor (BT2) is Proposal: Check the
BT12 connected/defective used for controlling max sensor and its
(condensor return) condensor out connections. See also
temperature for the the electrical wiring
compressor. If supply diagram.
sensor is also missing;
blocked heating mode
and blocked compressor
in HW mode.

16 Sensor fault Sensor not Automatic reset Proposal: Check the


BT16 connected/defective sensor and its settings.
(evaporator) See also the electrical
wiring diagram.

20 Ground source: Sensor not Ground source: Pump Proposal: Check the
Sensor fault connected/defective (AZ1-GP2) in FLM is sensor and its
AZ1-BT20 (exhaust air) blocked. connections. See also
Exhaust air: Exhaust air: Automatic the electrical wiring
Sensor fault reset diagram.
BT20

21 Ground source: Sensor not Grounde source: Pump Proposal: Check the
Sensor fault connected/defective (AZ1-GP2) in FLM is sensor and its
AZ1-BT21 (extract air) blocked. connections. See also
Exhaust air: Exhaust air: Automatic the electrical wiring
Sensor fault reset diagram.
BT21

22 Sensor fault Sensor not


DEW-BT6 connected/defective
(hot water sensor,
controlling in extra
water heater)

25 Sensor fault Sensor not External additive blocked Proposal: Check the
BT25 connected/defective sensor and its
(heat medium connections. See also
return external) the fault-tracing
schedule for the
current product.

26 Sensor fault Sensor not Pump (AZ1-GP2) in FLM is Proposal: Check the
AZ1-BT26 connected/defective blocked. sensor and its
(brine, collector in) connections. See also
the fault-tracing
schedule for the
current product.
27 Sensor fault Sensor not Compressor blocked Proposal: Check the
BP8 connected/defective sensor and its
(low pressure connections.
sensor)

28 Sensor fault Sensor not No action. Togehter with Proposal: Check the
BT71 connected/defective alarm 25; heat is blocked. sensor and its
(external heating connections.
medium return)

29 Sensor fault Sensor not Compressor blocked Proposal: Check the


BT29 connected/defective sensor and its
(compressor oil connections.
temperature)

31 Sensor fault Sensor not Automatic reset Proposal: Check the


BT63 connected/defective sensor and its
(heating medium connections. See also
supply after the electrical wiring
immersion heater) diagram.

VVM 500: Blocking


internal electric
addition

32 Sensor fault Air flow is out of Automatic reset. Check that the filter is
BS1 range of the air Compressor blocked. installed. Check the
velocity sensor fan speed.

33 Sensor fault Sensor not Solar additive blocked. Proposal: Check the
EP30-BT53 connected/defective senors and its
(solar collectors) connections. See also
the electrical wiring
diagram.

34 Sensor fault Sensor not Solar additive blocked Proposal: Check the
EP30-BT53 connected/defective sensor and its
(solar panel) connections. See also
the electrical wiring
diagram.

35 Sensor fault Sensor not Shunt closes. Burner Proposal: Check the
EM1-BT52 connected/defective shuts down. sensor and its
(boiler connections. See also
temperature) the electrical wiring
diagram.

36 Sensor fault Sensor not Control on return sensor Proposal: Check the
EP21-BT2 connected/defective (EP21-BT3) sensor and its
(supply sensor, connections. See also
heating system 2) the electrical wiring
diagram.

37 Sensor fault Sensor not Control on return sensor Proposal: Check the
EP22-BT2 connected/defective (EP22-BT3) sensor and its
(supply sensor, connections. See also
heating system 3) the electrical wiring
diagram.

38 Sensor fault Sensor not Control on return sensor Proposal: Check the
EP23-BT2 connected/defective (EP23-BT3). sensor and its
(supply sensor, connections. See also
heating system 4) the electric wiring
diagram.
39 Sensor fault Sensor not Brine blocked, brine Proposal: Check the
EQ1-BT64 connected/defective shunt closes. sensor and its
(brine, supply) connections. See also
the electric wiring
diagram.

40 Compressor Compressor phase Compressor blocked Proposal: Check the


phase1 missing is missing or has phase. Reset the
been below 160V in phase.
more than 30 min.

41 Compressor Compressor phase Compressor blocked Proposal: Check the


phase 2 missing is missing or has phase. Reset the
been below 160V in phase.
more than 30 min.

42 Compressor Compressor phase Compressor blocked Proposal: Check the


phase 3 missing is missing or has phase. Reset the
been below 160V in phase.
more than 30 min.

43 Faulty phase Phases ar connected Compressor blocked Proposal: Reconnect


sequence in wrong sequence the phase sequence
on incoming
electricity.

44 Overheated Fuses for the soft Compressor blocked. - Defective fuse


softstart start card are - Defective soft start
defective card
Also read: TDI Alarm
44 F1345 2013-12-18

45 Motor protection
on single phase
(Norway) has
probably been
triggered.

50 High pressure The high pressure Compressor blocked. Bad circulation in the
alarm switch has Manual reset. heating medium
triggered circuit.
repeatedly Proposal:
- Bleed heat pump
and climate system
- Check the heating
medium pump
- Open any radiator
thermostats
- Check that the
particle filter is not
blocked
- Check that the
pressure switch is
correctly connected
Fault in cooling
circuit:
- Call a qualified
refrigeration
technician

51 Low pressure F1145: Low Compressor blocked. Proposal:


alarm pressure sensor has Manual reset. Groundsource: Check
been below its cut- the brine flow and
off value. Others: brine frost protection
The low pressure point. See also the
switch has electric wiring
triggered. diagram. Exhaust air: -
Check ventilation flow
and exhaust air
temperature. - Check
that the pressure
switch is correctly
connected - Check the
defrost function and
the sensors that
control it.

52 Temperature Temperature Immersion heater Proposal:


limiter limiter has tripped blocked. Manual reset. - Check if air in
system.
- Check if heating
medium flow is
correct.
- Manual reset of the
temerature limiter.
See also the electric
wiring diagram.

53 Level switch Level switch The compressor and Proposal: Check and
brine /pressure brine pump are blocked. seal any leaks in the
switch has collector circuit.
triggered

54 The motor Proposal: Check the


protection breaker cabling connections of
has triggered. the compressor.
Manual reset.

55 Hot gas alarm Comperssor has Compressor blocked. Proposal:


been stopped Manual reset. Ground source: Call a
because the hot gas qualified refrigeration
temperature technician.
exceeded its limits. Exhaust air: See alarm
number 50, High
pressure alarm.

56 Incorrect serial Serial number does Compressor stopped and Proposal: Check the
number not exist relay deactivated serial number

57 Incorrect Serial number and Compressor blocked and Proposal: Make sure
firmware firmware do not relay deactivates. that the firmware is
match. designed for the
product and serial
number.

58 Pressure switch High- or low Compressor blocked. Bad circulation in


pressure switch heating medium or
have triggered. collector circuit.
Proposal:
- Bleed heat pump,
climate system and
collector circuit
- Check the brine
freezing point
- Check the heating
medium and brine
pump
- Open any radiator
thermostats
- Check that the
particle filter is not
blocked
- Check that the
pressure switch is
correctly connected
Fault in cooling
circuit:
- Call a qualified
refrigeration
technician

60 Low HTF out The temperature of Compressor blocked. Proposal:


the outgoing brine Bad circulation in the
goes below the set brine circuit
min- temperature - Check the brine
and the alarm is pump
selected. - Check that the brine
is bled. Minimum limit
is usually changed
only at groundwater
installations and open
systems.

63 Low air flow


Too low air flow at Compressor blocked Check the air filter ,
air flow sensor BS1 fan speed and air flow

64 Low exhaust air Exhaust air Compressor blocked, For firmware version
temperature temperature has automatic reset. before 1770 - select
been below 16° C Resets when the exhaust "auxiliary operation".
and not risen above air temperature has been For firmware version
17° C within 60 above 17° C in 60 from 1770 onwards-
minutes. minutes. the machine switches
to auxiliary operation
mode automatically.

65 High
condensation Alarm from Compressor blocked - Check the outflow
water level external level from external
monitor condensation water
container

66 High
condensation Alarm from level Compressor blocked - Check that the water
water level monitor in has a free flow from
condensation water the container
container - Empty water
container

67 Antifreeze
protection Supply air Fans stops and Suggestions:
Supply air temperature (BT22) compressor is blocked.
is below 5° C . Any blocking of - Bleed the supply air
immersion heater battery (QM 21).
repeals.
- Check the water
temperature and the
flow to the heating
battery.

69 Not affected
Non-calibrated The air flow sensor Perform a ventilation
air flow sensor has not been adj u stment and set
calibrated the real air flow in
menu 5.1.5.1

70 Perm. com. No communication Calculated flow is set to Proposal: Check the


error input with the input card min. flow. Manual reset. communication
card circuits connections on
the input card and
display card.

71 Perm. com. No communication Compressor blocked. Proposal: Check the


error base card with the base card Manual reset. communication
(AA2 at AA26). circuits connections on
the base-, input- and
display card.

72 Perm. com. No communication Compressor blocked. Proposal: Check the


error softstart with the softstart communication
card card. circuits connections on
softstart card and
base card.

73 Perm. com. No communication Accessory blocked. Proposal:


error heating with the accessory - Check the power
system 2 card. supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

74 Perm. com. No communiation Accessory blocked. Proposal:


error heating with the accessory - Check the power
system 3 card. supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

75 Perm. com.
error base card No communication Compressor blocked. Check the
with the base card Manual reset. communication circits
(AA26). connections on hte
base-, input- and
display card.

76 Perm. com. No communication Accessory blocked. Proposal:


error heating with the accessory - Check the power
system 4 card. supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

77 Accessory blocked.
Perm. com. No communication Proposal:
error additive with the accessory - Check the power
with shunt card. supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

78 Perm. com. No communication Accessory blocked. Proposal:


error pool with the accessory - Check the power
card. supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

79 Perm. com. Permanent Accessory blocked. Check the cables and


error FLM communication cards.
fault with the
accessory card for
FLM.
Communication
cables to the card
are incorrect or
incorrectly
installed.
Fault in the
communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

83 Unsuccessful
defrosting F 1 P r op o sal
1
0 :

Defrost discontinued.
Compressor stopped.

86 Perm. com. No communication - Check the power


error SAM 40 with the accessory supply to the
card for SAM 40 accessory card.
- Check the setting of
which is activated the dipswitch.
in menu 5.2. - Check the
communication cables
leading to the
accessory card.

87 Perm. com. Permanent Accessory blocked. Proposal: Check the


error step communication cables and cards.
controlled fault with the
additive accessory card with
step controlled
additive.

88 Perm. com. Permanent Accessory blocked. Proposal: Check the


error Solar communication cables and cards.
fault with the
accessory card for
Solar.
Communication
cables to the card
are incorrect or
incorrectly
installed.
Fault in the
communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

89 Perm. com. Permanent Accessory blocked. Proposal: Check the


error HPAC communication cables and cards.
fault with the
accessory card for
HPAC.
Communication
cables to the card
are incorrect or
incorrectly
installed. Fault in
the communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

90 Perm. com. Permanent Accessory blocked. Proposal: Check the


fault communication cables and cards.
groundwater fault with the
pump accessory card for
groundwater
pump.
Communication
cables to the card
are incorrect or
incorrectly
installed.
Fault in the
communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

91 Perm. com. Permanent Accessory blocked. Proposal: Check the


error HWC communication cables and cards.
fault with the
accessory card for
hot water
circulation.
Communication
cables to the card
are incorrect or
incorrectly
installed.
Fault in the
communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

92 Perm. com.
error DEW Permanent Accessory blocked. Proposal: Check the
communication cables and cards.
fault with the
accessory card for
DEW.
Communication
cables to the card
are incorrect or
incorrectly
installed.
Fault in the
communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

93 Perm. com.
error 2-pipes Permanent Accessory blocked. Proposal: Check the
cooling communication cables and cards.
fault with the
accessory card for
2-pipes cooling.
Communication
cables to the card
are incorrect or
incorrectly
installed.
Fault in the
communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

94 Perm. com. Permanent Accessory blocked. Proposal: Check the


error PCD4 communication cables and cards.
fault with the
accessory card for
4-pipes passive
cooling.
Communication
cables to the card
are incorrect or
incorrectly
installed.
Fault in the
communication
circuits in the
accessory-, input- or
display card.
Incorrect address on
the dipswitch.

95 Perm. Com. Permanent Accessory blocked. Proposal: Check cables


Error communication and cards.
fault with

96 Perm. Com. Permanent Room unit blocked. Proposal: Check


Room unit, communication communication
zone 1 fault with room cables.
unit, zone 1.

97 Perm. Com. Permanent Room unit blocked. Proposal: Check


Room unit, communication communication
zone 2 fault with room cables.
unit, zone 2

98 Perm. Com. Permanent Room unit blocked. Proposal: Check


room unit, communication communication cables
zone 3 fault with room
unit, zone 3

99 Perm. Com. Permanent Room unit blocked Proposal: Check


room unit, communication communication
zone 4 fault with room cables.
unit, zone 4.

100 Perm. Com. Permanent Compressor blocked Propposal:


error inverter communication - Check the power
fault with the supply leading to
inverter inverter and
communication
cables.

101 Sensor fault Sensor temporarily Proposal: Check any


BT1 missing sensors and
connections

102 Sensor fault Sensor temporarily Proposal: Check any


BT2 missing sensors and
connections

103 Sensor fault Sensor temporarily Proposal: Check any


BT3 missing sensors and
connections

104 Sensor fault Sensor temporarily Proposal: Check any


BT4 missing sensors and
connections

105
Sensor fault Sensor temporarily Proposal: Check any
BT5 missing sensors and
connections

106 Sensor fault Sensor temporarily Proposal: Check any


BT6 missing sensors and
connections

107 Sensro fault Sensor temporarily Proposal: Check any


BT7 missing sensors connections

108 Sensor fault Sensor temporarily Proposal: Check any


BT8 missing sensors and
connections

109 Sensor fault Sensor temporarily Proposal: Check any


BT9 missing sensors and
connections

110 Sensor fault Sensor temporarily Proposal: Check any


BT10 missing sensors and
connections

111 Sensor fault Sensor temporarily Proposal: Check any


BT11 missing sensors and
connections

112 Sensor fault Sensor temporarily Proposal: Check any


BT12 missing sensors and
connections

113 Sensor fault Sensor temporarily Proposal: Check any


BT13 missing sensors and
connections

114 Sensor fault Sensor temporarily Proposal: Check any


BT14 missing sensors and
connections

115 Sensor fault Sensor temporarily Proposal: Check any


BT15 missing sensors and
connections

116 Sensor fault Sensor temporarily Proposal: Check any


BT16 missing sensors and
connections

117 Sensor fault Sensor temporarily Proposal: Check any


BT17 missing sensors and
connections

118 Sensor fault Sensor temporarily Proposal: Check any


BT18 missing sensors and
connections

119 Sensor fault Sensor temporarily Proposal: Check any


BT19 missing sensors and
connections

120 Sensor fault Sensor temporarily Proposal: Check any


BT20 missing sensors and
connections

140
Compressor Compressor phase 1 Proposal: No action
phase 1 missing has been briefly needed. Possibly check
missing compressor phase.

141 Compressor Compressor phase 2 Proposal: No action


phase 2 missing has been briefly needed. Possibly check
missing compressor phase.

142 Compressor Compressor phase 3 Proposal: No action


phase 3 missing has been briefly needed. Possibly check
missing compressor phase.

145 Temporary Temporary problem Proposal: Check


general phase with the cables/cards
fault communication
from the base card
to the motor
protection

150 High condensor Condensor out has Automatic reset


out reached max
permitted
temperature

155 Hot gas alarm The Hot gas (BT14) Compressor stopped. Proposal:
has temporarilly Automatically reset when - Contact a qualified
been over 135° C the hot gas is below 90° service technician.
C.

158 Low defrost


temperature The temperature at Defrost Proposal:
the defrost (BT76) is discontinued. Compressor - Check the defrost
below -25° C . stopped. function
- Check the defrost
sensor (BT76)
- Check solenoid valve

159 High
evaporator The evaporator Compressor Proposal:
temperature temperature (BT16) stopped. Defrost - Check the defrost
has exceeded discontinued. function
- Check the
evaporator sensor
(BT16)
- Check solenoid valve

160 Low HTFout Brine out has Automatic reset


reached set min
temperature

161 High HTFin Brine in has Automatic reset


reached set max
temperature

162 High condensor Condensor out has Automatic reset


out reached max
permitted
temperature

163 High condensor


in Condensor exceeds Automatic reset
max temperature
164 Low exhaust air See alarm 64 Automatic reset when
temperature the temperature exceeds
17° C below X minutes

166 Electrical Fault in the Proposal:


anode incorrect electrical anode - Check the electric
anode, circuit board
at the electric anode
and the cables to the
electric anode.

170 Com. error Communication Proposal: Check any


input card with the input card cables/cards
is temporarily
missing

171 Com. error Communication Proposal: Check any


base card with the base card cables/cards
is temporarily
missing

172 Com. error Communication Proposal: Check any


softstart card with the softstart cables/cards
card is temporarily
missing

173 Com. error Communication Proposal: Check any


heating system with accessory card cables/cards
2 for climate system 2
temporarily missing

174 Com. error Communication Proposal: Check any


heating system with accessory card cables/cards
3 for climate system 3
temporarily missing

175 Start-up of The softstart card is Proposal: Check any


softstart card started up. Takes cables/cards
approx 20 sec

176 Com. error Communication Proposal: Check any


heating system with accessory card cables/cards
4 for climate system 4
temporarily missing

177 Com. error Communication Proposal: Check any


addition with with accessory card connections, cables
mixing valve for mixing valve and cards.
controlled
additional heat
temporarily missing

178 Com. error Communication Proposal: Check any


pool with accessory card cables/cards
for pool
temporarily missing

179 Com. error FLM Communication Proposal: Check any


with accessory FLM cables/cards
is temporarily
missing

180 Freeze prot Freeze protection Permits room heating


active. Occurs if the
outdoor
temperature is
below 3 degrees
and no heating is
permitted.

181 Failed periodic Periodic increase


increase did not reach the
stop temperature
within 5 hours

182 Load monitor One or more power Proposal: Check the


activated steps cannot be phase load. It may
activated because require a larger main
the current in at fuse.
least one phase is
too high

183 Defrosting Defrosting in No action


progress

184 Filter alarm Air filter needs Proposal: Clean the air
cleaning filter and restart the
heat pump.

185 Anti-freeze Supply air Fans stopped and - Check the water
supply air temperature (BT22) compressor blocked. Any temperature and the
or the return blockage of the flow to the heating
temperature from immersion heater is battery.
the heating battery lifted.
(BT69) is below

187 Com. error step Temporary Proposal: Check any


controlled communication cables/cards
additional heat fault with accessory
card with step
controlled
additional heat

188 Com. fault Temporary Proposal: Check any


solar communication cables/cards
fault with accessory
card with solar

189 Com. error Temporary Proposal: Check any


HPAC comunication fault cables/cards
with accessory card
with HPAC

190 Com. error Temporary Proposal: Check any


ground water communication cables/cards
pump fault with accessory
card with ground
water pump

191 Com. error Temporary Proposal: Check any


HWC communication cables/cards
fault with accessory
card with hot water
circulation

192 Com. error 2 Temporary Proposal: Check any


pipe cooling communication cables/cards
fault with accessory
card with 2 pipe
cooling

193 Com. Error Temporary Proposal: Check any


DEW communication cables/cards
fault with accessory
card DEW

194 Com. Error Temporary Proposal: Check any


PCD4 communication cables/cards
fault with accessory
card with 4 pipe
cooling

195 Com. error Temporary Proposal: Check any


FJ V M communication cables/cards
fault with

196 Com. room unit Temporary Proposal: Check any


zone 1 communication cables/cards
fault with room
unit zone 1

197 Com. room unit Temporary Proposal: Check any


zone 2 communication cables/cards
fault with room
unit zone 2

198 Com. room unit Temporary Proposal: Check any


zone 3 communication cables/cards
fault with room
unit zone 3

199 Com. room unit Temporary Proposal: Check any


zone 4 communication cables/cards
fault with room
unit zone 4

200 Com. error


inverter

201 Inverter alarm Inverter indicates See chapter


alarm Troubleshooting in
the Service manual
SEM NIBE F750 for
fault specification.
Alarm code stands in
alarm log in F750 in
brackets.

202 Inverter fault Inverter indicates See chapter


alarm Troubleshooting in
the Service manual:
SEM NIBE F750 for
fault specification.
Alarm code stands in
alarm log in F750 in
brackets.

203 Inverter error Permanent inveter See alarm tab menu 6


type I fault type I for error code. See
chapter
Troubleshooting in
the Service manual:
SEM NIBE F750 for
fault specification.

204 Inverter error Permanent inverter See alarm tab menu 6


type II fault type II for error code. See
chapter
Troubleshooting in
the Service manual:
SEM NIBE F750 for
fault specification.

205 Inverter error Permanent inverter See alarm tab menu 6


type III fault type III for error code. See
chapter
Troubleshooting in
the Service manual:
SEM NIBE F750 for
fault specification.

206 Perm. com. No communication Proposal:


error HW- with accessory card - Check the power
comfort for 15 sec supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

207 Com. error HW- No communication Proposal: Check any


comfort with the accessory cables/cards

208 Com. error Acc- No communication VVM 500:


EB1 with accessory card - Check the
for 15 sec communication cables
- Check the dip switch
settings

209 Com. error 3 communication Blocking addition


ACC-EPxx faults in a row with
the accessory card

213 Inverter error Temporary inverter Inverter blocked. If the


type I fault alarm is active more than
1h the alarm will pass
over to alarm 203
(Permanent inverter fault
type II)

214 Inverter error Temporary inverter Compressor blocked. If


type II fault type II the alarm is active more
than 1h or if the alarm is
activated 3 times in 2h,
the alarm will pass over
to alarm 204 (permanent
inverter fault type II)

215 Inverter error Temporary Inverter Compressor blocked. If


type III fault type III the alarm is active more
than 1h or if the alarm is
activated 3 times in 2h,
the alarm will pass over
to alarm 204 (permanent
inverter fault type II)

216 Inverter alarm


type II Incorrect inverter Manual reset in menu. Suggestion:
Compressor blocked.
- Upgrade firmware to
at least version:

F1155,
v7740R4
F1255

F2120 v431

F750 v7679R4

F730 v7696R6

- Replace the inverter

220 High pressure Heat pump Compressor blocked See troubleshooting


alarm (selected outdoor for selected outdoor
unit) sending fault unit.
message to the
controller

221 Low pressure Heat pump Comperssor blocked. See troubleshooting


alarm (selected outdoor for selected outdoor
unit) sending fault unit.
message to the
controller

222 Motor Heat pump Compressor blocked See troubleshooting


protection (selected outdoor for selected outdoor
alarm unit) sending fault unit.
message to the
controller

223 Communication Heat pump Compressor blocked See troubleshooting


alarm (selected outdoor for the selected
unit) sending fault outdoor unit.
message to the Read more in: TDI
controller 20141023

224 Fan error Heat pump Compressor blocked See troubleshooting


(selected outdoor for the selected
unit) sending a outdoor unit.
fault message to
the controller

225 Flow/ return Heat pump Compressor blocked See troubleshooting


(selected outdoor for the selected
unit) sending fault outdoor unit.
message to the
controller

227 Sensor fault Heat pump Compressor blocked See troubleshooting


(selected outdoor for the selected
unit) sending fault outdoor unit.
message to the
controller

228 Defrost fault Heat pump Compressor blocked


(selected outdoor
unit) sending fault See troubleshooting
message to the for the selected
controller outdoor unit.

229 Short
operation Compressor has Compressor blocked - Open thermostatic
times for stopped three times valves to ensure
compressor in a row, short time circulation in the
after start heating system
- Bleed the climate
system and heat pump
- Check the filter in
the climate system
and possible
ventilation
- Check the start- and
stop temperature for
hot water charging
- Check the heating
medium pump
- Check the cooling
circuit

230 Hot gas alarm Heat pump Compressor blocked See troubleshooting
(selected outdoor for the selected
unit) sending fault outdoor unit.
message to the
controller

231 Phase sequence Heat pump Compressor blocked See troubleshooting


error (selected outdoor for the selected
unit) sending fault outdoor unit.
message to the
controller

232 Low Heat pump Compressor blocked See troubleshooting


evaporation (selected outdoor for the selected
unit) sending fault outdoor unit.
message to the
controller

236 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check sensor
AZ2-BT20 connected/defective GP2) in FLM blocked and its connections
(exhaust air)

237 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check sensor
AZ2-BT21 connected/defective GP2) in FLM blocked and its connections
(exhaust)

238 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check sensor
AZ2-BT26 connected/defective GP2) in FLM blocked and its connections
(brine collector in)

239 Sensor fault Sensor not


AZ3-BT20 connected/defective
(exhaust)

240 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check any
AZ3-BT21 connected/defective GP2) in FLM blocked sensor and its
(exhaust) connections

241 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check sensor
AZ3-BT26 connected/defective GP2) in FLM blocked and its connections
(brine collector in)
242 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check sensor
AZ4-BT20 connected/defective GP2) in FLM blocked and its connections
(exhaust)

243 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check sensor
AZ4-BT21 connected/defective GP2) in FLM blocked and its connections
(exhaust)

244 Sensor fault Sensor not Circulation pump (AZ1- Proposal: Check sensor
AZ4-BT26 connected/defective GP2) in FLM blocked and its connections
(brine collector in)

245 Com. error FLM No communication Accessory blocked Proposal:


2 temporarily with - Check fuses, power
the accessory FLM 2 supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

246 Com. error FLM No communication Accessory blocked Proposal:


3 temporarily with - Check fuses, power
accessory FLM3 supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

247 Com. error FLM No communication Accessory blocked Proposal:


4 temporarily with - Check fuses, power
the accessory FLM4 supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

248 Communication
fault No connection Compressor and charging - Checkt the
between the pump stopped communication cable
display unit and the between the display
base card unit and the base card

250 Com.error ACC- No communication Accessory blocked See troubleshooting


SMS 40 temporarily with IHB SMS 40
accessory card

251 Com. error ACC No communication Accessory blocked See troubleshooting


Modbus 40 temporarily with IHB SMS 40
accessory card

252 Com.error slave No communication Compressor in slave Proposal: Check slave


temporarily with blocked settings in menu 5.2.2,
slave heat pump communication cables
and its connections.
Read more in: TDI
20141023

253 Sensor fault Sensor not Mixing valve closes Proposal: Check sensor
QZ1-BT70 connected/defective and its connections
(hot water flow)

255 Motor Motor protoection Current comperssor Bad circulation in


protection on the brine pump blocked. Automatic reset. brine circuit:
alarm, brine triggered - check the brine
pump pump
- vent the brine
system
- check the particle
filter so its not
clogged
- check the brine
pump cables and
connections with the
heat pump

257 Com. error No communication Accessory blocked Proposal:


ACS45 temporarily with - Check fuses, power
accessory card supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

258 Sensor fault Sensor not Proposal: Check sensor


EQ1-BT57 connected/defective and its connections
(Cooling brine)

259 Sensor fault Sensor not Proposal: Check sensor


EQ1-BT75 connected/defective and its connections
(cooling flow heat
pump)

261 This alarm was Temperature Compressor blocked Proposal:


generated by deviation on the - Defect sensor
the heat pump heat exchanger - Insufficient air
sensor (Tho-R1/R2) circulation
five times within 60 - The heat exchanger
minutes or is clogged
continuously in 60 - Defect control card
minutes EB101
- Too large amount of
refrigerant

262 This alarm was Overheat power Compressor blocked 15V power to the
generated by transistor inverters PCB is
the heat pump unstable.

263 This alarm was Incorrect voltage Compressor blocked Proposal:


generated by out from the - Disruption on
the heat pump inverter incoming power
- Service valve closed
- Not enough
refrigerant amount
- Compressor fault
- Defect circuit board
for the inverter in
EB101

264 This alarm was Communication Compressor blocked Proposal:


generated by between circuit - Disruption on the
the heat pump board for the connection between
inverter and control cards
card is interupted - Defect circuit board
for the inverter in
EB101
- Defect control card
EB101

265 This alarm was Continuous error Compressor blocked Proposal:


generated by on power transistor - Defect fan motor
the heat pump during 15 minutes - Defect circuit board
for the inverter in
EB101

266 This alarm was Low refrigerant Compressor blocked Proposal:


generated by amount - Service valve closed
the heat pump - Loose contact on
sensor (BT15, BT3)
- Defect sensors (BT15,
BT3)
- Too low refrigerant
amount

267 This alarm was Inverter fault, boot Compressor blocked Proposal:
generated by failure - Defect circuit board
the heat pump for the inverter in
EB101
- Defect control card
EB101
- Compressor fault

268 This alarm was Overcurrent, Compressor blocked - Sudden power


generated by inverter A/F module failure
the heat pump

270 Compressor Preheat Compressor is in


preheater is preheat mode until
active BT29> B P8

270 Preheating
Preheat of the Compressor is blocked.
compressor is active Automatic reset.

271 Cold outdoor EB 101 sending Compressor blocked


air EB 101 message to the
controller

272 Hot outdoor air EB 101 sending Compressor blocked


message to the
controller

273 HW-start and Adj u stment of HW-start and HW-stop


HW-stop have hotwater-settings for economy and normal
been reset to because of short have been reset to
factory settings operation time factory settings

274 Compressor Load monitor has


phase caused the
overloaded compressor not to
operate with
desired power.

275 Compressor Load monitor has


phase caused the
overloaded compressor not to
longtime operate with
desired power.

277 This alarm was Sensor fault MHI Compressor blocked Proposal:
generated by exchanger - Sensor fault heat
the heat pump exchanger F2040,
THO-R1(BT16)/THO-
R2
EB101
- Defect control card

278 This alarm was Sensor fault MHI Compressor blocked Proposal:
generated by ambient air - Sensor fault outdoor
the heat pump temperature sensor
Tho-A(BT28) EB101
- Defect control card
EB101

279 This alarm was Sensor fault MHI Compressor blocked Proposal:
generated by discharge - Sensor fault hotgas
the heat pump BT14 (Tho-D) EB101
- Defect control card
EB101

280 This alarm was Sensor fault MHI Compressor blocked Proposal:
generated by suction - Sensor fault suction
the heat pump gas BT17 (Tho-S)
EB101
- Defect control card
EB101

281 This alarm was Sensor fault MHI LP Compressor blocked Proposal:
generated by - Sensor fault low
the heat pump pressure sensor BP2
(LTP) EB101
- Defect control card
EB101
- Error in refrigerant
circuit EB101

282 Comm.error Three Accessory blocked.


ACC.-EQ1 communication Temporary
error in a row has communication fault.
occurred towards
the accessory card
ACS 310

283 Comm. Error Permanent Accessory blocked Proposal:


Acc.-EQ1 communication - Check
error ACS310 communication cables
- Check dipswitch
settings

290 Fan alarm


The speed signal - Compressor stopped. Check the fan, cables
(tachometer signal) - Immersion heater and connections and
from the fan stopped. the base card.
indicates that the - Defrost stopped.
fan speed is zero.
291 Charge pump
alarm The speed signal - Compressor stopped. Check the charge
(tachometer signal) - Immersion heater pump, cables and
from the charge stopped. connections and the
pump indicates that - Defrost stopped. base card.
the charge pump
speed is zero.

294 Not compatible


heatpump The alarm occurs if HW blocked. Unit cannot Check the connections
the outdoor unit be restarted after power of the outdoor unit
toward VVM320 is supply was off. and dip switch
not a F2030-7, settings.
F2030-9, F2040-8, Read more in: TDI
F2040-12. 20141023 , TDI
Faulty settings of 20140813
the dip switches on
the circuit board.

299 Wrong version Firmware version Compressor blocked. Proposal:


PCA Base on the base card Reset when the correct - Change base card
(AA2) is too low for version is detected. (AA2)
inverter
communication.

301 Com. error


slave 1 No communication Slave compressor blocked Proposal: Check slave
temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB101) and its connections.
Read more in: TDI
20141023

302 Com. error No communication Slave compressor blocked Proposal: Check slave
slave 2 temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB102) and its connections

303 Com. error No communication Slave compressor blocked Proposal: Check slave
slave 3 temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB103) and its connections

304 Com. error No communication Slave compressor blocked Proposal: Check slave
slave 4 temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB104) and its connections

305 Com. error No communication Slave compressor blocked Proposal: Check slave
slave 5 temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB105) and its connections

306 Com.error slave No communication Slave compressor blocked Proposal: Check slave
6 temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB106) and its connections

307 Com. error No communication Slave compressor blocked Proposal: Check slave
slave 7 temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB107) and its connections
308 Com. error No communication Slave compressor blocked Proposal: Check slave
slave 8 temporarily with settings in menu 5.2.2,
slave heat pump communication cables
(EB108) and its connections

325 Temperature
limiter alarm Temperature Heatpump changes to - Check the filter and
for defrost limiter FD3 has passive defrost air flow
element tripped
- The alarm can be
reset in the alarm
menu but will return
when the defrost
element tries to
connect until the
temperature limiter is
reset.

- Temperature limiter
shall be reset and
function tested by an
installer or service
technician

326 Fault in EB16


Active defrosting Heat pump merges to - Check the filter and
has failed three passive defrost air flow
times in a row - Checkt the
calibration of air
speed sensor BS1 in
menu 5.1.5.1
- Checht the
defrosting element
EB16

340 Anti-freeze Supply air HW load blocked. - Bleed the supply air
supply air temperature (BT22) Returns automatically battery.
is below 11° C . when the supply air - Check the water
temperature exceeds temperature and the
16° flow to the heating
battery.
- If repeated alarms;
verify that circulated
water volume is
sufficient.

351 Uncertain Uncertain sensor GP2 switches to manual Proposal:


sensor accuracy accuracy on the speed if auto control is - Check sensors
brine sensors BT10 selected. Manual reset of BT10
and BT11. The auto control in menu and BT11 and their
difference is more 5.1.9
than 2K between
them at calibration.

352 Uncertain Uncertain sensor GP1 switches to manual Proposal:


sensor accuracy accuracy on the HM speed if auto control is - Check the sensors
sensors BT2 and selected. Manual reset of BT2 and BT3 and their
BT3. The difference auto control in menu connections.
is more than 2K 5.1.11
between them at
calibration.

353 Uncertain Uncertain sensor GP1 switches to manual Proposal:


sensor accuracy accuracy on the HM speed if auto control is - Check the sensors
sensors BT3 and selected. Manual reset of BT3 and BT12 and
BT12. The auto control in menu their connections.
difference is more 5.1.11
than 2K between
them at calibration.

354 Slave EB101 Delta BT3-BT12 is Changes from auto to


larger than 2K after manual circulation pump
calibration speed. Uncertain sensor
accuracy.

355 Slave EB101 Delta BT3-BT63 is Changes from auto to


larger than 2K after manual circulation pump
calibration speed. Uncertain sensor
accuracy.

356 Failed sensor Sensor calibration GP1 will go over to Check the flow in the
calibration differs more than manual operation heating system is not
2K between BT3 disturbed by air or
and BT63 closed ventilators.
Restart the display.

372 Perm. com.


error pool 2 No communication Accessory blocked. Proposal:
with the accessory - Check the power
card. supply leading to the
accessory card.
- Check the
communication cables
leading to the
accessory card.
- Check the setting of
the dipswitch.

403 Sensor fault on Sensor fault - Compressor blocked Proposal:


EB101 detected on EB101 - If GP12 or GP1 is - Check the
of the COM- regulated by sensor temperature sensor
interface MHI- EB101-BT3, they will and its connections.
EMMY swich to the manually set See also the wiring
speed. diagram.

404 Sensor fault on Sensor fault - Compressor blocked Proposal:


EB101 detected on EB101 - Check the
of the COM- temperature sensors
interface MHI- and its connections.
EMMY See also the wiring
diagram.

412 Sensor fault on Sensor fault - Compressor blocked Proposal:


EB101-BT12 detected on EB101 - If GP12 or GP1 is - Check the
of the COM- regulated by sensor temperature sensor
interface MHI- EB101-BT3, they will and its connections.
EMMY swich to the manually set See also the wiring
speed. diagram.

415 Sensor fault on Sensor fault Compressor blocked Proposal:


EB101-BT15 detected on EB101 - Check the
of the COM- temperature sensor
interface MHI- and its connections.
EMMY See also the wiring
diagram.

420 Inverter alarm Compressor stopped. Proposal:


type II Automatic reset 60 sec. - Check the main fuse
A temporary after the inverter fault is and the group fuses
communication reset. The compressor and their connections
alarm has occured. will make a new attempt - Check the
to start according to communication cable
normal start routine. to the inverter and its
connections.
- If the alarm occurs
again; contact a
service technician.

421 Inverter alarm A temporary Compressor blocked. Proposal:


type II communication Manual reset in menu. - Check the main fuse
alarm has occured 3 and the group fuses
times within 2 and their connections.
hours or has been - Check the
continuously for 1 communication cable
h. to the inverter and its
connections
- Do a restart of the
heat pump by turning
it off through the
operating switch
- If the alarm occurs
again; contact a
service technician.

422 Inverter alarm A temporary alarm Compressor stopped. Proposal:


type II on the external Automatic reset 60 sec. - Check the main fuse
input of the after the inverter fault is and the group fuses
inverter has reset. The compressor and its connections
occured will make a new attempt - If the fault occurs
to start according to again; contact a
normal start routine. service technician

423 Inverter alarm A temporary alarm Compressor blocked. Proposal:


type II on the external Manual reset in menu. - Check the
input of the communication cable
inverter has on the external input
occurred 3 times of the inverter
within 2 hours or - Check the main fuse
the input has been and the group fuses
continuously - Restart the heat
broken for 1 hour. pump by turning it off
through the operation
switch
- If the fault occurs
again; contact a
service technician

425 Triggered
pressure switch High pressure Compressor blocked Bad circulation in
switch or low heating system or lack
pressure switch is of
triggered. refrigerant/problem in
refrigerant circuit.

Suggestions:

- Vent the heatpump


and heatingsystem.

- Open all thermostats


on the radiators.

- Check and clean


filters/strainers.
- Check the
chargepump.

- Check that
pressureswitches are
correct wired.

Problem in refrigerant
circuit:

- Call a certified
refrigeration
technician.

426 Inverter alarm A temporarily fault Automatically reset 30 Proposal:


type III in the inverter has minutes after the - Check the main fuse
occur. inverter fault is and the group fuses
corrected. Compressor and their connections.
stopped. - Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

427 Inverter alarm A temporary Compressor blocked. Proposal:


type III internal fault in the Manual reset in menu. - Check the main fuse
inverter has and the group fuses
occurred 3 times and their connections.
within 2 hours or - Restart the heat
continuously in 1 pump through the
hour. power switch to brek
the power.
- If the alarm occurs
again; contact a
service technician.

428 Inverter alarm


type III A temporary Compressor stopped. Proposal:
internal fault in the Automatic reset 60 sec. - Check the main fuse
inverter has after the inverter alarm and the group fuses
occurred. has been corrected. and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

1 phase inverter:
Check the
condensator

429 Inverter alarm


type II A temporary Compressor blocked. Proposal:
internal fault in the Reset manually in menu. - Check the main fuse
inverter has and the group fuses
occurred 3 times and their connections.
within 2 hours or - Restart the heat
continuously in 1 pump through the
hour. power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

1 phase inverter:
Check the
condensator

430 Inverter alarm Phase voltage to Automatic reset 60 sec. Proposal:


type I the inverter has after the fault is - Check the main fuse
temporarily been corrected. Compressor and the group fuses
too high. stopped. and their connections.
- If the alarm occurs
again; contact a
service technician.

431 Inverter alarm Phase voltage to Reset manually in menu. Proposal:


type I the inverter has Compressor blocked. - Check the main fuse
temporarily been and the group fuses
too high more than and their connections.
1 hour. - If the alarm occurs
again; contact a
service technician.

432 Inverter alarm Phase voltage to Automatic reset 60 sec. Proposal:


type I the inverter has after the fault is - Check the main fuse
temporarily been corrected. and the group fuses
too low. and their connections.
- If the alarm occurs
again; contact a
service technician.

433 Inverter alarm Phase voltage to Compressor blocked. Proposal:


type I the inverter has Reset manually in menu. - Check the main fuse
been too low, and the group fuses
below 180V in and their connections.
more than 1 hour. - If the alarm occurs
again; contact a
service technician.

434 Inverter alarm A compressor phase Compressor stopped. Proposal:


type I has temporarily Automatic reset 60sec. - Check the main fuse
been missing. and the group fuses
and their connections.
- If the alarm occurs
again; contact a
service technician.

435 Inverter alarm A compressor phase Compressor blocked. Proposal:


type I continuously Reset manually in menu. - Check the main fuse
missing to the and the group fuses
inverter for an and their connections.
hour. - If the alarm occurs
again; contact a
service technician.

436 Inverter alarm A temporary Compressor stopped. Proposal:


type II internal fault in the Automatic reset 60 sec. - Check the main fuse
inverter has after the inverter fault. and the group fuses
occurred. and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

437 Inverter alarm A temporary Compressor blocked. Proposal:


type II inverter fault in the Manual reset in menu. - Check the main fuse
inverter has and the group fuses
occurred 3 times and their connections.
within 2 hours or - Restart the heat
continuously in 1 pump through the
hour. power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

438 Inverter alarm


type II The inverter has Compressor stopped. Poor circulation in HM
temporary reach Automatic reset 60 sec. circuit. Proposal:
the maximum after the inverter fault is - Bleed the heat pump
operating corrected. and the climate
temperature system.
because of poor - Check the particle
cooling filter, so it is not
clogged.
- Open
radiators/under floor
heating thermostats.

439 Inverter alarm


type II The inverter has Compressor blocked. Poor circulation in HM
temporary reached Reset manually in menu. circuit. Proposal:
maximum - Bleed the heat pump
operating and the climate
temperature system.
because of poor - Check the particle
cooling 3 times filter, so it is not
within 2 hours or clogged.
been missing - Open
continuously in 1 radiators/under floor
hour. heating thermostats.
- If the alarm occurs
again; contact a
service technician.

440 Inverter alarm Max "power in" has Compressor stopped. Proposal:
type II temporary been too Automatic reset 60 sec. - Check the main fuse
high. after the inverter fault is and the group fuses
corrected. and their connections.
- If the alarm occurs
again; contact a
service technician.

441 Inverter alarm Max "power in" has Compressor blocked. Proposal:
type II temporary been too Reset manually in menu. - Check the main fuse
high 3 times within and the group fuses
2 hours or been and their connections.
missing - If the alarm occurs
continuously for an again; contact a
hour. service technician.

442 Inverter alarm


type II Inverter has Compressor stopped. Poor circulation in HM
temporary reached Automatic reset 60 sec. circuit.
max operating Proposal:
temperature after the inverter fault is - Bleed the heat pump
because of poor corrected. and the climate
cooling. system.
- Check the particle
filter, so it is not
clogged.
- Open
radiators/under floor
heating thermostats.

443 Inverter alarm


type II Inverter has Compressor blocked. Poor circulation in HM
temporary reached Manual reset in menu. circuit. Proposal:
max operating - Bleed the heat pump
temperature and the climate
because of poor system.
cooling 3 times - Check the particle
within 2 hours or filter, so it is not
been missing clogged.
continuously in an - Open
hour. radiators/under floor
heating thermostats.
- If the alarm occurs
again; contact a
service technician.

444 Inverter alarm A temporary Compressor stopped. Proposal:


type II internal fault has Automatic reset 60 sec. - Check the main fuse
occurred in the after the inverter fault is and the group fuses
inverter. corrected. and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

445 Inverter alarm A temporary Compressor blocked. Proposal:


type II inverter fault has Manual reset in menu. - Check the main fuse
occurred 3 times and the group fuses
within 2 hours or and their connections.
continuously in 1 - Restart the heat
hour. pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

446 Inverter alarm A compressor phase Compressor stopped. - Check the main fuse
type II has temporarily Automatic reset 60 sec. and the group fuses
been missing. after the phase has been and their connections.
reset. - If the fault occurs
again; contact a
service technician.

447 Inverter alarm A phase has Compressor blocked. - Check the main fuse
type II temporarily been Manual reset in menu. and the group fuses
missing 3 times and their connections.
within 2 hours or - If the fault occurs
been missing again; contact a
service technician.
continuously for 1
hour.

448 Inverter alarm The compressor has Compressor stopped. - Check the main fuse
type II temporarily been Automatic reset 60 sec. and the group fuses
operating with after the inverter fault is and their connections.
lower speed than corrected. - If the fault occurs
allowed minimum again; contact a
speed. service technician.

449 Inverter alarm The compressor has Compressor blocked. - Check the main fuse
type II temporarily been Manual reset is possible and the group fuses
operating with when the alarm has and their connections.
lower speed than disappeared. - If the fault occurs
allowed minimum again; contact a
speed, 3 times service technician.
within 2 hours or
been missing
continuously for 1
hour.

450 Inverter alarm Not used function - Check the main fuse
type III (false alarm) and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

451 Inverter alarm Not used function - Check the main fuse
type III (false alarm) and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

452 Inverter alarm Power out from Compressor stopped. - Check the main fuse
type II inverter to Automatic reset 60 sec. and the group fuses
compressor has after the inverter fault is and their connections.
temporarily been corrected. - If the fault occurs
too high. again; contact a
service technician.

453 Inverter alarm Power out from Compressor blocked. - Check the main fuse
type II inverter to Manual reset in menu. and the group fuses
compressor has and their connections.
temporarily been - If the fault occurs
too high 3 times again; contact a
within 2 hours or service technician.
been missing
continuously in 1
hour.

454 Inverter alarm Temporary too high Compressor stopped. - Check the main fuse
type II output from the Automatic reset 60 sec. and the group fuses
inverter has after the inverter has and their connections.
occurred. occurred. - If the fault occurs
again; contact a
service technician.

455 Inverter alarm Temporary too high Compressor blocked. - Check the main fuse
type II output from the Manual reset in menu. and the group fuses
inverter has and their connections.
occurred 3 times - If the fault occurs
within 2 hours or again; contact a
been missing service technician.
continuously in 1
hour.

460 Inverter alarm (Only 1-phase) Too Compressor stopped. - Check the main fuse
type II high "power in" to Automatic reset 60 sec. and the group fuses
inverter has after the inverter fault is and their connections.
temporarily corrected. - If the fault occurs
occurred. Can again; contact a
depend on low service technician.
incomming power
(> 1 98 VAC)

461 Inverter alarm (Only 1-phase) Too Compressor blocked. - Check the main fuse
type II high "power in" to Manual reset in menu. and the group fuses
inverter has and their connections.
temporarily - If the fault occurs
occurred 3 times again; contact a
within 2 hours or service technician.
been missing
continuously in 1
hour. Can depend
on low incomming
power (> 1 98

468 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

469 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

470 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

471 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

472 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

473 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

474 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

475 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.
476 Inverter alarm Not used function Proposal:
type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

477 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

478 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

479 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

480 Not used function Proposal:


(false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

481 Inverter alarm Not used function Proposal:


type III (false alarm) - Check the main fuse
and the group fuses
and their connections.
- Restart the heat
pump through the
power switch to break
the power.
- If the alarm occurs
again; contact a
service technician.

995 External alarm An alarm according Only information. - Check possible


to chosen on the A u tomatic reset external connection
AUX - entrance. w h en function.
closing the entrance is

996 Blocked External addition Automatic reset when


heat blocked closing over the entrance
through AUX - is broken. Additional
heat blocked.

997 Compressor
blocked External Automatic reset when
compressor blocked closing over the entrance
through AUX - is broken. Compressor
blocked.