LCD-8200 Installation and


user manual
LDC Panel
INDEX Installation Manual LCD-8200
NOTIFIER ITALIA Doc. M-189.1-LCD8200-ENG Rev A.1 LCD-8200_manu_ENG
.

DETECTION SYSTEM LIMITS


An alarm or fire detection system can be very useful for the prompt warning of any dangerous event, such as
fire, a robbery or a simple burglary, in some cases it can automatically manage events (transmission of
messages for room evacuation, automatic fire-extinguishing, TVCC system interface, access route or door
blockage, automatic warning to authorities, etc.), but in any case, it does not ensure protection against
damages to propriety or damages caused by fires or robberies).
Moreover, each system may not properly operate if it is not installed and maintained according to the
manufacturer’s instructions.

PRECAUTIONS
These instructions contain procedures to be followed in order to avoid damages to
equipment. It is assumed that the user of this manual has performed a training
course and that he knows the applicable rules in force.
The system and all its components must be installed in an environment having the
following features:
Temperature: -5 °C ¸ +40 °C.
Humidity: 10 % - 93 % (without condensation).
Peripheral devices (sensors, etc.) which are not perfectly compatible with the
control unit may cause damages to the same control unit, and a bad operation of
the system in any moment. Therefore, it is essential to only use material which is
guaranteed by NOTIFIER and is compatible with its own control units.
Please consult NOTIFIER Technical Service for any doubt.
This system, like all solid state components, may be damaged by induced
electrostatic voltages: handles the boards keeping them among the edges and
avoid to touch the electronic components.
An appropriate earthing connection ensures, in any case, a sensitivity reduction to
disturbances.
Please consult NOTIFIER Technical Service if you cannot solve installation
problems.
Any electronic system does not operate if it is not powered.
If power supply from the mains fails, the system ensures its operation through
battery, but only for a limited period of time.
During the system planning phase, take into account the autonomy required to
appropriately dimension the power supply and batteries.
Skilled personnel shall periodically check the state of batteries.
Disconnect the MAINS and the batteries BEFORE removing or inserting any board.
Disconnect ALL power supply sources from the control unit, BEFORE performing
any servicing.
The control unit and the connected devices (sensors, modules, repeaters, etc.)
may be damaged, if a new board is inserted or removed, or if the powered cables
are connected.
The most common cause for malfunctioning is inappropriate maintenance.
Take special care of these aspects since you start the system planning phase; this
will facilitate future servicing and will reduce cost.

This panel is market with the CE label to comply with the following European Directives
:
EMC Directive 2004/108/EC and LVD Directive 2006/95/CE)

LCD-8200 Installation and User Manual PAGE - 1


LCD-8200_manu_ENG Doc. M-189.1-LCD8200-ENG Rev A.1 NOTIFIER ITALIA
National Standards

This equipment must be installed and must comply with these instructions and
regulations in force at the installation site.

GENERAL DESCRIPTION
LCD-8200 is a remote repeat panel for the AM-8200, with a 7 "color touch screen.

Connection to Panel:
It connects to the single AM-8200 Panel via an RS.485 serial line.
Along the above serial line can be connected up to 32 LCD-8200.

Configuration:
1- The panel must be configured locally as "GENERAL RECEIVER" or as "Partial".
Note: If configured as "Partial", you must program through the PK-8200 the pairs to the
Zones or Devices you want to display.

2- On the LCD-8200 panel, locate the device address locally (see procedure description). The
programmable addresses range from 1 to 16 for both categories (GLOBAL or PARZIAL), for a total
of up to 32 repeaters.

SPECIFIC PROGRAMMING
If programmed as "GLOBAL", the LCD-8200 repeats all the messages on the control panel and if the control
panel is in a CanBus network, repeats all network events.
In this case, you can perform the following functions:
• EVENT ACKNOLEDGE (Local Buzzer and Central Blur)
• RESET EVENTS
• Lamp test (LEDs and displays)
• Local Buzzer Test
• Historical Archive View
• USB storage of the AM-8200 historical store

If programmed as "PARTIAL", the LCD-8200 allows the display of active events in the sensor / modules
module or selected zones.
You can select up to 64 types of events, referring to the following states in the control panel, or zones or
individual devices:
• Panel Faults
• Panel Exclusions
• Zone Alarm
• Zone Fault
• Fault / Zone Alarm
• Zone Exclusion
• Test Zone
• Sensor Alarm
• Sensor Fault
• Fault and Alarm of Sensor
• Sensor Exclusion
• Module Alarm
• Fault and Alarm of Module
• Module Exclusion

PAGE - 2 Installation and User Manual LCD-8200


NOTIFIER ITALIA Doc. M-189.1-LCD8200-ENG Rev A.1 LCD-8200_manu_ENG
TECHNICAL CHARACTERISTICS

72Mhz microprocessor system, 1Gbit Nand Flash, 256Mbit DDR, 16Mbit Flash SPI

Display 7 "wide TFT RGB 800x480-with resistive Touch Pad with LED backlight.Active area
152.5 mm x 91.44mm anti-glare treatment

Serial lines:
- 1 RS 485 interface

Power supply: 11Vcc ÷ 30Vcc max (polarity inversion protection)

Current Consumption
- At rest 125mA @ 24Vcc (in the absence of anomalies)
- In alarm 236mA @ 24Vcc

Connections
- 2 power supply leads
- 2/3 conductors for serial line connection (2 with common power supplies, 3 with
independent power supplies)

Mechanics: The mechanics of the LCD-8200 panels are suitable for wall mounting.
- Dimensions 213mm (L) x 118mm (H) x 27mm (P)
- Degree of protection: IP 30
- Operating temperature: -5 ° C to + 40 ° C
- Relative humidity: Max 95% (no condensation)
- Storage temperature: -10 ° C to + 50 ° C
- Weight 410g

LCD-8200 Installation and User Manual PAGE - 3


LCD-8200_manu_ENG Doc. M-189.1-LCD8200-ENG Rev A.1 NOTIFIER ITALIA
INSTALLATION
Dimensions for wall mounting

Installation of the LCD-8200 wall panel is


done by fastening the wall mount bracket
through n. 2 self-locking blocks (masonry
walls) or self-tapping screws
prefabricated panels, etc.).
The diameter of the screws used must be
5 mm. max. It is advised not to install the
2 panel near heat sources (radiators,
radiators, etc.).
Staffa di supporto a muro

mu

83,5 mm

Open the cover by Introduce the incoming


unscrewing the two fixing cable to the CNU terminal
screws block.
Secure the incoming cable
with a cable tie.

It is recommended not to install LCD-8200 panels near heat sources (radiators, radiators, etc.).

PAGE - 4 Installation and User Manual LCD-8200


NOTIFIER ITALIA Doc. M-189.1-LCD8200-ENG Rev A.1 LCD-8200_manu_ENG
SIGNALS ON THE FRONT PANEL

ALARM (Red):
Flashes if there is at least one alarm device and has not yet been
recognized.
Fixed if all alarm events have been recognized.
Power (Green):
Fixed Fixed if panel is powered.

Silence Sounder (Yellow):


Switch on after the Silence Sounder command from AM-8200

Fault (Yellow):
Blinks in the presence of an unrecognized failure event.
Fixed if all the faults present have been recognized

Exclusion (Yellow):
Fixed On In the presence of dots or zones disabled.
TEST (Yellow):
Fixed with walk test in progress.

USER INTERFACE DESCRIPTION

The following conditions apply to the panels programmed as "General", while for the panels
programmed as "Partial" you must associate the types of events to be displayed with the help of the
PK-8200.

Normal condition

The following screen is displayed when there are no abnormal conditions on the panel (alarms or faults.

Counter Zone in Counter Zone Counter zones


Pre-Alarm Faults disabled

Counter Zone Counter for


alarm System faults

Panel status signaling icons

In the absence of alarms and failures, the NOTIFIER


logo is present..

The Alert icon is displayed when pre-alarms appear..


The Flame icon is displayed when alarms appear.
The Triangle icon is displayed when alarms appear.

N.B. The alarm condition prevails if there are alarms and Date - Hour
faults in the control panel.

Pressing the "UTIL" Pressing the "DISABL" Pressing the "TEST" Event Acknowledge Silence Sounder Reset Events
key enables the input key enables the input key enables the input to and Buzzer Silence
to the Utility menu to the Exclusions menu the Test menu

LCD-8200 Installation and User Manual PAGE - 5


LCD-8200_manu_ENG Doc. M-189.1-LCD8200-ENG Rev A.1 NOTIFIER ITALIA
20097 Tel: 02/518971
San Donato Milanese Fax: 02/5189730
(MILANO) www.notifier.it
Via Grandi, 22 E-mail: notifier@notifier.it
A Honeywell company

Every care has been taken in the preparation of this data sheet but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice.


D-532.3-NFX-ENG Rev. A.1 10/2009
Photoelectric Smoke Detector

DESCRIPTION
New Series NFX is the latest generation of the
addressable fire detectors develop by Notifier
NFX Series offers cost savings for installers,
enhanced configurability, management and
outstanding detection performance and false alarm
immunity for end users. All of the new benefits are
delivered while maintaining full electrical and
mechanical backwards compatibility with previous
versions to support existing systems. NFX Series has
a new protocol that delivers more devices on the loop
and gives greater control, configurability and device
management whilst enabling the overall system to be
optimised to the location and use of the bulding with
far grater flexibility than even before.
The compatibility with previous protocol, that can
manage up to 99+99 addresses, is ensured 0786-CPD-20658 0786-CPD-20652
(AM2000N, AM4000 e AM6000N). The detector used
with this control panel provide the same functionality NFX-OPT NFXI-OPT
as 700 Series. Additional features allowed by the new
protocol will be available on a new range of control TECHNICAL FEATURES
panel of upcoming production. Voltage range: 15 to32Vdc
Stanby current:
MAIN FEATURES 200µA @ 24Vdc NFX-OPT (no communication)
New mechnical platform with revolutionary chamber 250µA @ 24Vdc NFXI- OPT (no communication)
offering improved false alarm immunity: 220µA @ 24Vdc NFX- OPT (max. avg. standby)
- Improved detection across multiple fire types 270µA @ 24Vdc NFXI- OPT (max. avg. standby)
- Improved resilience to false alarms through dust 3.5mA @ 24Vdc LED red
- Removed risk of false alarms through insects 7.0mA @ 24Vdc LED green
Available with or without Isolator module 10.5mA @ 24Vdc LED amber
Tri colour LED offering red, green and amber Isolation current (NFXI-OPT): 15mA @ 24Vdc
colours Additional loop resistence (NFXI-OPT): 20m
Rotary decade address switches Remote output: 22.5Vdc – 10.8mA
Pure white colour to compliment modern buildings Temperature range: -30°C to +70°C
Inctudes Series 700 Advanced Protocol Humidity: 10 to 93% (without condensate)
100% mechanical and electrical backwards Height: 52mm installed in B501
compatibility IP Rating: IP30 (IP33 with WB-1AP)
New Base design to compliment the detector. Diameter: 102mm
Weight: 97g
Wiring: 2,5mmq
Colour: white
Material: PC/ABS

The NFX-OPT photoelectric smoke detector has a The NFX-OPT has two integraI tri-colour LEDs that
completely new detection chamber design, the result provide 360° local visual indication of the device status.
of many years of research and design. This delivers The LEDs are programmable with static or blinking red,
improved responsiveness, reduced sensitivity amber and green status indications available. NFX-OPT
changes caused by settling dust and reduced false conforms to EN54-7. The new digital protocol provides
alarms resulting from insect ingress and other debris. reduced power consumption across the loop and
The plug-in unit uses sophisticatedprocessing circuitry enables up to 159 devices and modules per loop.
that incorporates smoothing filters to help eliminate
transient environmental noise conditions that can be
the cause of unwanted alarms. The devices are
managed by embedded software running complex
algorithms that further improve resilience to false All detectors are environmentally friendly and meet the
alarms and improve detection speed. WEEE and RoHS legislative requirements, minimising
end of lite disposal costs.
D-532.3-NFX-ENG Rev. A.1 10/2009
Photoelectric Smoke Detector

MOUNTING BASES 1001-001: Kit for detector test


smoke + temperature (includes
1 test unit, 1 TS3-001 smoke
capsule, 2 batteries and
1 battery charger) (ACI110)
2001-001: Kit for detector test
smoke + temperature + CO
(includes 1 test unit, 1 TS3-001
B501AP smoke capsule, 1 TC3-001 CO
capsule, 2 batteries and 1
B501AP: base standard white backward compatible battery charger) (ACI111)
withe (RII200) TS3: Pack of 3 smoke capsule
B524RTE-W: base with relay (RII62RLAP) for unit test for 1001-001 and
2001-001 (ACI112)
ACCESSORIES
WB-1AP: anti-water
cover cap for base 2001-001
and detector white
(RII76AP) MODELS
SMK400EAP:
surface mounting kit STOCK
MODEL DESCRIPTION
CODE
to interface pipeline
bases white (RII71AP) Photoelectric smoke
NFX- OPT RIL400
RMK400AP: flush detector
mounting kit white (RII72AP) Photoelectric smoke
NFXI- OPT RIL410
detector with isolator
TEST ACCESSORIES
SOLO-100: 4,5mt telescopic
tube (ACI100) COMPATIBILITY WITH EXISTING PRODUCTS
SOLO-101: 1mt extension for BASES:B501: base standard h 18,5mm
SOLO-100 (ACI101) B501DG: as base B501 alta 26mm
SOLO-330: Ionization/optical B524IE: base with isolator module
detectors test tool (ACI102) B524RE: base with relay output.
SOLO-AER: Aerosol bomb
for detectors test (350 detectors
around) (ACI103)
SOLO-200: Universal
extraction tool (ACI106)
SOLO-610: Tool bag for
accessories (ACI107)
SOLO-713: Accessory for SOLO-200
magnet (ACI713)

NOTIFIER ITALIA S.r.l. - A socio unico - 20097 San Donato Milanese (Ml) - Via Grandi, 22 - Tel.: 02/518971 - Fax: 02/5189730 - E-mail:
notifier@notifier.it Capitale Sociale € 2.700.000,00 i.v. - C.C.A.A. 1456164 - Trib. Milano Reg. Soc. 348608 - Vol. 8549 Fasc. 8 - Partita IVA
IT 11319700156 (informativa privacy art. 3 Digs 196/03) - Ufficl Regionali: 10151 Torino - Via Pianezza, 181 - Tel.: 011/4531193 - Fax: 011/4531183 -
E-mail: notifier.torino@notifier.it - 35010 Limena (PD) Via IV Novembre, 6/c Int. 9 - Tel.: 049/7663511 - Fax: 049/7663550 - E-mail:
notifier.padova@notifier.it - 40050 Funo di Argelato (BO) - Asta Servizi, Bl. 3B, Gall. B n. 85, Centergross - Tel.: 051/864855 - Fax: 051/6647638 - E-mail:
notifier.bologna@notifier.it - 50136 Firenze –Via Aretina, 167/M Tel/Fax: 055/289177 - 00118 Roma - Via Del Casale Santarelli, 51 - Tel.: 06/7988021 - SISTEMA GESTIONE
QUALITÀ CERTIFICATO
UNI EN ISO 9001:2000
Fax: 06/79880250 - E-mail: notifier.roma@notifier.it - 80143 Napoli - Palazzo Prof. Studi - Centre Direzionale, Isola G1, Scala D, Piano 15° - Tel.:
081/7879398 - Fax: 081/7879159- E-mail: notifier.napoli@notifier.it - 70125 Bari - Via Delia Costituente, 29 - Tel.: 080/5013247 - Fax: 080/5648114 - E-mail:
notifier.bari@notifier.it - 95126 Catania – Viale Alcide De Gasperi, 187 - Tel.: 095/7128993 - Fax: 095/7120753 - E-mail: notifier.catania@notifier.it
www.notifier.it

Tutti i dati sono soggetti a cambiamento senza preavviso. Tutti i diritti di questa pubblicazione sono riservati.
D-532.2-NFX-ENG Rev. A.1 10/2009
Multi-Criteria Photo Thermal Detector

DESCRIPTION
New Series NFX is the latest generation of the
addressable fire detectors develop by Notifier
NFX Series offers cost savings for installers,
enhanced configurability, management and
outstanding detection performance and false alarm
immunity for end users. All of the new benefits are
delivered while maintaining full electrical and
mechanical backwards compatibility with previous
versions to support existing systems. NFX Series has
a new protocol that delivers more devices on the loop
and gives greater control, configurability and device
management whilst enabling the overall system to be
optimised to the location and use of the bulding with
far grater flexibility than even before.
The compatibility with previous protocol, that can
manage up to 99+99 addresses, is ensured
(AM2000N, AM4000 e AM6000N). The detector used
with this control panel provide the same functionality
as 700 Series. Additional features allowed by the new
protocol will be available on a new range of control
panel of upcoming production. 0786-CPD-20657 0786-CPD-20651

MAIN FEATURES NFX-SMT2 NFXI-SMT2


Two sensor multi-criteria fire detector incorporating
photoelectric, and thermal sensing elements.
TECHNICAL FEATURES
New mechnical platform with revolutionary chamber
Voltage range: 15 to32Vdc
Available with or without Isolator module
Stanby current:
Tri colour LED offering red, green and amber
200µA @ 24Vdc NFX-SMT2 (no communication)
colours
250µA @ 24Vdc NFXI-SMT2 (no communication)
Rotary decade address switches 220µA @ 24Vdc NFX-SMT2 (max. avg. standby)
Pure white colour to compliment modern buildings 220µA @ 24Vdc NFXI-SMT2 (max. avg. standby)
Inctudes Series 700 Advanced Protocol 3.5mA @ 24Vdc LED red
100% mechanical and electrical backwards 7.0mA @ 24Vdc LED green
compatibility 10.5mA @ 24Vdc LED amber
New Base design to compliment the detector. Temperature range: -30°C to +70°C
Humidity: 10 to 93% (without condensate)
Height: 61mm installed in B501
IP Rating: IP30 (IP33 with WB-1AP)
Diameter: 102mm
Weight: 99g
Wiring: 2,5mmq
Colour: white
Material: PC/ABS

The multi-criteria multi-sensor NFX-SMT2 Photo unwanted alarms, the detector can be programmed to
Thermal detector uses thermal assistance to the care operate in a "heat only" mode, automatically reverting to
photoelectric smoke detector to give enhanced false full photo-thermal operation during unoccupied periods.
alarm immunity and faster response to a wide range The new digital protocol provides reduced power
of incipient fires. The unit combines two separate consumption across the loop and enables up to 159
sensing elements that are managed by embedded devices and modules per loop.
software to act as a single unit. The NFX-SMT2
conforms to EN54-5, a 58°C fixed temperature and
rate of rise thermal assistance conforming to EN54- 7.
The thermal detection fuction combines thermistor
technology with a software corrected linear All detectors are environmentally friendly and meet the
temperature response. The thermal detection function WEEE and RoHS legislative requirements, minimising
combines thermistor technologywith a software end of lite disposal costs.
corrected lineartemperature response. ln areas where
the normal daytime activities may potentially create
D-532.2-NFX-ENG Rev. A.1 10/2009
Multi-Criteria Photo Thermal Detector

MOUNTING BASES
1001-001: Kit for detector test
smoke + temperature (includes
1 test unit, 1 TS3-001 smoke
capsule, 2 batteries and
1 battery charger) (ACI110)
2001-001: Kit for detector test
smoke + temperature + CO
B501AP (includes 1 test unit, 1 TS3-001
smoke capsule, 1 TC3-001 CO
B501AP: base standard white backward compatible capsule, 2 batteries and 1
withe (RII200) battery charger) (ACI111)
B524RTE-W: base with relay (RII62RLAP) TS3: Pack of 3 smoke capsule
for unit test for 1001-001 and
ACCESSORIES 2001-001 (ACI112)
WB-1AP: anti-water
cover cap for base
and detector white 2001-001
(RII76AP)
SMK400EAP: MODELS
surface mounting kit
to interface pipeline STOCK
MODEL DESCRIPTION
CODE
bases white (RII71AP)
RMK400AP: flush 58°C fixed temperature
NFX-SMT2 RIL401
mounting kit white (RII72AP) detector
78°C fixed temperature
TEST ACCESSORIES NFXI-SMT2 RIL411
detector
SOLO-100: 4,5mt telescopic
tube (ACI100)
SOLO-101: 1mt extension for COMPATIBILITY WITH EXISTING PRODUCTS
SOLO-100 (ACI101) BASES:B501: base standard h 18,5mm
SOLO-330: Ionization/optical B501DG: as base B501 alta 26mm
detectors test tool (ACI102) B524IE: base with isolator module
SOLO-AER: Aerosol bomb B524RE: base with relay output.
for detectors test (350 detectors
around) (ACI103)
SOLO-461: Thermal detector
test tool with battery (ACI104)
SOLO-424: 220V test tool SOLO-461
for thermal detectors (ACI105)
SOLO-200: Universal
extraction tool (ACI106)
SOLO-610: Tool bag for
accessories (ACI107)
SOLO-713: Accessory for
magnet (ACI713)

NOTIFIER ITALIA S.r.l. - A socio unico - 20097 San Donato Milanese (Ml) - Via Grandi, 22 - Tel.: 02/518971 - Fax: 02/5189730 - E-mail:
notifier@notifier.it Capitale Sociale € 2.700.000,00 i.v. - C.C.A.A. 1456164 - Trib. Milano Reg. Soc. 348608 - Vol. 8549 Fasc. 8 - Partita IVA
IT 11319700156 (informativa privacy art. 3 Digs 196/03) - Ufficl Regionali: 10151 Torino - Via Pianezza, 181 - Tel.: 011/4531193 - Fax: 011/4531183 -
E-mail: notifier.torino@notifier.it - 35010 Limena (PD) Via IV Novembre, 6/c Int. 9 - Tel.: 049/7663511 - Fax: 049/7663550 - E-mail:
notifier.padova@notifier.it - 40050 Funo di Argelato (BO) - Asta Servizi, Bl. 3B, Gall. B n. 85, Centergross - Tel.: 051/864855 - Fax: 051/6647638 - E-mail:
notifier.bologna@notifier.it - 50136 Firenze –Via Aretina, 167/M Tel/Fax: 055/289177 - 00118 Roma - Via Del Casale Santarelli, 51 - Tel.: 06/7988021 - SISTEMA GESTIONE
QUALITÀ CERTIFICATO
UNI EN ISO 9001:2000
Fax: 06/79880250 - E-mail: notifier.roma@notifier.it - 80143 Napoli - Palazzo Prof. Studi - Centre Direzionale, Isola G1, Scala D, Piano 15° - Tel.:
081/7879398 - Fax: 081/7879159- E-mail: notifier.napoli@notifier.it - 70125 Bari - Via Delia Costituente, 29 - Tel.: 080/5013247 - Fax: 080/5648114 - E-mail:
notifier.bari@notifier.it - 95126 Catania – Viale Alcide De Gasperi, 187 - Tel.: 095/7128993 - Fax: 095/7120753 - E-mail: notifier.catania@notifier.it
www.notifier.it

Tutti i dati sono soggetti a cambiamento senza preavviso. Tutti i diritti di questa pubblicazione sono riservati.

You might also like