You are on page 1of 2

HSE Observation Report

Date: 2-4-2020
Action required /
S. No Location Issues Photograph Rectification Close Out Photo
Recommendations

Observed Contractor need to Reference to the


Insufficient /
provide proper/ picture edge
1 A02-B Improper edge
sufficient edge protection has been
protection
protection to control provided .
the hazard

Observed that Contractor needs to ensure


excavation work that all excavation works Immediately hold the
2 Ground was going without must have a valid work activity inspect the area
Floor A05 valid work permit and issued the permit.
permit on lection

Observed that
Contractor need to ensure
operative is using
that plugs should be Plug of power tools
3 Ground Floor power tool without maintained for power tools have been maintained
A02 a plug inserting
cables .
cable directly in the
power socket
HSE Observation Report

Action required /
S. No Location Issues Photograph Rectification Close Out Photo
Recommendations

Repairing of toilets
Contractor need repair and
are in progress .Due In progress
A02, Level-1 Found toilets in maintain in a condition to
4 to current situation
broken condition use the toilets material not
available .

Contractor need to
It was observed
ensure that all vehicles
vehicle parked at Removed and parked in
5 Basement-1 should parked in designated area.
ramp at basement-1
designated parking
to basement-2
area only

Contractor need to
Observed Poor
maintained a good
A02 & A05 housekeeping at Proper housekeeping
6 housekeeping all over the
all over the has been done .
building premises
building area
(A02&A05)

Prepared by:
Mohammed Vajid ali