DETAILS
Project: 400/220 kV GSS AT JAISALMER (II) Sub-Station: 400/220 kV GSS, RRVPNL, JAISALMER (RJ.)
PROTECTION /
CORE RATIO CLASS BURDEN
METERING
Remove the connected earthing to system involving CT under test and disconnect the connected
terminals of CT marshalling box
PHASE
UNIT
CORE RØ YØ BØ
PRIMARY - CORE I GΩ 86.8 138 45.4
PRIMARY - CORE II GΩ 90.5 108 59.6
PRIMARY – EARTH GΩ 588 221 92.7
c) Check IR value between tan delta point and earth at 500V in secondary box
RØ YØ BØ
IV. POLARITY
PHASE
CORE BETWEEN
R -PHASE Y –PHASE B –PHASE
1S1 1S2 OK OK OK
CORE I 1S1 1S3 OK OK OK
1S1 1S4 OK OK OK
2S1 2S2 OK OK OK
CORE II 2S1 2S3 OK OK OK
2S1 2S4 OK OK OK
V. TAN DELTA AND CAPACITANCE MEASUREMENT
Make of testing kit : MEGGER (DELTA-4110)
Date of calibration : 07/04/2018 to 06/04/2019
Ambient temperature: 45°C
CAPACITANCE
TAN DELTA