SITE TEST REPORT SIEMENS

PRE-COMMISSIONING FORMATS FOR CURRENT TRANSFORMER

I. GENERAL DETAILS DATE OF TESTING – 16/11/2018

DETAILS

Project: 400/220 kV GSS AT JAISALMER (II) Sub-Station: 400/220 kV GSS, RRVPNL, JAISALMER (RJ.)

LOA No. : RVPN/SE(P&P)/XEN/kfw/ICB-1 D.1771 Dated:


Feeder name: 211 CT
16-10-2015

Make: MEHRU Type: MEHRU

Sr. No.: Year of Manufacture:


R Ø:- OC 6724/2/31/18 RØ:- 2018
Y Ø:- OC 6724/2/30/18 YØ:- 2018
BØ:- OC 6724/2/29/18 BØ:- 2018
Rating: 245/220 kV

II. RATED DATA AND DUTY

BURDE
CORE RATIO CLASS KVp & I max. PROTECTION /
N
METERING
4000-2000-1000
Winding I 2000-1000-500/1 PS - PROTECTION
30-60-120
4000-2000-1000
Winding II 2000-1000-500/1 PS - PROTECTION
30-60-120
Winding III 2000-1000-500/1 0.2S 20VA - METERING
2000-1000-500
Winding IV 2000-1000-500/1 PS - PROTECTION
30-60-120
2000-1000-500
Winding V 2000-1000-500/1 PS - PROTECTION
30-60-120

KVp : Knee Point Voltage In Volts

III. INSULATION RESISTANCE MEASUREMENT (Applied Voltage- 5 kV)

a) Insulation Resistance Measurement Primary to Secondary & Earth


(Using 5 kV Digital Megger)

Make of testing kit --: AGAM (AT501)


Date of calibration --: 13/09/2017 to 12/09/2018
Ambient temperature --: 44 deg. C

Format : 220 kV Current Transformer


Page 1 of 4
SITE TEST REPORT SIEMENS
Remove the connected earthing to system involving CT under test and disconnect the connected
terminals of CT marshalling box

PHASE
UNIT
CORE RØ YØ BØ
PRIMARY - CORE I GΩ 20 81 130
PRIMARY - CORE II GΩ 21 71 175
PRIMARY - CORE III GΩ 20 106 125
PRIMARY - CORE IV GΩ 21 81 128
PRIMARY - CORE V GΩ 19.8 53 132
PRIMARY – EARTH GΩ 523 601 497

b)Insulation Resistance Measurement between Secondary core to Earth


(Applied Voltage- 500 Volt)

PHASE
BETWEEN
UNIT RØ YØ BØ
 
SECONDARY CORE I - EARTH GΩ 10.0 9.9 8.7
SECONDARY CORE II - EARTH GΩ 10.1 9.6 8.4
SECONDARY CORE III – EA RTH GΩ 11.0 12.8 8.5
SECONDARY CORE IV - EARTH GΩ 10.0 12.0 8.7
SECONDARY CORE V - EARTH GΩ 12.0 12.0 8.3

c) Insulation Resistance Measurement between Secondary Core to Core


(Applied Voltage- 500 Volt)

PHASE
BETWEEN UNIT
RØ YØ BØ
CORE I - CORE II GΩ 13 16 8.2
CORE I - CORE III GΩ 10 14.1 8.4
CORE I - CORE IV GΩ 10 15.0 9.2
CORE I - CORE V GΩ 10 15.6 10.6
CORE II - CORE III GΩ 10 13 8.3
CORE II - CORE IV GΩ 10 21 8.3
CORE II - CORE V GΩ 12 16 9.4
CORE III - CORE IV GΩ 10 20 9.8
CORE III- CORE V GΩ 12 21 10.3
CORE IV - CORE V GΩ 12 20.7 10.3

d)Check IR value between tan delta point and earth at 500V in secondary box

RØ YØ BØ

>1GΩ >1GΩ >1GΩ

Format : 220 kV Current Transformer


Page 2 of 4
SITE TEST REPORT SIEMENS
IV. TAN DELTA AND CAPACITANCE MEASUREMENT
Make of testing kit : MEGGER (13850213)
Date of calibration : 07/04/2018 to 06/04/2019
Ambient temperature: 45°C
 
CAPACITANCE

PRE COMMISSIONING VALUES (in pF)


ACROSS STACK
R Ø YØ B Ø

2 kV 854.2 834.0 819.3


10 kV 854.1 834.1 819.4

TAN DELTA

ACROSS PRE COMMISSIONING VALUES


STACK
R Ø YØ B Ø
2 kV 0.176 0.177 0.176
10 kV 0.176 0.178 0.178

V. POLARITY
PHASE
CORE BETWEEN
R -PHASE Y –PHASE B –PHASE

1S1 1S2 OK OK OK
CORE I 1S1 1S3 OK OK OK
1S1 1S4 OK OK OK
2S1 2S2 OK OK OK
CORE II 2S1 2S3 OK OK OK
2S1 2S4 OK OK OK
3S1 3S2 OK OK OK
CORE III 3S1 3S3 OK OK OK
3S1 3S4 OK OK OK
4S1 4S2 OK OK OK
CORE IV 4S1 4S3 OK OK OK
4S1 4S4 OK OK OK
5S1 5S2 OK OK OK
CORE V 5S1 5S3 OK OK OK
5S1 5S4 OK OK OK

VI. NOTE-: WRM, MAGNETIZING CURVE (KNEE POINT) & RATIO TEST DONE BY CT
ANALYZER (OMICRON) KIT ALL RESULT ENCLOSED WITH THIS REPORT.

Format : 220 kV Current Transformer


Page 3 of 4
SITE TEST REPORT SIEMENS
Signature: Signature: Signature: Signature:
MPT & S , RRVPNL
OTEPL (Testing ) SIEMENS LTD. T & C , RRVPNL JAISALMER
JAISALMER

Format : 220 kV Current Transformer


Page 4 of 4