Professional Documents
Culture Documents
PSM
Hence, the IDMT OCR setting can be done if the PSM and TMS are
known. How to determine the PSM and TMS…?
• PSM desired pick-up current
• TMS desired operating time
= =
− ( × )
Previously, for the electromechanical relay, the setting of pick-up current was done by setting the Plug
Setting Multiplier (PSM). For instance as shown in the figure, the “plug” is attached to the value of 5,
which means that the pick-up current is set to be 5 times of rated current of secondary of CT.
Later on, the concept of PSM is also adopted by other types of relay, such as solid state relay and
numerical (microprocessor) relay, even though it does not physically use the plug.
≥ + ×
For example, a 3-phase motor rated of 1 MVA, 400 V is protected by an OCR. Then, the full load current is
,
= = 1,440 A, and the pick-up current will be = 100 + 15 × = 1,743 A.
Generally, in practice, the grading margin time interval used is between 0.30 to 0.50 seconds.
Rele-A
I , =5A
I , = 1.25 × 5 = 6.25 A
I , = × , = × 1400 = 70 A
Rele-B
I , =5A
I , = 1.25 × 5 = 6.25 A
I , = × , = × 1400 = 35 A
Rele-A Rele-B
I , =5 I , =5
I , = 6.25 I , = 6.25
I , = 70 I , = 35
, ,
, = = .
= . , = = .
= .
, ,
13
Rele-B Rele-A
= .6 = .
= . = .
Operating time = 1.1 s Operating time = 0.6 s
Hence, if the fault current occurred is 1400 A at the points as shown in the figure, then Relay-A will operate
within 0.6 s. If Relay-A fails to operate then Relay-B will operate as back-up within 1.1 s.
If, let say, the fault occurs between A and B, with the fault current is twice (2800 A), then Relay-B will
operate faster than 1.1 s, because 1.1 s is set for 1400 A fault current which means higher fault level will
cause the relay to operate faster.
FZN, Proteksi STL 14