LEGEND
A SYMBOL DESCRIPTION A
ECP
AC AC AC
L LCC (70 sq. mm Y/G COPPER CABLE)
480V AC 400/220V AC
B D
B
AC
D
D D DOOR EARTHING (70 sq mm Y/G COPPER CABLE)
ECP
A
B
BATTERY BANK-2
110VDC
B
AUX. TRAFO.
DC DC PANEL/BATTERY CHARGER(95 sq mm Y/G COPPER CABLE)
AT E04 E02
ECP
R
B
R B
P CONTROL ROOM PANELS (70 sq. mm Y/G COPPER CABLE)
B
D 415VAC
AC AC PANEL EARTHING (240 sq. mm STRANDED CONDUCTOR)
BATTERY BANK
PANEL
48VDC
D DC
CHR-1
110 VDC
DVR-1
DC
DVR-2
DC
CHR-2
110 VDC
DC
B BATTERY (95 sq mm Y/G COPPER CABLE)
P2
B
P
ECP
P6 ECP ECP EARTH CONNECTING POINT
BATTERY BANK-1 DC EOT EOT
CP-1
110VDC
DC
AT AUX. TRANSFORMER (95 sq mm Y/G COPPER CABLE)
110VDC SYSTEM
B
CP-2
ECP
DC
D
50 X 6 mm BARE COPPER TAPE
DC
CP-3
P
TRAFO.
AUX.
S 240 sq. mm Cu.STRANDED CONDUCTOR TO MAIN MESH
PANEL P
CP-4
EOT EOT
S S S
CP-5
C P
GIS HALL C
ECP
=E01 (=E05)
(=E06) =E05 =E04 =E03 =E02 =E01
D
EOT L L L L L L EOT
D
P ECP E.EXIT ECP
P8
RP-1
D
P
P3
TRAFO. SERGI PANEL
RP-2
P
L
P P P P
R
E05 B R B
A
Y Y
ECP ECP
D
D 48 VDC SYSTEM
P
D D
P
D
SECTION A-A NOTES
SCADA
SCADA PANEL
ECP
P
PLC-2 PLC-1
P
MDF
P
PABX
P
2. THE DRAWING SHALL BE REFLECTED ONLY FOR THE PURPOSE OF
EQUIPMENT EARTHING.
ECP P
panel panel
P
Metering Metering 3. 50 X 6 mm COPPER TAPE CONNECTED TO MAIN EARTHING MESH, VIDE 1C X
240 sq. mm CU STRANDED CONDUCTOR. MOREOVER ALL INDOOR EQUIPMENT
P HAVE BEEN GROUNDED VIDE Y/G INSULATED CU. CONDUCTOR.
Metering
panel
ECP
F F
H H
1 2 3 4 5 6 7 8 9 10