You are on page 1of 56

CARRIER TRANSICOLD

2013 Vector Unit


FOR NDK537

TRAILER REFRIGERATION UNITS

FOLLOW THE FLEET


HANDBOOK
Section One

Follow the Fleet Program


2013 EPA Compliant Trailer
FTF HANDBOOK

FOLLOW THE FLEET PLAN SUMMARY

TARGET FLEETS:
Varied

GOAL:
To obtain feedback regarding the quality, reliability, and performance of
the 2013 EPA compliant trailer refrigeration units operating in North America.

UNIT INSTALLATION, PRE-DELIVERY INSPECTION, AND CUSTOMER


PICK-UP:

Installation and Pre-Delivery Form


The standard trailer unit Pre-Delivery Form is included in this manual.
Upon completion of the inspection, send a copy of the completed Pre-Delivery
Form, and a data download from the microprocessor via E-Mail to Athens GA
Service Engineering:

Service.Engineering@carrier.utc.com

If it is not possible to e-mail a scanned copy of the pre-delivery form, please fax it
to 860-622-7352, ATTN: 2013 Trailer Team.

Customer Pick-up
A second E-Mail is to be sent to your Field Service Engineer to notify them
when the unit / trailer is picked up from your lot by the customer.

DATA COLLECTION METHODS:

Follow The Fleet Team Visits


2013 Trailer team members may periodically visit customers’ primary
service locations to collect customer & dealer feedback, inspect units, download
information from the units’ data recorders, and review unit maintenance and
service records. A portion of this group of FTF units will also be equipped with
PAR technologies data collection and cellular transmission.

Unit Inspections
Periodic unit inspections are to be conducted by the local Carrier
Transicold Dealer, Regional FSE and/or Customer.

Units that are equipped with the Par Communications System require only
quarterly (every 3 months) inspections.
1
Inspection forms are included in the 2013 Trailer FTF handbook to guide
the dealer through the inspection process. Completed inspection sheets should
be submitted to:

Carrier Transicold Service Engineering


Attn: Ken Shuart
service.engineering@carrier.utc.com
Fax 860-622-7352

Every effort should be made to complete unit inspections bi-monthly or


when the unit requires repair or maintenance.

Inspection Labor Allowance: 1.3 hours @ dealer standard rate


Warranty Filing: Claims submitted for labor inspection need
to be marked for “2013 Trailer Unit Field
Trial”

The timely submittal of fully completed inspection reports is critical to the


success of the Field Trial, to consider product release is solely the responsibility
of the quality of reporting from the FSE’s. Failure to properly submit inspection
reports, per the schedule of expectation, can result in product release delay,
and/or cancellation of the project

Incident / Feedback Reports


Incident / Feedback reports should be submitted by the customer or
Carrier Transicold dealer to report any unit problems, concerns, or repairs.
Warranty Filing: All Claims submitted for unit repairs or
maintenance need to be marked for “2013
Trailer Unit Field Trial”

Datarecorder Data
All 2013 compliant units in the target fleets will be equipped with
datarecorder capability. Datarecorder data is to be downloaded from these units
by the customer or Carrier Transicold dealer whenever unit repairs are made.
Downloads should be emailed to ken.shuart@carrier.utc.com

FOLLOW THE FLEET REVIEW:

The 2013 EPA Compliant Trailer Follow the Fleet team will conduct a
review of the unit data monthly and will plan future follow up visits to 2013 EPA
Compliant Trailer FTF customers and dealers. After approximately one year in
service, a Follow the Fleet review board will be conducted during which all 2013
EPA Compliant Trailer FTF data, warranty & failure data, and active corrective
action items will be summarized and presented.

2
2013 TRAILER FOLLOW THE FLEET TEAM
MEMBERS
CONTACT POSITION PHONE FAX
NAME
*Ken Shuart Service Engineering 800-448-1661 860-998-4089
Athens, GA
Bill Maddox Service Engineering 800-448-1661 860-998-2762
Athens, GA
David Goodhew Field Service Eng. Mgr 706-355-5476 860-998-2795
Athens, GA
Kevin Williams Trailer Product Manager 706-357-7217 706-355-5435
Athens, GA
Mitch Mattison Service Parts 315-432-6193 860-998-1087
Syracuse, NY
Roger Redmond Project Leader 315-432-3750 860-998-1412
Syracuse, NY
Mike Balistreri Engineering 315-432-7184 860-998-4599
Syracuse, NY
* PRIMARY CONTACT

IMPORTANT:
Please report all incidents of repair work, unit problems, concerns, and
comments to one of the above team members. Fax copies of completed
inspection sheets, incident reports, and repair work orders to Ken Shuart.

Remember to include the following in any correspondence:


Unit Model Number
Unit Serial Number
Unit Hours at incident
Application (Frozen, Perishable, Mixed)
Description of incident / problem / concern
Section Two

Unit Operation
9
NEW COMPONENT DESCRIPTIONS Liquid Injection Solenoid Valve (LIV)

Compressor The LIV is opened, during periods high compressor dis-


charge temperature to inject refrigerant into the eco-
The unit is fitted with a scroll compressor equipped with nomizer connection to cool the compressor. It is located
suction and discharge service valves and an econom- at the front of the economizer.
izer connection. The compressor draws refrigerant gas
from the evaporator and delivers it to the condenser at Economizer Circuit
an increased temperature and pressure. The pressure The economizer circuit consist of a compact braze plate
is such that refrigerant heat can be absorbed by the heat exchanger (item NO TAG, NO TAG) and the eco-
surrounding air at ambient temperatures. nomizer expansion valve (item NO TAG = ECXV). Both
are located above the compressor.
Compressor Switches, Transducers and Sensors In the economized mode, the frozen and pull down ca-
a. Compressor Discharge Pressure Transducer pacity of the unit is increased by subcooling the liquid
(CDP) refrigerant entering the evaporator expansion valve.
Overall efficiency is increased because the gas leaving
The CDP provides a signal to the control system the economizer enters the compressor at a higher pres-
equivalent to pressure leaving the compressor. The sure, therefore requiring less energy to compress it to
reading is displayed, recorded in the DataLink data the required condensing conditions.
recorder and used to control the refrigeration system. It
is located in the discharge line leaving the compressor. To place the unit in the economized mode, the control
system energizes (opens) the ECXV. The ECXV con-
b. Compressor Suction Pressure Transducer trols the flow of liquid from the main liquid line through
(CSP)
the economizer according to changes in superheat of
The CSP provides a signal to the control system the refrigerant leaving the economizer.
equivalent to pressure entering the compressor. The
reading is displayed, recorded in the DataLink data 2.1.1 Economizer Transducer and Sensor
recorder and used to control the refrigeration system. It a. Economizer Outlet Pressure Transducer
is located in the suction service valve. (ECOP)
c. Compressor Discharge Temperature Sensor The ECOP is located in the suction line leaving the
(CDT) economizer. It provides the control system with eco-
The CDT provides a signal to the control system nomizer outlet pressure information to be displayed,
equivalent to the temperature of the gas leaving the recorded in the DataLink data recorder and used to
compressor. The reading is displayed, recorded in the determine the required position of the economizer ex-
DataLink data recorder and used to control the pansion valve.
refrigeration system. It is located on the compressor b. Economizer Outlet Temperature Sensor (ECOT)
head.
The EVOT is located on the suction line leaving the
d. Compressor Suction Temperature Sensor (CST) economizer. It provides the control system with eco-
The CST provides a signal to the control system nomizer outlet temperature information to be displayed,
equivalent to to the temperature of the gas entering the recorded in the DataLink data recorder and used to
compressor suction service valve. It is located on the determine the required position of the economizer ex-
line entering the valve. pansion valve.

Model NDK(ST) Refrigerant Diagram 5/31


REFRIGERANT CIRCUIT DURING COOLING superheat. The vapor then returns to the compressor
through the compressor suction modulation valve
When cooling, the unit operates as a vapor compression (CSMV). The CSMV controls the flow of refrigerant
refrigeration system. The main components of the entering the suction line, thereby matching the load to
system are: the (1) scroll compressor, (2) air-cooled the compressor capacity.
condenser, (3) evaporator expansion valve, (4) direct b. Economized Mode
expansion evaporator and (5) economizer circuit.
In the economized mode the “main” refrigeration system
The refrigeration system will operate in one of three operates the same as in the Standard Mode except the
modes; Standard, Economized or Null. In addition, the control system operates (opens) the economizer
system may also operate in Liquid Injection mode. expansion valve (ECXV). With the economizer
expansion valve operating (see Figure 2), the capacity
At start, and during periods of high refrigeration system
of the unit is increased by subcooling the liquid
load, the system will operate in the standard mode. This
refrigerant entering the evaporator expansion valve.
allows the control system to place the unit in operation at
reduced capacity and measure the actual load. If the Liquid refrigerant for use in the economizer circuit is
microprocessor calculates addition capacity is required taken from the main liquid line as it leaves the filter drier.
and power is available (such as periods of high load or This liquid refrigerant flows through the economizer
during pull--down), the system will transition to expansion valve (ECXV) and the economizer heat
economized mode. exchanger internal passages absorbing heat from the
liquid refrigerant flowing to the evaporator expansion
a. Standard Mode valve. Overall efficiency is increased because the gas
In standard mode, (see Figure 1), the compressor leaving the economizer enters the compressor at a
raises the pressure and the temperature of the higher pressure, therefore requiring less energy to
refrigerant and forces it into the condenser channels. compress it to the required condensing conditions.
The condenser fans circulate surrounding air over the
c. Null Mode
outside of the condenser. The channels have fins
designed to improve the transfer of heat from the The system will enter null mode during periods where no
refrigerant gas to the air. This removal of heat causes cooling or heating is required and the system is in con-
the refrigerant to liquify. Liquid refrigerant leaves the tinuous run. In null mode the compressor and heaters
condenser and flows to the receiver. are shut down while the evaporator fans continue to op-
erate. The condenser fan will operate if engine cooling is
The receiver stores the additional charge necessary for required.
low ambient operation. The receiver is equipped with a The system may also enter the null mode while in start
fusible plug. stop if required time, coolant temperature or battery
The refrigerant leaves the receiver and flows through condition parameters have not been met.
the liquid line service valve to the subcooler. The d. Liquid Injection Mode
subcooler occupies a portion of the main condensing
The control system monitors the signal provided by the
coil surface and gives off further heat to the passing air.
compressor discharge temperature sensor. If com-
The refrigerant then flows through a filter-drier where an pressor temperature rises to the limit (refer to section
absorbent keeps the refrigerant clean and dry. 2.10), the system will enter Liquid Injection Mode. In this
mode the normally closed liquid injection valve (LIV) will
The liquid then flows to an evaporator expansion valve be pulsed or opened as required to allow flow of refriger-
(EVXV) which reduces the pressure of the liquid and ant into the economizer line, to cool the compressor.
meters the flow of liquid refrigerant to the evaporator to
obtain maximum use of the evaporator heat transfer HEAT AND DEFROST
surface.
The refrigerant pressure drop caused by the expansion In the Heat and Defrost Modes, the compressor is
valve is accompanied by a drop in temperature so the de--energized. In Heat Mode, the coil mounted heaters
low pressure, low temperature liquid that flows into the and evaporator fans are energized. Air flowing over the
evaporator tubes is colder than the air that is circulated warm coil is circulated throughout the refrigerated
over the evaporator tubes by the evaporator fan. The compartment to maintain the cargo at the desired
evaporator tubes have aluminum fins to increase heat temperature.
transfer; therefore heat is removed from the air
circulated over the evaporator. This cold air is circulated If the control system is Configured to allow Natural
throughout the refrigerated compartment to maintain Defrost, and the compartment temperature is above
the cargo at the desired temperature. freezing defrost may be accomplished using a
combination of coil heaters and return air.
The transfer of heat from the air to the low temperature
liquid refrigerant causes the liquid to vaporize.
If compartment temperature is below freezing or not
This low temperature, low pressure vapor passes the sufficiently warm enough to defrost the coil, the
evaporator outlet temperature and pressure sensors evaporator fans are de--energized and the coil mounted
(EVOT and EVOP) which aid in calculation of heaters energized.

Model NDK(ST) Refrigerant Diagram 5/31


9

DISCHARGEFOLW
LIQUID FLOW
SUCTION FLOW EVOT EVOP
MM
EVAPORATOR

EVXV

DISTRIBUTOR

CONDENSER
FUSIBLE
PLUG

RECEIVER
SUBCOOLER

FILTER DRIER
COMPRESSOR LIQUID LINE
DISCHARGE SERVICE VALVE
SERVICE VALVE CDP ECONOMIZER

CDT

CSMV
LIV N/C

ECOP
CST ECXV

COMPRESSOR CSP MM
SUCTION ECONOMIZER
CONNECTION ECOT
SERVICE VALVE
COMPRESSOR

Figure 1. Refrigerant Circuit Standard Mode

Model NDK(ST) Refrigerant Diagram 5/31


DISCHARGEFOLW
LIQUID FLOW
SUCTION FLOW
ECONOMIZER LIQUID FLOW
ECONOMIZER SUCTION FLOW EVOT EVOP
MM
EVAPORATOR

EVXV

DISTRIBUTOR

CONDENSER

FUSIBLE
PLUG

RECEIVER
SUBCOOLER

FILTER DRIER
LIQUID LINE
COMPRESSOR
SERVICE VALVE
DISCHARGE
SERVICE VALVE CDP ECONOMIZER

CDT

CSMV
LIV N/C

ECOP
CST ECXV

COMPRESSOR MM
LIQUID
SUCTION INJECTION LINE ECOT
SERVICE VALVE
CSP
COMPRESSOR
ECONOMIZER
CONNECTION

Figure 2. Refrigerant Circuit Economized Mode

Model NDK(ST) Refrigerant Diagram 5/31


Operating Instructions
Operating instructions for the NDK units may be found in the Operator’s Manual for X2
Series Trailer & Rail Refrigeration Units With APX Control System, Manual 62-11547,
with the exception of instructions on placing the unit in Standby Operation or Engine
Operation. Those instructions are provided in the following pages.

Trailer & Rail Refrigeration

ALARM

START/STOP

CONTINUOUS

DEFROST

MENU

I START/RUN

O OFF

OPERATOR’S MANUAL
for

X2 SERIES
Trailer & Rail Refrigeration Units
TM

With APX Control System

62-11547 Rev-

This manual may be found in the Information Center on TransCentral or ordered on the
Publications Shopping Cart.

NOTE: The cooling system capacity listed in the 62-11547 manual as 2.0
gallons for the X2 series units increases to 2.9 gallons for the NDK (X4)
units. Also, additional fuses in the Power Control manual may be found in
Section 4 of this Follow The Fleet Handbook.

Model NDK (ST) Operating Instructions 6/5


STARTING -- ENGINE OPERATION

WARNING
Be aware of HIGH VOLTAGE supplied at the power plug or from the generator. When per-
forming service or maintenance procedures: ensure any two way communication is dis-
abled in accordance with the manufacturer’s instructions, ensure the START/RUN-OFF
switch is in the OFF position and, whenever practical, disconnect the high voltage
source, lockout/tagout the receptacle and disconnect the negative battery connection.

WARNING

Under no circumstances should ether or any other starting aids be used to start the engine.

3
ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

2
36 .2
DEFROST

MENU
BOX TEMPERATURE °F
36
SETPOINT °F

STATUS OK 1

4
I START/RUN

O OFF

1. Place the START/RUN-OFF switch in the START/RUN position. Observe the status bar if “DIESEL” is
displayed, continue with step 3. If “ELECTRIC” is displayed, return the START/RUN-OFF to the “OFF”
position. Ensure the external power circuit breaker is off and disconnect the standby cable from the unit,
if required .
2. Place the START/RUN-OFF switch in the START/RUN position and press the “MENU” key until the
“STANDBY” soft key is displayed. Press the “STANDBY” key, the “STANDBY & DIESEL” soft keys will
display. Press the “DIESEL” soft key to place the unit in Engine Operation and then press the “EXIT’ key.
3. The system will display the Carrier Transicold logo, display the default screen, present language selec-
tion and the hour meter readings (if configured to do so) along with a test flash of the alarm light and light
bar amber LED’s. The system will then perform a start sequence, energize the buzzer, and then start the
unit automatically. NOTE: If the compressor has been off for more than 2 hours, it may cycle, one second
on -- nine seconds off, up to five times before entering steady state operation.
4. If there is an alarm present, the alarm message will be displayed in the MessageCenter and the alarm
LED will flash for 5 seconds. If one or more shutdown alarms are present, the alarm(s) must be cleared
before the unit will start.
5. Observe the MessageCenter. If the word “ACTIVE” or “MODIFIED” is displayed at the right, the unit is
equipped with IntelliSet settings. Proceed to page 4. If “ACTIVE” or “MODIFIED” is not displayed, pro-
ceed to page 6.
6. If the LCD Display does not illuminate, check:
S Battery voltage. A booster battery may be needed.
S Check for blown fuse(s).
S Verify the harness connector at the back of the display module is securely attached.
S Check CAN connections at the main microprocessor module and SMV module.

Model NDK (ST) Operating Instructions 6/5


STARTING -- STANDBY OPERATION

WARNING
Be aware of HIGH VOLTAGE supplied at the power plug or from the generator. When per-
forming service or maintenance procedures: ensure any two way communication is dis-
abled in accordance with the manufacturer’s instructions, ensure the START/RUN-OFF
switch is in the OFF position and, whenever practical, disconnect the high voltage
source, lockout/tagout the receptacle and disconnect the negative battery connection.

WARNING

Ensure the power plug is clean and dry before connecting to any electrical outlet/receptacle.
Do not connect power plug to any electrical outlet without checking that it meets the
460/3/60 and 30 amp electrical requirements of the unit.
4
ALARM

START/STOP

START/STOP ELECTRIC COOL


CONTINUOUS

36 .2
DEFROST
2
MENU
BOX TEMPERATURE °F
36
SETPOINT °F

STATUS OK 1

5
I START/RUN

O OFF

1. Ensure the START/RUN-OFF switch in the OFF position. Ensure the external power circuit breaker is off,
connect the standby cable and turn the external circuit breaker on. Place the START/RUN-OFF switch in
the START/RUN position. Observe the status bar if “ELECTRIC” is displayed, continue with step 3. If
“DIESEL” is displayed, continue with step 2.
2. Press the “MENU” key until the “STANDBY” soft key is displayed. Press the “STANDBY” key, the
“STANDBY & DIESEL” soft keys will display. Press the “STANDBY” soft key to place the unit in Standby
Operation and then press the “EXIT’ key.
3. The system will display the Carrier Transicold logo, display the default screen, present language selec-
tion and the hour meter readings (if configured to do so) along with a test flash of the alarm light and light
bar amber LED’s. The system will then perform a start sequence, energize the buzzer, and then start the
unit automatically. NOTE: If the compressor has been off for more than 2 hours, it may cycle, one second
on -- nine seconds off, up to five times before entering steady state operation.
4. If there is an alarm present, the alarm message will be displayed in the MessageCenter and the alarm
LED will flash for 5 seconds. If one or more shutdown alarms are present, the alarm(s) must be cleared
before the unit will start.
5. Observe the MessageCenter. If the word “ACTIVE” or “MODIFIED” is displayed at the right, the unit is
equipped with IntelliSet settings, follow IntelliSet operating instructions. If “ACTIVE” or “MODIFIED” is
not displayed, enter set point and other operational settings as required.
6. If the LCD Display does not illuminate, check:
S Battery voltage. A booster battery may be needed.
S Check for blown fuse(s).
S Verify the harness connector at the back of the display module is securely attached.
S Check CAN connections at the main microprocessor module and SMV module.

Model NDK (ST) Operating Instructions 6/5


Section Three

Wiring Information
HARNESS CONNECTOR WIRING

NOTE
All illustrations provided in this Section are looking at the connector connection end (with the wires in the back).

PCM -- WHITE 1MM -- BLACK

12 1 3 1

35 24 8 6

Component Terminal
PCM--19 1
Component Terminal
HVB7--C 2
SP--25 3
SP--15 3
SATPWR--B 6
HVB7--D 4
LB--B 7
PCM--32 6
3MM--34 8
SP--16 8
3MM--23 9
Unused terminals: 5 & 7
HVB7--E 10
PCM--35 13
SP--25 14
SP--23 15
3MM--18 16
3MM--17 17
SP--17 18
1MM--1 19
FLS--A 22
3MM--15 23
AFAS--A (F6--A) 24
3MM--13 26
3MM--14 27
3MM--28 28
PCM--12 29
1MM--6 32
SP--18 34
PCM--13 35
Unused terminals: 1, 2, 4, 5, 11, 12, 20, 21, 25, 30,
31& 33

Model NDK(ST) Connectors 6/19


HARNESS CONNECTOR WIRING -- Continued

2MM -- BLACK 3MM -- GRAY

12 1 12 1

35 24 35 24

Component Terminal Component Terminal


AAT--B 1 LIV--1 5
AAT--A 2 LB--H 7
DP16--G 3 ENCU--44 9
DP16--H 4 FP+ 10
DP16--C 5 SS--A 12
DP16--D 6 PCM--26 13
DP16--E 7 PCM--27 14
CDT--B 8 PCM--23 15
CSP--3 9 SP23 16
CDP--3 10 PCM--17 17
DP16--B 11 PCM--16 18
PCM--29 12 DAS+ 19
FLS--C 13 PCM--9 23
ECOP--3 14 PCM--28 28
ECOT--B 15 DAS-- (negative) 29
CST--B 16 PCM--8 34
DP16--S 17 Unused terminals: 1 Through 4, 6, 10, 11, 20, 21,
DP16--F 18 22, 24 Through 27, 30 Through 33 & 35
CDT--A 19
CSP--1 20
CDP--1 21
DP16--A 22
PCM--30 23
FLS--B 24
DP16--P 25
ECOT--A 26
CST--A 27
ECOP--1 28
PCM--31 29
SP--20 30
SP--24 35
Unused terminals: 31, 32, 33 & 34

Model NDK(ST) Connectors 6/19


HARNESS CONNECTOR WIRING -- Continued

1SVM -- BLACK 2SVM -- BLUE

3 1
12 1

8 6
35 24

Component Terminal
SP--15 1
DM--2 2 Component Terminal
DM--1 3 CSMV--A 2
DM--6 4 CSMV--B 3
SP--13 5 CSMV--C 4
SP--16 6 CSMV--D 5
SP--14 7 DP16--H 6
DM--10 8 DP16--N 7
Unused terminals: None DP16--K 8
DP16--L 9
DP16--M 10
SP--17 11
DS--A 13
REM--A* 14
REM--C* 15
SP--18 22
DS--B 24
REM--B* 25
REM--D* 26
Unused terminals: 1, 12, 16 Through 21, 23, 27
Through 35
*REM--A & REM--B connect to REMS1
REMC & REMD connect to REMS2

Model NDK(ST) Connectors 6/19


HARNESS CONNECTOR WIRING -- Continued

3SVM -- BLUE DM -- BLACK

12 1
5 1

35 24
14 10

Component Terminal
Component Terminal
ECXV--E 1
ECXV--A 2 1SVM--3 1
ECXV--B 3 1SVM--2 2
ECXV--C 4 SATCOM--B 3
ECXV--D 5 1SVM--4 6
SP--17 11 HVB7--K 7
SP--18 22
SATCOM--C 8
3SVM--32 31
1SVM--8 10
3SVM--31 32
SATCOM--A 12
Unused terminals: 6 Through 10, 12 Through 21,23
Through 30, 33, 34 & 35 Unused terminals: 4,5,6,9,13,14

Model NDK(ST) Connectors 6/19


HARNESS CONNECTOR WIRING -- Continued

ENCU REM
K F
1 23

A E
Harness Connector Shown

From Terminal To
(Component)
2SVM--14 A REMS1
2SVM--25 B REMS1
2SVM--15 C REMS2
22 44
2SVM--26 D REMS2
HVB8--A E REMSN--1
SP--26 F REMSN--1
HVB8--B G GHT (If Equipped)
Component Terminal SP--26 H GHT (If Equipped)
ENCT--B 1 Unused Terminals: None
ENSSN--2 2
ENCT--A 6
RPS--3 7
ENOPS--A 15
ENOPS--B 18
PCM--T2 19
ENSSN--1 20
SM 21
SP--18 22
SP--13 23
SP--14 24
SP--27 (With MAP)
27
RPS--2 (Without MAP)
MAP--3 (If Equipped) 28
SP--28 (With MAP)
29
RPS--1 (Without MAP)
FSA--1 36
FSA--2 41
ENSSN--3 43
3MM--9 44
Unused Terminals: 3, 4, 5, 8 Through 14, 16, 17,
25, 26, 30 Through 35, 37 Through 40 & 42

Model NDK(ST) Connectors 6/19


HARNESS CONNECTOR WIRING -- Continued

HVB7 DP16
K F
A H

J S
A E
Engine Harness Connector Shown

From Terminal From Terminal To


SP--15 A (Evaporator
Component)
SP--16 B
2MM--22 A 1DTT--B
1MM--2 C
2MM--11 B 1DTT--A
1MM--4 D
2MM--5 C 1SAT--A
PCM--10 E
2MM--6 D 1SAT--B
J1--A F
2MM--7 E EVOT--A
SP--14 G
2MM--18 F EVOT--B
SP--13 H
2MM--3 G 1RAT--A
SP--10 J
2MM--4 H 1RAT--B
DM--7 K
2SVM--7 J EVXV--A
Unused Terminals: None
2SVM--8 K EVXV--B
2SVM--9 L EVXV--C
HVB8 2SVM--10 M EVXV--D
2SVM--6 N EVXV--E
2MM--25 P EVOP--1
SP--20 R EVOP--2
C A 2MM--17 S EVOP--3
Unused Terminals: None

F D

From Terminal
REM--E A
REM--G B
IAT--A C
SP--26 D
Unused Terminals: E & F

Model NDK(ST) Connectors 6/19


SPLICE POINTS
Splice Point No. Component Splice Point No. Component
GND1--RING1 ENCU--27
27
SATPWR--A (MAP Ground -- If MAP--1
LIV--2 Equipped) RPS--2
10 FP-- (negative) ENCU--29
(Ground) 28
LB--G (MAP Power -- If MAP--2
FH--B Equipped) RPS--1
AFAS--B
1SVM--5
13 HVB7--H
(CAN HI)
ENCU--23
1SVM--7
14 HVB7--G
(CAN LO)
ENCU--24
1MM--3
15 HVB7--A
(Ground)
1SVM--1
1MM--8
16 1SVM--6
(Power)
HVB7--B
PCM--18
17 2SVM--11
(Ground)
3SVM--11
PCM--34
18 2SVM--22
(Power) 3SVM--22
ENCU--22
CSP--2
20 ECOP--2
(+5V power) CDP--2
DP16--R
PCM--15
23 HPS--A
(Power)
3MM--16
2MM--35
24 HPS--B
(Power)
J1--B
FH--A
25 PCM--14
(Power)
PCM--3
HVB8--D
26 REM--F
(+3V Power) REM--H
IAT--B

Model NDK(ST) Connectors 6/19


Section Four

Component Identification
9

1 2 3

24

23
22

21

20

19
18
17
16

15

14

13
10,11,12
9
8 4

5,6,7

1. Condenser Fans and Motors (CDM1 & CDM2) 12. Compressor Discharge Pressure
2. Ambient Air Temperature Sensor (AAT) Transducer (CDP - Located in discharge line)
3. Condenser 13. Compressor Suction Temperature Sensor (CST)
4. Model/Serial Number Nameplate 14. Economizer Outlet Temperature Sensor (ECOT)
5. Compressor (C) 15. Compressor Suction Modulation Valve (CSMV)
6. Compressor Junction Box 16. Liquid Injection Valve (LIV)
(At rear of compressor) 17. Economizer Expansion Valve (ECXV)
7. Compressor Discharge Temperature 18. Economizer Outlet pressure
Sensor (CDT --Located on compressor head) Transducer (ECOP)
8. Compressor Suction Service Valve 19. Economizer
9. Compressor Suction Pressure 20. Liquid Line Service Valve
Transducer (CSP) 21. Filter-Drier
10. Compressor Discharge Service Valve 22. Receiver Sight Glasses
11. High Pressure Switch (HPS - Located 23. Receiver
in service valve) 24. Defrost Air Switch (DAS)
Figure 1 Front View - Refrigeration System Components

Model NDK(ST) Component Identification 6/19


1
35

34

33

3
32 4
5
31 6

7
30 8

29 9
10

11
28
12
13
27 25 20 18 14
26 22 17 15
23,24 21 19 16

1. Coolant Bottle 21. Engine Oil Drain


2. Fuel Filter/Heater (FH)/Switch (FHTS) 22. Starter (SS,SSC,SM)
3. Exhaust 23. Engine Preheater (EPH)
4. Standby Box (See Figure 4) 24. Engine Coolant Temperature Sensor (ENCT)
5 Control Box (See Figure 4) (Behind Engine Preheater)
6. Bleed Valve 25. Generator (GEN)
7. Manual Plunger 26. Generator Temperature Sensor (GHT -- If
8. Fuel/Speed Actuator (FSA) Equipped)
9. Engine Speed Sensor (ENSSN) 27. Intake Air Temperature Sensor
10. Stepper Valve Module (SVM) ( IAT -- If Equipped)
11. Display Module (DM) 28. Battery (BTY)
12. START/RUN-OFF Switch (SROS) 29. Power Control Module (PCM - See Figure 5)
13. USB Interface Port 30. Main Microprocessor Module (MM)
14. Engine Oil Pressure Switch (ENOPS) 31. Air Cleaner, Air Cleaner Service Indicator &
15. Engine Control Unit (ENCU) Manifold Absolute Pressure Transducer
16. Power Supply Receptacle (PSR) (MAP -- If Equipped)
17. Engine Oil Filter 32. Battery Charger (BTYC, BTYC2)
18. Mechanical Fuel Pump 33. AutoFresh Air Exchange
19. Engine Oil Fill & Dipstick 34. AutoFresh Air Exchange Solenoid (AFAS)
20. Rack Position Sensor (RPS) 35. Radiator
Figure 2 Front View - Engine, Control System & AutoFresh Components

Model NDK(ST) Component Identification 6/19


9

1 2 3 4 5 6 7 8 9

16 13 12 11 10

15
14

1. Evaporator Coil 11. Drain Pan Heater (HTR1)


2. Evaporator High Temperature Switch* (EVHTS) 12. Defrost Heaters (HTR1 & 2)
3. Supply Air Temperature Sensor (1SAT) 13. Return Air Temperature Sensor (1RAT)
4. Evaporator Fan Motor Wiring 14. EVXV Inlet Strainer Location
5. Evaporator Air Nozzle 15. Evaporator Outlet Pressure Transducer (EVOP)
6. Evaporator Fan & Motor Assembly (EVM) and Evaporator Outlet Temperature
7. Low Pressure Defrost Air Switch Tubing (Clear) Sensor (EVOT)
8. High Pressure Defrost Air Switch Tubing (Red) 16. Evaporator Expansion Valve (EVXV)
9. Defrost Termination Temperature
Sensor* (1DTT) *Located on tubesheet
10. High Pressure Air Switch Fitting
Figure 3 Evaporator Section - Grille Removed

Model NDK(ST) Component Identification 6/19


CONTROL BOX
1 2 3 4 5

6
24 7
23
22 8

21 9
10
11
STANDBY BOX 20
12
19

13
18

17 16 15 14

1. Condenser Motor Contactor (CDCON1) 14. Generator Contactor (GENCON)


2. Condenser Motor Contactor (CDCON2) 15. Compressor Contactor (CCON)
3. Evaporator Motor Contactor (1EVCON) 16. High Voltage Transformer (HVT)
4. Heat Contactor 1 (1HTCON1) 17. Ground Plate (PE)
5. Heat Contactor 2 (1HTCON2) 18. Power Supply Contactor 2 (PSCON2)
6. Fuse (F41) 19. Power Supply Contactor (PSCON)
7. Fuse (F40) 20. Overload Ground Fault (OGF)
8. Fuse (F39) 21. Contactor Control Board 1 (1CCB)
9. Fuse (F38) 22. Fuse (F35)
10. Fuse (F37) 23. Fuse (F34)
11. Fuse (F36) 24. Fuse (F33)
12. Contactor Control Board 2 (2CCB)
13. AC Current Sensor (CT2,3,4)
Figure 4 Control and Standby Boxes

Model NDK(ST) Component Identification 6/19


9

19

2 18
F8 17
F1
F9
3 K1 16
F10 15
F3
F11
F12
4 F5 14
K2
5 F14
6
7 K3

8
F7

13
9

10 12

11 F6 (10 amp) located in the white wire at the autofresh air


exchange solenoid, just past the harness connector.

1. Fuse (F5 = 30 amp), Power Enable Relay 10. Battery Negative Connection (T2)
2. Fuse (F1 = 5 amp), Main Microprocessor/ 11. Fuse (F6), AutoFresh Air Exchange
Buzzer Power 12. Alternator Output Connection (T3)
3. Fuse (F3 = 5 amp), 2 & 3 SVM/Engine 13. Engine Preheater Power Connection (T4)
Control Unit Power 14. Fuse (F14 = 15 amp), Fuel Heater
4. Relay, Power Enable (PER) 15. Fuse (F12 = 5 amp), Satellite Communications
5. Relay, Fuel Heater (FHR) Power
6. Buzzer (B) 16. Fuse (F11 = 5 amp), Light Bar
7. Relay, AutoFresh Air Exchanger (AFAR) 17. Fuse (F10 = 20 amp), Relay Power
8. Fuse (F7 = 80 amp) Main Power 18. Fuse (F9 = 5 amp), CCB Power
9. Battery Positive Connection (T1) 19. Fuse (F8 = 5 amp), Fuel Level Sensor
Figure 5 Power Control Module

Model NDK(ST) Component Identification 6/19


5 6 7 8 9

4 ALARM

START/STOP

START/STOP DIESEL COOL


CONTINUOUS

36 .2
3 DEFROST

36
MENU

2 BOX TEMPERATURE °F SETPOINT °F


STATUS OK

10

I START/RUN

O OFF

13 12 11

1. LCD Display 8. “=” (Select) Key


2 MENU Key 9. Arrow Keys
3. DEFROST Key 10. MessageCenter
4. START/STOP - CONTINUOUS Key 11. START/RUN-OFF Switch
5. Status Bar 12. Soft Keys
6. Alarm LED 13. USB Interface Port
7. ALARM Key
Figure 6 Display Module

Model NDK(ST) Component Identification 6/19


Section Five

Troubleshooting
Section Six

Service Procedures
Compressor e. Disconnect the compressor discharge temperature
sensor (CDT) connector. The replacement com-
pressor comes with the compressor discharge tem-
perature sensor already assembled.
WARNING f. Remove and save the compressor base--mounting
bolts and spacers.
Before removal of the compressor, relieve
the internal pressure by very carefully loos- g. Rotate the compressor to gain access to the power
ening the connections to break the seal. plug. Remove the power plug retaining clip (see
Figure 2) by pulling out gently on the sides (to clear
the locking tabs) and then slide up and off the plug.
Pull the plug out and away from the compressor to
CAUTION remove.

The scroll compressor achieves low suc-


tion pressure very quickly. Do not use the 1
compressor to evacuate the system below
0 psig. Never operate the compressor with 2
the suction or discharge service valves
closed (frontseated). Internal damage will
result from operating the compressor in a 4
deep vacuum.

7 3
6
5

1. Retainer 3. Cable
8 2. Tether 4. D--Ring (Seal)

Figure 2. Compressor Plug Retainer


4
NOTE
Inspect the power plug terminals to ensure they
are not deformed or have any signs of heat or
9 3 arcing. If any damage is noted, replace the
power cable.
h. Remove (slide out) the old compressor from the unit
and slide the new compressor into the unit. Refer to
Figure 1.
NOTE
1 2 DO NOT add any oil to the replacement com-
pressor. Replacement compressor is shipped
1. Mounting Hardware 7. Discharge with full oil charge.
2. Compressor Connection i.. Install the “D--ring” into the square groove of the
3. Suction Connection 8. Power Plug power plug
4. Economizer (Back Side) j. Inject a small amount of lubricant (shipped with the
Connection 9. Oil Level Adjustment replacement compressor into each of the pin con-
5. Lifting Lug Port (replacement nections in the power plug. For ease of installation
6. Discharge compressors only). and to prevent the “D” ring from rolling, use a small
Temperature Sensor amount of the lubricant to lubricate the outside radius
of the “D” ring.
Figure 1. Compressor Kit k. Insert the power plug at a slight angle allowing the
“D” ring to start at the lower portion of the terminal
a. Remove the refrigerant charge. fence. Apply even pressure on the back of the power
b. Ensure the unit is disconnected from the power plug until the flat surface of the plug seats against the
source and that SROS is in the OFF position. outer face of the terminal fence.
c. Frontseat the discharge and suction service valves l. Reinstall the retainer.
to help protect the remainder of the system. m. Install the four base--mounting bolts and spacers
d. Remove the fittings from the suction and discharge loosely.
service connections, and uncouple the economizer n. Using new seals/O--ring, lubricate the seals/O--ring,
line from the compressor. back side of sleeves and coupling nuts with com-

Model NDK(ST) Unique Service Procedures 6/6


pressor oil and put in place. Hand tighten all three r. Backseat the suction and discharge service valves.
connections. Leak check, evacuate the unit and charge.

o. Torque mounting bolts to 50 +/-- 3 ft--lbs (68 +/-- 18


Nm). CAUTION
p. Using a backup wrench, torque the compressor con- The scroll compressor achieves low suc-
nections as follows: tion pressure very quickly. Do not use the
compressor to evacuate the system below
Service Valve / Connection Torque Value 0 psig. Never operate the compressor with
the suction or discharge service valves
Suction and Discharge 90 +/-- 10 ft--lbs closed (frontseated). Internal damage will
(122 +/-- 14 Nm) result from operating the compressor in a
Economizer Connection 33 +/-- 4 ft--lbs deep vacuum.
(45 +/-- 5 Nm) s. Following installation of a replacement compressor,
the oil level in the unit may be above the required
q. Connect the new compressor discharge temperat- level. Adjust the oil level in accordance with the in-
ure sensor (CDT) connector. Wire--tie any loose wir- structions packaged with the replacement com-
ing as appropriate. pressor.

Model NDK(ST) Unique Service Procedures 6/6


Economizer Heat Exchanger f. Unbraze the four lines at the economizer connec-
tions.
a. Remove the refrigerant charge.
g. Note orientation of economizer (mounted with con-
b. Ensure the unit is disconnected from the power nection markings upside--down). Remove econom-
source and that SROS is in the OFF position. izer heat exchanger, bolt replacement economizer
c. Remove insulation, brackets and clamps from eco- heat exchanger in place and rebraze lines by revers-
nomizer line assemblies as required (refer to figure ing the previous steps.
Figure 3). h. Leak check, evacuate the unit and charge.
d. Remove the economizer expansion valve and liquid i. reinstall the economizer outlet pressure transducer,
injection solenoid valve coils. economizer outlet temperature sensor, valve coils
and insulation.
e. Remove the economizer outlet pressure transducer
and economizer outlet temperature sensor. j. Place unit back in service and check operation.

2 4
1

2 3

9 4

5
1
8 8

1. Liquid Outlet Line (To EVXV) 5. Economizer Expansion Valve (ECXV)


2. Liquid Inlet Line (From Drier) 6. Economizer Outlet Temperature Sensor (ECOT)
3. Economizer Heat Exchanger 7. Compressor Economizer Connection
4. Economizer Outlet Pressure Transducer 8. Liquid Injection Solenoid Valve (LIV)
(ECOP) 9. Strainer (Location)
Figure 3. Economizer Assembly

Model NDK(ST) Unique Service Procedures 6/6


Compressor Suction
Modulation Valve (CSMV) 4 PIN CONNECTOR DRIVE & MOTOR
Servicing of the compressor suction modulation valve is ASSEMBLY
the same as previous units except for the drive and
motor assembly mounting arrangement. For this type of SCREWS
valve, ensure the gasket is installed in the body groove BODY
and torque the four mounting screws 80 to 97 in/lbs (9 to
11 Nm).

Figure 4 Suction modulation valve (CSMV)

Model NDK(ST) Unique Service Procedures 6/6


Electronic Expansion Valves Table 1. EVXV Connections
Connector Pin Wire Color Winding
The electronic expansion valves (EVXV = evaporator A ORANGE A
expansion valve & ECXV = economizer expansion
valve -- see Figure 5) are automatic devices which B RED B
maintain constant superheat of the refrigerant gas C YELLOW
leaving the evaporator/economizer regardless of A
suction pressure. The valve functions are: (a) automatic D BLACK B
response of refrigerant flow to match the evaporator E GREY COM (+12V)
load and (b) prevention of liquid refrigerant return to the
compressor. Unless a valve is defective, it seldom
requires any maintenance. b. To test the EVXV, place the SROS in the Start/Run
position. DO NOT ALLOW THE UNIT TO START.
NOTE When the MessageCenter displays “SMV CLOS-
ING”, measure the AC voltage between pins E & A
As a preliminary check ensure the valve coil is snapped and then between E & B, E & C and E & D.
down fully, and the coil retention tab is properly seated in To test the ECXV, start the unit and bring the setpoint
one of the valve body dimples. Also, check for a well below the refrigerated compartment temperat-
temperature drop at the valve inlet strainer location, ure to ensure the unit is operating in Economized
indicating the strainer is restricted or plugged. Mode. Measure the AC voltage between pins E & A
and then between E & B, E & C and E & D
A voltage should be read by the digital voltmeter for
each pair of wires. If the reading is present on all of
the wire pairs there is a good signal coming from the
3
SVM.
c. If the reading is not present on one or more of the
2 4 wire pairs, check the wiring between the SVM and
the valve connector, or check the Control System for
proper model number Configuration.
1
Diagnostics -- Stepper Motor
The valve stepper motor may be tested using a stepper
motor drive tester or ohmmeter.
FLOW
DIRECTION a. To test with a stepper motor drive tester (carrier
Transicold part number 07--00375--00), connect the 5
pin test cable to the valve connector, and the cable
wires to the tester in accordance with wire and termin-
al color. (if a 5 pin tester cable is required, order Carri-
er Transicold part number 07--00375--11
b. Set the step rate to 50 steps per second and either
open or close the valve. Each red LED should light se-
quentially until all four are illuminated. Any LED failing
to illuminate indicates an open on that leg and a need
1. Electronic Expansion 3. Coil to replace the drive.
Valve 4. Five Pin
2. Coil Boot Connector c. To test with an ohmmeter, check the winding resist-
ance between connector pin A & E, B & E, C & E and
Figure 5. Electronic expansion valve then between D & E. In normal ambient, the resist-
ance between the pins should be 46 ohms. If an infin-
ite or zero reading is observed, the piston and drive
Diagnostics -- Microprocessor or Wiring motor assembly is to be replaced.

a. Locate the wires, on the harness side of the valve Diagnostics -- Valve
connector labeled:
NOTE
EXVA, EXVB, EXVC, EXVD and EXVE
OR If the valve failed pretest and passed the pre-
ECVA, ECVB, ECVC, ECVD and ECVE. ceding diagnostic testing, this is an indication
that the valve internal mechanism is damaged
These will correlate to the connector pins labeled A, and the piston and motor assembly is to be re-
B, C, D and E. Refer to Table 1. placed.

Model NDK(ST) Unique Service Procedures 6/6


PIN A (ORANGE) PIN B (RED) CAUTION
The scroll compressor achieves low suc-
tion pressure very quickly. Do not use the
A B compressor to evacuate the system below
0 psig. Never operate the compressor with
COMMON the suction or discharge service valves
(+12VDC) closed (frontseated). Internal damage will
result from operating the compressor in a
deep vacuum.

b. Start the unit, set the step rate to 200 steps per
A B second, open and close the valve while watching the
suction pressure. Within one minute the suction pres-
sure should begin to change.
c. If the suction pressure does not change, this is an in-
PIN C (YELLOW) PIN D (BLACK) dication the valve is stuck and it is to be replaced.
PIN E (GRAY) Replacing Expansion Valve & Screen
a. Remove the refrigerant charge.
b. Remove coil and unbraze valve. Clean all tube stubs
Figure 6. Electronic Expansion Valve so new valve fits on easily.
c. Use a wet rag to keep the replacement valve cool and
a. To test the valve internal mechanism, connect a gage
braze in place.
to the suction service valve and a stepper motor drive
tester. d. Leak check, evacuate the unit and charge.

Model NDK(ST) Unique Service Procedures 6/6


Liquid Injection Solenoid Valve
1
2
6
3 7
4 8

9
5

6
INTERNAL COMPONENTS
COIL ASSEMBLY
1. Locking Nut 6. Armature Tube
2. Upper O--Ring 7. Internal O--Ring
3. Threaded Collar 8. Spring
4. Coil 9. Armature
5. Lower O--Ring
Figure 7. Solenoid Valve (LIV)
Replacing the Coil a. Remove the armature tube, taking care the armature
and spring do not drop out.
NOTE b. Ensure the spring is properly seated in the armature
The coil may be replaced without removing the and install into the armature tube.
refrigerant. c. Install a new internal O--ring into the valve body and
then reinstall the enclosing tube with armature and
spring.
a. Ensure the unit is disconnected from the power
source and that SROS is in OFF position. Disconnect Replacing Valve
coil connector. Remove locking nut, upper O--ring, a. To replace a valve, remove the refrigerant charge.
threaded collar, coil and lower O--ring (See Figure 7). b. Ensure the unit is disconnected from the power
b. Verify coil type, voltage and frequency of old and new source and that SROS is in OFF position. Remove
coil. This information appears on the coil housing. coil, refer to “Replacing the Coil” above.
c. Unbraze valve from unit and braze new valve in
c. Ensure upper and lower O--rings are installed on top place. Wrap valve in wet rag and point flame away
and bottom of coil and tighten locking nut to 10 to 18 from valve during brazing operation.
inch--pounds (1,2 to 1,4Nm).
d. Install coil, refer to “Replacing the Coil” above. Leak
Repairing Valve check, evacuate the unit and charge.

Model NDK(ST) Unique Service Procedures 6/6


Compressor Discharge Temper- c. Using the syringe supplied with the replacement
sensor, squeeze all of the dielectric compound into
ature Sensor the sensor well.
Values for testing the sensor, in accordance with d. Place a bead of the silicone sealer supplied with the
standard procedures, apr provided in Table 2. To replacement sensor around the sensor sealing ring.
replace the compressor discharge sensor (see Insert sensor into the well with the leads parallel to the
Figure 8) do the following: suction fitting.
a. Ensure the unit is disconnected from the power
e. Reconnect sensor connector and run a Pretrip to test.
source and that SROS is in OFF position.
b. Remove the existing sensor. Clean all silicone sealer
and dielectric compound from the sensor well. En-
sure well is clean and dry. Top of compressor, where
the sensor seals, must also be clean and dry.

SENSOR

SILICONE BEAD

SENSOR WELL

Figure 8. Compressor Discharge Temperature


Sensor

Model NDK(ST) Unique Service Procedures 6/6


Table 2. Sensor Resistance (CDT)

°F °C Ohms °F °C Ohms °F °C Ohms °F °C Ohms


--40 --40 2,889,600 96.8 36 53,887 233.6 112 4,204 370.4 188 706
--36.4 --38 2,532,872 100.4 38 49,656 237.2 114 3,977 374.0 190 697
--32.8 --36 2,225,078 104.0 40 45,812 240.8 116 3,759
--29.2 --34 1,957,446 107.6 42 42,294 244.4 118 3,550
--25.6 --32 1,724,386 111.2 44 39,078 248.0 120 3,354
--22.0 --30 1,522,200 114.8 46 36,145 251.6 122 3,173
--18.4 --28 1,345,074 118.4 48 33,445 255.2 124 3,004
--14.8 --26 1,190,945 122.0 50 30,985 258.8 126 2,850
--11.2 --24 1,056,140 125.6 52 28,724 262.4 128 2,711
--7.6 --22 938,045 129.2 54 26,651 266.0 130 2,580
--4.0 --20 834,716 132.8 56 27,750 269.6 132 2,454
--0.4 --18 743,581 136.4 58 23,005 273.2 134 2,335
3.2 --16 663,593 140.0 60 21,396 276.8 136 2,223
6.8 --14 593,030 143.6 62 19,909 280.4 138 2,119
10.4 --12 530,714 147.2 64 18,550 284.0 140 2,021
14.0 --10 475,743 150.8 66 17,294 287.6 142 1,928
17.6 --8 426,904 154.4 68 16,133 291.2 144 1,839
21.2 --6 383,706 158.0 70 15,067 294.8 146 1,753
24.8 --4 345,315 161.6 72 14,078 298.4 148 1,670
28.4 --2 311,165 165.2 74 13,158 302.0 150 1,591
32.0 0 280,824 168.8 76 12,306 305.6 152 1,508
35.6 2 253,682 172.4 78 11,524 309.2 154 1,430
39.2 4 229,499 176.0 80 10,793 312.8 156 1,362
42.8 6 207,870 179.6 82 10,122 316.4 158 1,302
46.4 8 188,494 183.2 84 9,494 320.0 160 1,247
50.0 10 171,165 186.8 86 8,918 323.6 162 1,193
53.6 12 155,574 190.4 88 8,376 327.2 164 1,142
57.2 14 141,590 194.0 90 7,869 330.8 166 1,096
60.8 16 129,000 197.6 92 7,404 334.4 168 1,054
64.4 18 117,656 201.2 94 6,972 338.0 170 1,014
68.0 20 107,439 204.8 96 6,571 341.6 172 975
71.6 22 98,194 208.4 98 6,197 345.2 174 938
75.2 24 89,916 212.0 100 5,848 348.8 176 902
78.8 26 82,310 215.6 102 5,529 352.4 178 867
82.4 28 75,473 219.2 104 5,233 356.0 180 834
83.0 30 69,281 222.8 106 4,953 359.6 182 798
89.6 32 63,648 226.4 108 4,692 363.2 184 764
93.2 34 58,531 230.0 110 4,446 366.8 186 733

Model NDK(ST) Unique Service Procedures 6/6


Rack Position Sensor (RPS) Calibration
a. Setup 6. With the Control System in Advance User mode,
1. Procure a Rack Position Sensor Calibration Kit from enter the Refrigeration System Unit Data and bring
Carrier Transicold Service Engineering. the suction modulation valve position reading into
view. Observe the SMV position (with screen locked)
and allow the unit to run until the SVM is stable.

REFRIGERATION SYSTEM (8 OF 8)
EVAPORATOR PRESSURE: 48.8 PSIG
EVAPORATOR OUTLET TEMP: 72.3 °F
SUCTION MOD VALVE: 68 %
EXPANSION VALVE: 100 %
END OF LIST
UNLOCK BACK EXIT
PLUG GATE VALVE SCREEN
ASSEMBLY

b. Calibration
1. Enter the Engine Unit Data and bring the Engine
Speed and Engine load readings into view.

ENGINE (1 OF 5)
BATTERY: 14.1 VOLTS
AMP DRAW: 12.2 AMP
ENGINE COOLANT TEMP: 132.8 °F
ADAPTOR HARNESS ENGINE SPEED: 1800 RPM
ENGINE LOAD: 89 %
UNLOCK BACK EXIT
SCREEN
Figure 9 Rack Position Sensor Kit
2. Place the START/RUN--OFF switch in the OFF posi-
tion. Disconnect the ENCU connector and plug the
adaptor harness between the ENSCU and harness
connector. Remove the J1 jumper and plug the ad- 2. Slowly close the gate valve to reduce flow and bring
apter harness two pin connector in it’s place. Ensure engine speed between 1780 and 1730 RPM.
the J1 jumper switch is in the open position. 3. Note and record engine load reading. Place the J1
3. Disconnect the air intake hose from the air cleaner jumper switch in the closed position for a minimum of
inlet and connect the gate valve assembly in its 5 seconds. The rack position sensor will recalibrate
place. Enure gate valve is fully open. and engine load reading change to 100 %.
4. Remove the kazoo from the air cleaner and install 4. Place the J1 jumper switch in the open position and
the plug in its place. shut down the unit by placing the RUN/START-- OFF
switch in the OFF position.
5. Start the unit in Continuous Operation and change
the setpoint sufficiently below the present refriger- 5. Remove the adaptor harness, gate valve assembly
ated compartment temperature to force the unit into and plug. Reinstall the J1 Jumper, reconnect the air
pull down. The unit must be operating in high speed, cleaner inlet hose and ENCU connector and reinstall
fully loaded, during the calibration procedure. the kazoo.

Model NDK(ST) Unique Service Procedures 6/6


Section Seven

Parts Information
2013 NDK Replacement Parts
P/N Description
08-00343-00 Coil Assembly
08-00345-00 Liquid suction BPHX
18-10151-00 Compressor
14-00410-00 Compressor SMV
12-00638-40 Pressure Switch
14-00176-01 Strainer
14-00329-06 Liquid Injection Valve
22-60734-02 Liquid Injection Valve Coil
14-00393-00 Evap EEV Valve
14-00393-01 Economizer EEV Valve
14-00393-10 EEV coil
14-00410-00 SMV
22-04249-00 Battery cable, positive
22-04249-01 Battery cable, negative
26-00135-00 Engine
22-04248-02 Main S/T harness
22-04248-03 Main M/T harness
30-00471-03 Air cleaner
30-00493-00 Exhaust flex pipe
30-00494-00 Vertical exhaust pipe
30-00489-00 Upper exhaust pipe
30-00497-00 Muffler
24-02024-00 Heater
24-02024-01 Heater
40-00673-02 Discharge Service Valve
40-00673-03 Suction Service Valve
54-00656-00 Generator
58-04880-00 Coolant hose
58-04903-00 Coolant hose
58-04914-00 Coolant hose
58-04928-00 Coolant hose
91-00425-00 Control Box Assembly – S/T
91-00425-01 Control Box Assembly – M/T
25-39491-00 Fuel Injector
ENCU
25-15582-00 Camshaft Assembly
25-15583-00 Piston
25-15584-00 Fuel Camshaft Assembly
25-15585-00 Rack Position Sensor
25-15586-00 RPS O-Ring
25-15587-00 Rack Position Sensor Adaptor
25-39480-00 Flange Bolt
25-15588-00 Fork Lever Assembly

Page 1 of 1
Section Eight

Forms
Unit Installation & Pre-Delivery Inspection 2013 NDK
Unit
NDK537 Trailer Refrigeration Units
(With APX)

Customer Name Unit Model

Address Unit Serial Number

City, State, Zip Compressor Serial


Number
Trailer Engine Serial
Manufacturer Number
Trailer Model Microprocessor
Serial Number
Trailer VIN Date Installed

Installing Company Installing


or Dealer Technician

The following items are the responsibility of the Installing Company or Dealer:

1. Ensure that a qualified technician performs the installation.


2. Installation of the unit, battery, fuel tank, and fuel lines as specified in the applicable Carrier Transicold installation
drawings. Installation drawings are supplied with every unit; they may also be obtained directly from Carrier
Transicold.
3. Install all options specified by the customer. These may include air chutes, return air bulkheads, light bars, etc.
Installation instructions should be provided with each of these items by the manufacturer.
4. Add a minimum of 15 gallons of diesel fuel to the fuel tank of the refrigeration unit. Use #2 diesel fuel if the
ambient temperature is expected to remain above +10 F (-12 C); if the ambient temperature is expected to drop
below +10 F (-12 C), #1 diesel fuel should be used.

The following items are the responsibility of the Technician, Installing Company and/or Dealer performing the Pre-
Delivery Inspection and unit delivery to owner:
1. Fill out identification data (above and below) and inspect the installation of unit and all options. Verify that the
installation has been performed to the requirements specified in the Carrier Transicold installation drawings.
2. Perform the Pre-Delivery Inspection, ensuring the use of the appropriate form for the model unit
3. As the owner takes delivery of the unit (from Dealer or installer) AND the unit is put into service, the in-service date
must be stamped on the unit serial plate, as this in-service date verifies the beginning date of ownership and
warranty.
4. Within ten (10) days of the in-service date, the unit must be registered with the Carrier Transicold Warranty
Department.
5. For completing steps 3 and 4 above, Dealers should refer to the Warranty Administration Policies & Procedures
Manual, P/N 62-10068 (Dealer Operating Manual, Section 6.1), for specific instructions. Trailer and truck body
OEM’s should contact the selling Carrier Transicold Dealer for copies of these detailed instructions.

Dealer Comments:

Inspecting
Technician
Signature of
Technician
Date

62-9XXXX Rev 5/23/2012 Page 1 of 4


NDK537 with APX 2013 NDK Unit

Pre-Installation & Pre-Delivery Inspection

Caution: Take all necessary steps to ensure that the unit will not start while technician is working on any moving
parts of the unit. Unit can start automatically. Disconnect battery cable when appropriate.

A. Pre-Start Unit Check / Installation SUCTION PRESSURE ......... _______________________


Torque unit mounting bolts and nuts (60 ft-lbs). DISCHARGE PRESSURE .... _______________________
Check fuel tank and fuel line installation (both supply and ENGINE COOLANT TEMP . _______________________
return lines should be one inch from bottom of fuel tank). RETURN AIR TEMP ............ _______________________
Check fuel and oil line connections for leaks. SUPPLY AIR TEMP ............. _______________________
Check wire connections and grounds for tightness. AMBIENT AIR TEMP .......... _______________________
Check all wire harnesses, cables, hoses and fuel lines for DEFROST TERM TEMP ..... _______________________
clearance or chafing. COMP DISCH TEMP ........... _______________________
Check battery cable connections and routing. BATTERY ............................. _______________________
Check engine coolant hose connections for leaks. CURRENT DRAW ............... _______________________
Check engine oil level. Add qts. ENGINE RPM ....................... _______________________
Check engine coolant level. Add qts. SOFTWARE REVISION ...... _______________________
Open all refrigeration system service valves. CONTROL SERIAL # .......... _______________________
Check defrost air switch setting (1.40” Water Gauge) UNIT MODEL #.................... _______________________
Install latest software from TransCentral * Re-check refrigerant level Add lbs.
Record software version installed _____________ Place the unit in Manual Defrost operation.
Check defrost drains for proper drainage.
B. Set up of APX * * Record engine speeds (adjust if needed):
Check & Set Microprocessor Configurations (See page 3) High Speed________ rpm, Low Speed________ rpm
Check & Set Functional Parameters (See page 3)
Check & Set Data Recorder (See page 3) NDK537
High Speed 1800
C. Initial Start-Up of Engine Low Speed 1350
Install refrigeration service gauges. Select Start/Stop operation. *Verify engine cycles off &
Start unit automatically. Warning buzzer should sound for restarts automatically.
five seconds prior to automatic unit start-up. If the buzzer Shut unit off.
does not sound, repair before proceeding. Recheck engine oil level. Add qts.
Enter 11°F (-12°C) Set Point, Continuous Run operation. Recheck engine coolant level. Add qts.
Listen for unusual noises, check all lines, hoses and * Check belt tensions:
gasket areas for leaks. Check all coolant hoses, fuel & oil lines, refrigerant
Check condenser and evaporator for proper airflow. fittings and gasket areas for leaks.
After 5 minutes of operation, record : Backseat all service valves, remove service gauges, and
Discharge Pressure @ gauges ________________ ensure valve caps are installed and tight.
Suction Pressure @ gauges ________________ Check any optional equipment for proper operation.
Ambient Temp. @ micro ________________ Check for proper installation and operation of bulkhead,
Return Air Temp @ micro ________________ air chute, fuel tank, light bar, etc.
* Check refrigerant level Add lbs. *Clear all Active and Inactive alarms from microprocessor.
D. Engine Break-In
Check fuel level in tank, add if required. F. Datagate Activation if Applicable
Open trailer doors. Start unit and enter a -22 F (-30 C) Follow the procedure for Datagate Activation form
Set Point, Continuous Run operation. (In extremely cold
weather, enter an 80°F (27°C) Set Point.) Operate unit for G. Unit Registration
4-6 hours minimum. Fill out Warranty Registration Card.
Stamp in-Service Date
E. Run Test / Re-Check Final Engine Hour Meter
Close trailer doors and let box temperature pull down. Final Switch On Hour Meter ________________
At approximately 0 F (-18 C) Box Temperature, scroll
through the unit data and record the following (see top of
next column):
*Refer to Operation and Service manual for
correct procedures and specifications.

62-XXXXX Rev- 5/23/2012 Page 2 of 4


NDK537 with APX 2013 NDK

Pre-Installation & Pre-Delivery Inspection


HOUR METERS
* Configurations VIEWABLE STANDARD METERS
DISPLAY TOTAL YES
CONFIG SETTINGS Factory Setting Changed to ENGINE HR:
UNIT IDENTIFICATION DISPLAY TOTAL YES
UNIT MODEL #: See Serial Plate SWITCH ON HR:
TRAILER ID #: SET PM CONFIGURATIONS
SET DATE AND TIME PM 1 CONFIG: OFF
SETPOINT(S) & RANGE LOCK PM 2 CONFIG: OFF
DECIMAL NOT DISPLAYED PM 3 CONFIG: OFF
MIN SETPOINT: -22.0 °F PM 4 CONFIG: OFF
MAX SETPOINT: 89.6 °F PM 5 CONFIG: OFF
RANGE 1 LOCK: OFF REMOTE SENSORS
RANGE 2 LOCK: OFF REMOTE TEMP SENSOR OFF
1
START-STOP SETTINGS
REMOTE TEMP SENSOR ON
CURRENT FOR S/S 7.0 AMPS
2
SHUTOFF:
DOOR SWITCH: NOT INSTALLED
VOLTAGE FOR S/S 12.2 VOLTS
RESTART REMOTE SWITCH 1: NOT INSTALLED
ENG TEMP FOR S/S 10.0 °F OTHER SETTINGS
RESTART: ENABLE ADVANCE NO
S/S PARAMETERS TOGETHER USER MODE:
INTELLISET & PRODUCTSHIELD PROTECT DATA WITH NO
PIN
ENABLE INTELLISET AT NO
= KEY: PARAMETERS NO
LOCKOUT
PRODUCTSHIELD: OFF
ECONO 8 HR ADDITIONAL YES
DATA
PRODUCTSHIELD: HIGH OFF
AIR HIGH SPEED DELAY 1.0 MINS
PRODUCTSHIELD: OFF LIGHT BAR: NOT INSTALLED
WINTER SET DATE AND TIME
PRODUCTSHILED NO RAIL SETTINGS
FRESH: UNIT OPERATION: STANDARD
ENGINE SETTINGS AUTO FRESH AIR SETTINGS
GLOW TIME: INTAKE HEATER AUTOFRESH AIR: NOT INSTALLED
ENGINE OIL LEVEL NO
SWITCH:
ENGINE OIL LEVEL NO
Customer Name
SHUTDOWN: Unit Serial Number
ENGINE HIGH TEMP NO Trailer Number
SHUTDOWN
ENGINE OIL PRESS NO
SHUTDOWN
FUEL LEVEL SENSOR: NO
LOW FUEL: UNIT
SHUTDOWN
FUEL HEATER: NOT INSTALLED
MAX. THROTTLE 125%
POSITION:
ALARM SETTINGS
OUT OF RANGE NO
SHUTDOWN:
RPM ALARM YES
SHUTDOWN:
LOW PRESSURE YES
SHUTDOWN:
LP SHUTDOWN DELAY: 10 SECS
HIGH SUCT PRESS YES
SHUTDOWN:
REFRIGERATION SYS
SHUTDOWN: YES
ALTERNATOR CHECK NO
SHUTDOWN:

62-XXXXX Rev- 5/23/2012 Page 3 of 4


* Functional Parameters * Data Recorder Setup
Sensors Factory Setting Changed to
FUNCTIONAL Factory Setting Changed to Return Air Temperature Average
SETTINGS Supply Air Temperature Average
Ambient Air Temperature Average
ECONOMY SETTINGS Defrost Term Temp 1 Average
LOW SPEED DELAY S/S: 10 MINS Defrost Term Temp 2 Average
LOW SPEED DELAY 0 MINS Compressor Disch Temp Average
CONT: Compressor SuctionTemp Average
AIR FLOW: NORMAL Evaporator Temp Average
TEMPERATURE SETTINGS Engine Coolant Temp Average
DEFROST TIMER SET 6 HRS Compressor Disch Press Average
FOR: Compressor Suct Press Average
FRESH PROTECT: C Evaporator Press Average
TEMP CONTROL: RETURN AIR Battery Voltage Snapshot
OUT OF RANGE OFF Battery DC Current Snapshot
ALARM:
Engine RPM Snapshot
START-STOP SETTINGS
Remote Sensor #1 Off
MIN RUN TIME: 4 MINS
Remote Sensor #2 ON
MIN OFF TIME: 30 MINS
Sensor Recording Interval 10 Minutes
RESTART TEMP: 5.4°F
OVERRIDE TEMP: 12.0°F Events Factory Setting Changed to
MAX OFF TIME: OFF Pretrip Start On
FROZEN SHUTDOWN 0.0°F Pretrip End On
OFFSET: Trailer ID On
SLEEP MODE: OFF Unit Serial Number On
OVERRIDES Unit Model Number On
VIEWING PREFERENCES Unit Mode On
DISPLAY °F Control Mode On
TEMPERATURES IN Door Opened / Closed On
DISPLAY PRESSURES IN PSIG Transducer Calibration On
DATE FORMAT: MM/DD/YYYY
ALARM DESCRIPTIONS: YES
CONTRAST 39

62-XXXXX Rev- 5/23/2012 Page 4 of 4


DATAGATE ACTIVATION & OPERATION VERIFICATION INSTRUCTIONS:
TO BE COMPLETED BY FIELD SERVICE PERSONNEL.
Reefer unit must be located outdoors for this procedure for GPS communication purposes.
1.) Disconnect the negative battery cable from the reefer battery.

2.) DataGate Activation:


For initial activation of system, locate “P7” Internal Battery connector on DataGate cable,
and plug the attached “P6” jumper into connector. (For best success, make the connection
quickly. If the electrical connection “makes-breaks-makes” while plugging the jumper
in, the PAR box can be tricked to go into another mode and the LED indicator light will stay
on continuously. In this case, follow the DataGate Reset instructions below.)
The LED will light for approx 1 minute, and go out permanently. This operation MUST
be witnessed. The DataGate is now energized and will transmit initialization
messages to the PAR LMS.
The unit is now energized and will transmit initialization messages to the PAR LMS
Operation Center.
Let the DataGate sit powered for 15 minutes (without the reefer powered or running) while
it completes its initialization by cycling through its Burn-In and In-Service Messages.
PAR LMS Operation Center will see that its system has come on line as the system
transmits its initialization messages.
Verify that PAR can see the DataGate’s “location”. Call Sal Farruggia at
703.433.6395.

Connected to Internal Extension Harness:


COMM, Power, & Fuel Sensor connectors.

Internal Battery Connections

Front view of DataGate.


3.) DataGate Reset:
To be performed in case the LED stays on continuously as described in Step 2 above.
For subsequent reset of the system, unplug the “P6” jumper from “P7” connector
(interrupting internal battery power), wait 45 seconds, then replug “P6” into “P7”.

4.) Reconnect the negative battery cable to the reefer battery.

5.) Turn the reefer’s APX controller START-RUN/OFF switch to START-RUN. Allow the reefer to run
for 15-30 minutes, changing the temperature set point at least once during this time, then turn
controller switch OFF. Turning the reefer unit off will force the DataGate to send temperature and
control information to the PAR LMS Operation Center.

6.) Record the serial number of the DataGate, along with the reefer’s serial number and fuel tank
capacity (if the Fuel Sensor option is installed). This information must be reported to PAR to
complete the installation.

DataGate Serial Number: ________________________.

Refrigeration Unit Serial Number: ________________________.

Fuel Tank Capacity: ________________________.

7.) DataGate Operation Verification & Troubleshooting:


Wait 15 minutes after reefer is shut down so that PAR system has time to transfer data to
PAR. (Data only transmits after unit power switch shutdown or alarm-shutdown events.)
Verify PAR operation with PAR Tech Support. Call Sal Farruggia @ 703.433.6395.
Call PAR for troubleshooting needs: Sal Farruggia @ 703.433.6395.
Sal Farruggia’s backup: Matt Paoni @ 703.433.6322 or Ryan Howe @
703.433.6324.

8.) DataGate & Reefer Unit Serial Number Association:


Provide data to PAR LMS to initiate PAR DataGate and APX reefer association.
Association requires the DataGate serial number, and the reefer unit’s serial number and
fuel tank capacity. Call Chris Fryc (pronounced Frye) @ 703.433.6397.

9.) Provide verification to Carrier (Syracuse) Engineering that DataGate Operation and Association
activities have been successfully completed. Call Jason Gough @ 315.432.7138. Engineering will
verify that the PAR system successfully transmits reefer unit operation data to the PAR LMS website.
Trailer Refrigeration Equipment 2013 NDK Unit
Pre-Trip Inspection
(APX Controller)
Customer: Maintenance Performed By:
Trailer Number: Date: For use on the following models with 2013 Platform
Unit Model: S/N: Modular Controllers:
Engine Hours: Switch-On Hours: NDK537
BEFORE STARTING ENGINE OK ADJ PRETRIP PASS FAIL
Drain water from bottom of fuel tank   Initiate Pre-Trip  
Drain water from water separator on fuel List any Pre-trip Alarms ________________________________
filter (if applicable)   _________________________________________________
Check radiator coolant level 1   _________________________________________________
Check condenser coil for cleanliness   AFTER OPERATING UNIT FOR 15
Check radiator coil for cleanliness   MINUTES OR MORE OK ADJ
Check air cleaner and hoses   Check refrigerant level 2
 
Check air cleaner indicator   Check for proper temperature control 2  
Check engine oil level 1
  Check engine speeds2  
Check condition and tension of belt 1   Check auto-start/stop operation 2  
Check all fan bearings   Initiate defrost and allow to terminate
Check door latches and hinges   automatically  
Check condition of condenser fan blades  
Check battery fluid level (if applicable)   OPERATE IN HIGH SPEED COOL AND RECORD
(From Microprocessor Unit Data List)
Check battery cables and terminals   SUCTION PRESSURE ................................. _______________
Check evaporator coil(s) for cleanliness   DISCHARGE PRESSURE ............................ _______________
Check air chute (if applicable)   ECONOMIZER PRESSURE ......................... _______________
Check bulkhead and return air screen   ENGINE COOLANT TEMP ......................... _______________
Check all defrost water drains   RETURN AIR TEMP .................................... _______________
Place in Continuous Run, and start unit.   SUPPLY AIR TEMP ..................................... _______________
AMBIENT AIR TEMP .................................. _______________
IMMEDIATELY AFTER STARTING DEFROST TERM TEMP #1 ......................... _______________
ENGINE OK ADJ DEFROST TERM TEMP #2 ......................... _______________
Check fuel lines and filters for leaks   COMP DISCH TEMP ................................... _______________
Check oil lines and filters for leaks   SMV………………………………………… _______________
Check coolant hoses for leaks   _______________
BATTERY .....................................................
Check exhaust system for leaks   CURRENT DRAW ........................................ _______________
Check condenser fan for proper airflow.   _______________
ENGINE RPM ...............................................
Check evaporator fan for proper airflow.   SOFTWARE REVISION .............................. _______________
CONTROL SERIAL # ................................... _______________
_______________
UNIT MODEL #............................................
Comments / Notes: _______________
HOURS TO ENGINE MAINTENANCE ......
___________________________________________________ HOURS TO UNIT MAINTENANCE ........... _______________
___________________________________________________ TIME LEFT TO PM1 .................................... _______________
___________________________________________________ TIME LEFT TO PM2 .................................... _______________
___________________________________________________ TIME LEFT TO PM3 .................................... _______________
TIME LEFT TO PM4 .................................... _______________
1
See reverse side for specifications and/or part numbers. TIME LEFT TO PM5 .................................... _______________
2
Refer to Operation and Service Manual for procedures and/or specifications. DATALOGGER TIME & DATE .................. _______________
FINAL OK ADJ
Review Functional Parameters and fill in
table on reverse side  
Download recorder data (if required)  
Enter Trip Start in Micro  

62-XXXXX Rev 05/23/2012 Page 1 of 2


Trailer Refrigeration Equipment
Preventive Maintenance Inspection
Customer: For use on the following models:
Trailer Number: Date: NDK537
Unit Model: S/N:
Engine Hours: Switch-On Hours:
Inspection Performed By:

Every Service Interval1 or Yearly


ENGINE Electrical System
Change lube oil and filters 1  Check all ground connections for corrosion & tightness 
Check low oil pressure safety  Check Stand-by plug for signs of wear or damage 
Clean crankcase breather  Check condenser fan amperage 
Check engine hours, adjust engine valves every 4k hrs  Check evaporator fan amperage 
FUEL SYSTEM Check compressor amperage 
Clean fuel pump strainer  Check heater amperage 
Change fuel filter1  Every 10,000 Hours
Check fuel heater (if equipped)  Clean and adjust injector nozzles 
COOLING SYSTEM Every 5 years or 12,000 hours
Check antifreeze concentration1  Drain and flush cooling system2 
Clean radiator and condenser fin surface 
Check water pump  1
See reverse side for specifications and/or part numbers.
Check water temperature sensor  Refer to Operation and Service Manual for procedures
EXHAUST SYSTEM and/or specifications.
Check mounting hardware 
Check muffler and exhaust pipes  Comments:
AIR INTAKE SYSTEM
Change air cleaner element1 
Check and reset air filter indicator if needed 
STARTING CIRCUIT
Clean battery cable connections and cable ends 
Check battery hold-down clamps 
Check battery condition 
Check starter operation 
CHARGING CIRCUIT
Check battery charger output voltage 
Check battery charger amperage 
UNIT
Check unit mounting bolts 
Check engine and compressor mounting bolts 
Check door latches and hinges 
Check gauges, switches and electrical connections 
Check water pump belt tension, adjust as necessary1 
Check control box / relay box condition 
Check all electrical ground connections 
REFRIGERATION SYSTEM
Check air switch and calibrate (1.4” wg) 
Check and clean evaporator coil & defrost drain hoses 
Connect gauges & check operating refrigerant pressure 
Check Calibration of suction pressure transducer 
Check manual defrost operation 

62-XXXXX Rev
SERVICE REFERENCE
ENGINE SERVICE INFORMATION
Primary Bypass Oil Change Interval Oil Change Interval
Engine Type Oil Filter Type Oil Filter using API Class CF engine oil using Mobil Delvac 1 engine oil
DI 30-00463-00 No 3000 hrs / 2 yrs 4000 hrs / 2 yrs
Engine Oil Type: API Class CF or Mobil Delvac 1
Engine Oil Viscosity: SAE 15W40 or 10W-30;
Extreme cold 5W-30 Engine Coolant Mixture: 50/50 to 60/40 Antifreeze/Water
Engine Oil Capacity: 15 quarts (U.S.) Engine Coolant Capacity: 8 quarts (U.S.)

REFRIGERATION SYSTEM CAPACITIES

NDK537

Refrigerant R-404A 13 lbs.

Compressor Oil 07-00317-00 (for R-404A) 64 ounces

MAINTENANCE PARTS

Part Description NDK537 FILTER PART NUMBERS


Oil filter 30-00463-00
Fuel filter without bowl 30-01090-01
with bowl 30-01079-01
Air filter 30-00471-20
BELT TENSIONS
Pre-tension new belt to tension indicated, then check and re-tension belt to final tension after 15-minute BELT PART
break-in. Numbers
Measure tension with Belt Tension gauge P/N 07-00253-00.
Water pump belt (new, final) (45-55, 45-55) (45-55, 45-55) 50-00162-22

ENGINE SPEEDS
NDK537
Engine speed (RPM) High 1800
Low 1350

OTHER
Unit mounting bolt torque 60 ft-lb.
Engine/compressor shock mount torque 90 ft-lb.

2
2013 NDK Unit
Periodic Inspection Form
Follow the Fleet
Unit Inspection Sheet
Dealer: Customer:
Model #: Unit Serial #:
Trailer #: Engine Hours:
Inspection Date: Standby Hours:
Inspected By: Switch On Hours:

Visual / Physical Inspection with Unit Off


Open all unit doors and perform the following checks on the front of the unit:
NOT
Check / Inspect OK Problem / Comment
OK
PCM module mounting points for any
damage and/or cracks

Note: If PCM module must be removed, and


nylon spacers are present behind the
mounting points, they must be re-used upon
re-installation.
Wire harnesses for chaffing areas, loose tape
wrap, and ensure proper tie-downs
Battery cables for signs of chaffing,
insulation damage, and ensure tie-downs are
secure
Battery tiedown for tightness and signs of
battery leakage
Compressor fittings (CSP, CDP, CDT, HP1,
ECOP) for signs of refrigerant leaks
Air cleaner mounting for cracks and tightness
MAP sensor on air intake filter
Coolant hose clamps for tightness / leaks
Coolant clamps on copper tube attached to
pod
Water pump belt tension and wear
Refrigerant tube braze joints for signs of oil /
leakage
Engine mounts for wear or degradation
Lower frame corner bolt on gussets for bolt
tightness or cracking
Bell housing for cracks
Exhaust system for evidence of leakage
High voltage AC cable from control box to
high voltage plug
Condenser fans and fan motor mounting
frame for signs of cracking or damage
Low voltage control harness
Condenser and evaporator motor connections
Tightness of condenser fan motor mounting
bolts
Condenser coil fin surfaces
Starter solenoid wire to “S” terminal

Page 1 of 3
2013 NDK Unit
Periodic Inspection Form
Remove the access panels in the bulkhead and evaporator to perform the following checks in the evaporator
section of the unit:
NOT
Check / Inspect OK Problem / Comment
OK
Evaporator tubesheets near mounting points
to evaporator frame
Evaporator air nozzle for signs of damage or
warpage
Evaporator blower for signs of interference
with nozzle
EVXV Coil, make sure it is snapped down
fully
EVOP transducer for signs for refrigerant
leakage
Heater rods, make sure all are securely in
place
Evaporator Fans for signs of cracking or
damage

Re-install evaporator and bulkhead access panels, reconnect air chute & transition if disconnected.

Pretrip – Diesel Mode

Pre-trip the unit. This will take approx. 10 mins. Check box if no alarms are generated □
If alarms occur, list all that are generated:
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
Allow unit to restart and continue running when Pretrip is finished before continuing to the next step. Correct
any defects found during Pretrip.

Pretrip Inspection with Unit Running in Standby Mode *optional*


1. With unit run/stop switch off, plug unit into Standby Power outlet (460V 60 Hz). Turn circuit breaker on.
2. Select Standby Operation and turn run/stop switch on.
3. Let unit start automatically in Standby Mode.
Pretrip – Standby Mode

Pre-trip the unit. This will take approx. 10 mins. Check box if no alarms are generated □
If alarms occur, list all that are generated:____________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
Correct any defects found during Pretrip.

Download Data Recorder Completed

1. *Download all unit data and email to service.engineering@carrier.utc.com □


2. List any problems downloading unit: ________________________________________
______________________________________________________________________

Clear all active and inactive alarms from Micro.

Page 2 of 3
2013 NDK Unit
Periodic Inspection Form

Record any further comments below:


_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________
_____________________________________________________________________________

Warranty Filing

Labor Allowance for complete 2013 Belt Drive Unit Inspection = 1.3 hrs @ std dealer rate
Note on warranty claim: “2013 Belt Drive Unit”

Fax Completed Forms to:


860-622-7352 Carrier Transicold
Service Engineering
Attn: Ken Shuart
700 Olympic Drive
Athens, Georgia 30601

service.engineering@carrier.utc.com

Page 3 of 3

You might also like