One important heat load that has been omitted in the calculation is the heat gain due to
solar radiation. This factor depends on a number of conditions which are related to both
the location of the store and its method of construction. In some cases, solar heat load
may not be significant but in other instances, precautions may be necessary to reduce
its effect.
Specification
Dimensions 20 m x 10 m × 5 m = 1 000m3
Insulation thickness (0.25 m)
External store surface area (771.5m 2)
Maximum ambient temperature (35C)
Store temperature (-30C)
Load calculation
If a pump is used to circulate refrigerant, the heat equivalent must be added to the
capacity of the refrigeration condensing unit but not to the capacity of the room cooler.
The minimum refrigeration requirement will be when there is only an insulation heat load
and the fans are in operation. In this example, the minimum load corresponds to only
about 25 percent of the capacity of the installed refrigeration plant. This minimum load
factor will vary considerably with the type of store and mode of operation but some
account may have to be taken of this difference between the maximum and minimum
refrigeration requirements. Large cold stores should be operated with a number of
compressors, which can be switched on and off as required. Large compressors may be
fitted with off-loading equipment which allows them to work efficiently on partial loads.
The reliance on one large compressor for a large cold store could be catastrophic in the
event of its failure. In the case of smaller stores it may be that only one compressor is
viable. Other arrangements can be made to cater for the variation in refrigeration
demand. What must not happen is that a large compressor should operate with a low
load and hence operate with a very low suction pressure or stop and start too frequently.
The first condition is bad for the compressor and the second for the electrical
equipment.
Therefore, unless only one product is stored under closely defined conditions, this
definition is obviously unsuitable. It is generally agreed that it is more appropriate to
define storage capacity in terms of the store volume but there are a number of ways in
expressing this value.
Net volume is the volume that can potentially be used for storage and is the gross
volume less the volume required for coolers, structural requirements, doorways and
other permanent features of the store.
Effective volume is the store space that can actually be utilised for storage and it takes
into account the requirements for passageways, stacking equipment etc.
Gross volume and net volume can easily be defined by devising a simple set of rules for
making these calculations. These store volumes, however, can only give a rough
estimate of storage capacity and their main use may before statistical purposes. The
effective volume can only be calculated for each particular case and to achieve any
degree of accuracy, a drawing of the store layout would be required together with full
details of the storage conditions. Store operators should therefore use general
statements of store capacity with care and when placing an order they would give full
details of the products and the storage operation to enable the supplier to provide a
store to suit the operating requirements with the maximum utilisation of the gross
storage volume.