Professional Documents
Culture Documents
Mechanical Design of Overhead Transmission Line: Assignment-Module 3 Transmission and Distribution
Mechanical Design of Overhead Transmission Line: Assignment-Module 3 Transmission and Distribution
Corona
8. Define corona. Define critical disruptive voltage.
9. What are the methods adopted to reduce corona?
10. What is the difference between visual critical voltage and disruptive critical voltage?
11. A 3-phase equilaterally spaced transmission line has a total corona loss of 55 K W at
11 DKV and a loss of 110 k W at 120 kV. What is the disruptive critical voltage
between the lines? What is the corona loss at 125 k V?
12. Find the disruptive critical and visual corona voltage of a grid line operating at 132
kV. The data are given
Conductor diameter = 1.9 cm
Conductor spacing = 3.81 m
Temperature = 44° C
Barometric pressure = 73.7 cm
Conductor surface factor: Fine weather = 0.8 rough weather = 0.66
Distribution
1. State Kelvin’s law. What are the limitations of Kelvin’s law?
2. List the various types of distribution systems.
3. Describe the radial system and ring main system of distribution.
4. A 2-wire dc. Distributor AB 500m long, fed at both ends at equal potential of 250 V is
loaded with uniformly distributor load of 0.5 A/m along with concentrated load of
100A, 200A, 300A and 400A at distances of 100 M, 200 M, 300 M and 400 M
respectively from end A. Calculate the distance from A where the potential of the line
would be minimum. Assuming the resistivity of the conductor material to be
1.7 × 10-8 ΩM. Calculate the minimum cross-section of the conductors so that the
maximum drop may not exceed 20V.
5. Calculate the voltage at a distance of 200 m of a 300 m long distributor uniformly
loaded at a rate of 0.75 A/meter. The distributor is fed at one end at 250 V. The
resistance of the distributor (go and return) per meter is 0.00018 ohm. Also calculate
the power loss in the distributor.
6. A DC distributor AB is fed at both ends. At feeding point A, the voltage is maintained
at 235V and at B 236 V. The total length of distributor is 200 meters and loads are
trapped off as follows
20A at 50 M from A;
40A at 75 M from A
25A at 100 M from A
30A at 150 from A.
7. A 2-wire DC distributor 200 meters long is uniformly loaded with 2A/meter.
Resistance of single wire is 0.3 Ω. If the distributor is fed at one end, calculate:
(i) Voltage drop up to a distance of 150 m from the feeding point.
(ii) Maximum voltage drop.