Professional Documents
Culture Documents
AND
NUMERICAL(Digital) RELAYS
Introduction
A static (solid state) relay refers to a relay in which there is no armature
or other moving element and response is developed by electronic,
magnetic or other components without mechanical motion.
The rectifier was rectifying the input signal and pass it to the relaying
measuring unit.
The rectifying measuring unit has the comparators, level detector and
the logic circuit.
The output signal from relaying unit obtains only when the signal
reaches the threshold value. The output of the relaying measuring unit
acts as an input to the amplifier.
Static…
The amplifier amplifies the signal and gives the output to the output
devices. The output device activates the trip coil only when the relay
operates.
The output is obtained from the output devices only when the measured
has the well-defined value. The output device is activated and gives the
tripping command to the trip circuit.
The static relay only gives the response to the electrical signal. The
other physical quantities like heat temperature etc. is first converted into
the analogue and digital electrical signal and then act as an input for
the relay.
Static…
Merits and Demerits of Static Relays
1) Low burden on CTs and VTs. The static relays consume less power
and in most of the cases they draw power from the auxiliary dc supply.
2) Fast response.
3) Long life.
8) Compact size.
The relay does all this by comparing two quantities either in amplitude
or in phase. The phase relation and the amplitudes are a function of
the system conditions. The device which makes these comparison is
known as a comparator and forms the heart of the relay. The
comparator decides operating characteristics of a relay.
Types of Comparators
1. Amplitude Comparator
2. Phase Comparator
The basic circuit for the circulating current is shown in figure. the
currents are the input signals. The relay will operate whenever S1>S2,
where S1 =Ki1 and S2= Ki2.
When i1 and i2 are out of phase, the difference (i1-i2) has both the
positive and negative loops. If i1>i2, the positive loop is bigger than the
negative and if i1<i2, the negative loop is bigger than the positive.
When i1 = i2 the positive and negative loops are equal, each loop
occupying ¼ of the time duration of one cycle of the input currents. The
out put waveform is therefore, a double frequency pulsation.
In this comparator one or both the signals are sampled at the same
instant or at different instants and are compared. When one signal is
sampled, it is compared with the signal proportional to its rectified
(average) value.
In case of reactance relay the sampled value of voltage is compared
with the average value of current when it is passing through zero value.
let Φ be the power factor angle of the circuit.
When current passes through zero the instantaneous value of voltage
will be V sin Φ.
the reactance relay operates when X < K, where X is the reactance
seen by the relay and K is design reactance of the system.
since X = Z sinΦ,
therefore Z sin Φ < K
V/I sin Φ < K
Vm/√2 sin Φ < KIav x 1.11
Vm sin Φ < √2 KIav x1.11
Vm sin Φ < K’Iav
The block diagram for the comparator is shown in figure. reactance
relay operation can also be explained when both voltage and current
signals are sampled.
Voltage is sampled again when the current is passing through zero
value and current is sampled after a delay of say α.
Again if power factor of the circuit is cosΦ, the voltage signal at the
current zero instant will be Vm sin Φm and the current signal after delay
of α will be Im sin α
Comparators…
If the two samples are taken at different instants, the pulse width
representing the one taken first in time sequence is delayed by the
time difference between the two sampling instants, before feeding to
the AND gate.
Phase comparison technique is the most widely used technique for all
practical directional, distance, differential and carrier relays.
In this type of comparator, the operation of the relay takes place when
the phase relation between two inputs S1 and S2 varies within certain
specified limits. Mathematically the condition of operation is given by
−α1 ≤ θ ≤ α2
where θ is the angle by which S1 lags S2.
In this method one input is converted into a square wave and the other
into a pulse of short duration (known as spike) at the instant when this
input is either passing through zero value or when it is passing through
peak value.
The squared wave and the spike then are fed into an AND gate and
there is an out put when the two signals coincide at any time as shown
in figure.
The method requires splitting of phase of the two input signals, each
into two components shifted ±45o with respect to the original signal.
The four components are then fed into an AND gate which gives an
output when the four signals are positive simultaneously at any time in
the cycle as shown in figure. it can be seen that output will be obtained
for − 90 o ≤ α ≤ 90 o. The block schematic is shown figure.
Comparators…
The two signals S1 and S2 are fed into an AND gate the output of which
is integrated to measure the period of coincidence of the two signals.
Φ = Φm sin wt
Let I1 = Im sin wt
The two fluxes ФA and ФB through the elements A and B are φ A ∞ I 1 and
dI 2 dI 1
φ A∞I 2 the currents through the elements are I A ∞ and I B ∞
dt dt
Since the two elements are so connected that the output voltages
oppose each other , therefore resultant voltage is given by
VH = V A − VB
∞I m1. sin wt.I m2 w cos(wt + α ) − I m2 sin(wt + α ) wI m1 cos wt
V H ∞ I m1 I m 2 sin α
Comparators…
This type of relay is mostly used in USSR and is considered better than
Hall element relay because of simpler construction and circuitry.
Comparators…
The input transformer has an air gap in the iron core to give linearity in
the current/voltage relationship up to the highest value of current
expected, and is provided with tapings ion its secondary winding to
obtain different settings.
In a static distance relay it is necessary that the two input quantities are
similar i.e., voltage/voltage or current/current because they are not
electrically separate as they are in case of electromagnetic relays (in an
impedance relay magnets are energized by voltage and currents).
So the comparators employed in static distance relays can be of either
voltage comparator or current comparator.
ZR ∠
∠θ is the design impedance or a replica of the impedance of the line
to be protected on a secondary basis. Distance relay based on voltage
comparison.
The output unit is usually a moving coil relay. The starting element is
usually an over current relay. The output is given to the measuring
element. Phase comparators are employed in the measuring devices.
The measuring device determines whether the fault is within the
protected zone or not. Correspondingly a tripping signal is initiated in
case the fault is within the protected zone.
In case the fault is outside the protected zone, the timer unit starts. This
initiates zone-wise protection.
The static differential relays are most commonly used for the protection
of generators and transformers for any type of internal faults (two- and
three-phase faults, earth faults with solidly grounded neutral or low
resistance grounded neutral-inter-turn faults).
These relays are advantageous over electromagnetic differential relays
as they are
i. very compact,
ii. highly sensitive for internal faults and have absolute stability for heavy
through faults,
i. extremely short tripping times (20-50 ms) regardless magnitude of
auxiliary voltage,
ii. accurate and absolutely stable tripping characteristic even for
asymmetrical faults as each phase can have its own relay,
iii. low VA burden,
iv. inrush current proof characteristic even during high starting currents,
inrush currents.
respectively .
I. Microprocessor based
The output of the transducers are applied to the signal conditioner (also
called analog input sub system).
It brings real-world signals into digitizer. It isolates relay from the power
system, reduces the level of the input voltages, converts currents to
equivalent voltages and removes high frequency components from the
signals using analog filters.
Since A/D converters accept voltage signals only, the current signals
are converted into proportional voltage signals by using I/V converters
or by passing through precision shunt resistors.
The outputs of the signal conditioner (the analog input sub system) are
applied to the analog interface, which includes sample and hold (S/H)
circuits, analog multiplexers and A/D converters.
These components sample the reduced level signals and convert their
analog levels to equivalent numbers that are stored in memory.
ii. Flexibility
xiv. Standardization
Disadvantages