Room
Phase-Earth Phase-Neutral
Reference
Remarks
Socket
Prospective Prospective
Reference
Impedance Earth Fault Impedance Short Circuit
(ohm) Current (ohm) Current
(A) (A)
PG-BB-38/B1 0.42 507 0.73 328 VEST1BULE-1 PASS
PG-DB-38/47 0.36 665 0.42 507 PLT2-GF-12 PASS
B5 Y DAMAGED
OUT SIDE
Phase-Earth Phase-Neutral
Socket Prospective Prospective Room
Impedance Impedance
Reference Earth Fault Short Circuit Reference Remarks
(ohm) (ohm)
Current(A) Current(A)
PG-DB-32-B2 0.26 923 0.67 359 GALERIE-4 PASS
PG-DB-30-Y9 0.64 373 1.40 166 GALERIE-4 PASS
PG-DB-30-B10 0.45 532 0.90 250 GALERIE-4 PASS
SIGNATURE
Phase-Earth Phase-Neutral
Prospective Prospective
Socket Room
Impedance Earth Fault Impedance Short Circuit Remarks
Reference Reference
(ohm) Current (ohm) Current
(A) (A)
PG-DB-27-46 0.44 542 1.20 194 VESTIBULE-2 PASS
PG-DB-27-B5 0.59 405 1.34 178 VESTIBULE-2 PASS
PG-DB-27-49 0.37 646 0.76 327 VESTIBULE-2 PASS
PG-LG-DB03-B3 0.59 406 1.20 189 LG WASH
PASS
ROOM GF
PG-DB-25-R1 0.55 433 0.33 723 ROOM NO
PASS
3645
PG-DB-25-Y1 0.43 555 1.19 201 GALLERY-6 PASS
PG-DB-25-R5 0.55 433 2.01 118 GALLERY-6 PASS
PG-DB-25-R5 0.56 426 2.27 105 GALLERY-6 PASS
PG-DB-24-Y7 0.36 665 0.39 612 PASSAGE-8 PASS
PG-GF-DB12-B8 0.32 753 1.08 223 GALLERY-14 PASS
OUTSIDE
COMPANY TEST CARRIEDOUT BY: WINSTAR TEST APPROVED BY: LOUVRE
SIGNATURE
Phase-Earth Phase-Neutral
Prospective Prospective
Socket Room
Impedance Earth Fault Impedance Short Circuit Remarks
Reference Reference
(ohm) Current (ohm) Current
(A) (A)
PG-DB-20-Y3 0.33 723 0.87 275 PASSAGE-8 PASS
PG-DB-24-Y3 0.43 556 0.53 451 GALLERY-7 PASS
PG-DB-24-B7 0.64 373 0.56 425 GALLERY-7 PASS
PG-DB-24-B1 0.40 599 1.05 228 PLT-2-GF-051 PASS
PG-DB-22-R2 0.30 797 0.63 378 PER-2-GF-22 PASS
PG-DB-21-Y2 0.49 488 1.20 198 GALLERY-8 PASS
PG-DB-21-Y2 0.52 460 1.52 129 GALLERY-8 PASS
PG-DB-21-R3 0.31 769 0.74 323 PER-2-GF-23 PASS
PG-DB-21-B2 0.34 706 1.05 228 GALLERY-9 PASS
PG-DB-19-R2 0.50 476 1.01 236 GALLERY-10 PASS
PG-DB-19-B3 0.23 1000 0.74 324 GALLERY-10 PASS
EX-GF-DB02-B1 0.58 416 0.72 335 TEMP.GALLER
PASS
Y OUT SIDE
EX-GF-DB02-Y2 1.43 169 2.08 116 TEMP.GALLER PASS NOTE
Y OUT SIDE ONE SOCKET
NO SUPPLY
SIGNATURE
Phase-Earth Phase-Neutral
Socket Prospective Prospective Room
Impedance Impedance
Reference Earth Fault Short Circuit Reference Remarks
(ohm) (ohm)
Current(A) Current(A)
PG-DB-19-Y1 0.58 414 1.10 207 GALLERY-11 PASS
PG-DB-14-Y1 0.21 1100 0.46 521 PLT-2-GF-06 PASS
PG-DB-16-Y3 0.21 1100 0.44 544 PLT-2-GF-07 PASS
PG-LG-DB02- 0.39 615 1.35 177 WING-3 WASH
PASS
B10 ROOM
PG-DB-16-B1 0.46 521 1.04 230 GALLERY-12 PASS
PG-DB-16-B3 0.46 524 0.88 273 GALLERY-12 PASS
PG-DB-16-B1 0.65 371 3.13 86 GALLERY-12 PASS
PG-DB-14-R3 0.41 582 0.83 277 GALLERY-13 PASS
PG-DB11-R1 0.63 380 3.09 77 GALLERY-14 PASS
PG-DB11-B1 0.52 463 0.44 548 GALLERY-14 PASS
PG-DB11-R3 0.53 451 1.41 170 GALLERY-14 PASS
PG-DB13-R2 0.38 628 0.41 584 GALLERY-15 PASS
SIGNATURE
Phase-Earth Phase-Neutral
Socket Prospective Prospective Room
Impedance Impedance
Reference Earth Fault Short Circuit Reference Remarks
(ohm) (ohm)
Current(A) Current(A)
PG-LG-DB01 1.02 236 1.62 148 WING-4 PASS
B10 WASH ROOM NOTE SOCKET
DAMAGED
PG-LG-DB01-B9 0.47 512 1.27 189 WING-4
PASS
WASH ROOM
PG-DB01-B4 0.48 503 0.44 548 GALLERY-19 PASS
PG-DB-04-Y2 0.32 751 0.86 279 PER-2-GF-46 PASS
PG-GF-DB09-Y4 0.34 649 0.99 243 PASSAGE-15 PASS
PG-GF-DB09-B4 0.43 547 0.88 273 GALLERY-21 PASS
PG-GF-DB09-B3 0.35 691 1.0 242 PASS
PG-GF-DB09-B3 0.72 334 1.10 108 PASS
PG-GF-DB09-R4 0.53 454 1.42 169 PASS NOTE
LOOSE
CONNECTION
SIGNATURE
Instrument Name Instrument Make Type Serial No. Cal. Due. Date
SIGNATURE