with 0.8 pf
Total demand for lighting and general power (kVA) 85.9 85.9
Total demand for Mechanical Equipments (kVA) 631.8 582.5
Total (kVA) 717.7 668.4
Total demand with 15% spare (kVA) 825.3 768.6
Total Area of the Building (m2) 19024 19024
Total demand of the project (VA/m2) 43.4 40.4
Selected Transformer(kVA) 800 800
Maximum Transformer Loading (%) 89.71 83.55
Selected Generators (kVA) 3x200+10+110
Maximum Generator Loading (%) 100.00
with 0.8 pf
574.1359
PROPOSED TEA FACTORY COMPLEX FOR GEORGE STEUART TEAS (PVT.) LTD. AT BIYAGAMA
Estimated Electrical Demand
Lighting and Power KVA
LOAD TYPE
AREA (m2) LIGHTING GENERAL POWER
LUX LEVEL (lx) DEMAND (VA) POWER (VA/m2) DEMAND (VA) Total(kVA)
18 460.83 29.86
8 20.37 0
18 1077.50 23.27
4 34.44 2.23
18 690.00 22.36
18 700.00 22.68
10 209.26 13.56
18 703.33 22.79
18 388.33 12.58
10 101.39 6.57
2 1.67 0
4 2.04 0.13
18 787.50 51.03
8 20.37 0
18 555.83 36.02
18 778.33 25.22
18 453.33 14.69
18 416.67 13.50
10 17.13 2.22
18 330.00 10.69
18 713.33 0.00
18 0.00 57.78
18 566.67 45.90
2 18.81 1.22
10 80.56 5.22
2 7.44 0.48
10 86.81 5.63
4 10.06 0.87
10 15.56 1.01
8 9.81 0.00
4 10.47 0.90
2 1.67 0.07
4 2.04 0.00
18 963.33 0.00
18 0.00 15.61
18 373.33 24.19
18 736.67 23.87
10 66.20 4.29
10 63.89 41.40
18 1200.00 38.88
18 356.00 11.53
10 84.72 5.49
10 66.44 4.31
2 115.09 0.00
18,796.81 1,514.80
PF 0.8
12,029.96 969.47 12,999.43 kWh
Demand Calculation for Mechanical Equipment
Power Factor 0.8
Power Factor for lifts 0.6
Power Factor for machinery 0.6
Power per Demand/ Connection Type Power Source Connection
Equipment Equipment Power (kVA) Qty Diversity Demand Demand (kVA) Phase (Isolator/Industrial Socket (UPS/Row Method (Top/
(kVA) with 0.8 pf Outlet/ Socket Outlet) Power) Bottom)
(kW) Factor
Ground Floor & First Floor
Reach Truck Charger 16.55 20.69 6 0.3 37.24 37.24 3 ph IND RP -
Roller Door 0.37 0.46 2 0.6 0.56 0.56 1ph ISO RP -
SDB-GF1 DB-GF1-COR
SDB-GF2 DB-GF2-COR
SDB-GF1 DB-GF1-COR
SDB-GF1 DB-GF1-MUB
SDB-1F2 DB-1F2-COR
SDB-2F2 DB-2F2-MSK
SDB-1F1 ISO-1F1-BM
SDB-1F1 DB-1F1-MBA
SDB-1F1 DB-1F1-MBA
SDB-1F1 DB-1F1-MBA
SDB-1F1 DB-1F1-MBA
SDB-1F1 DB-1F1-MBA
SDB-1F1 DB-1F1-MBA
SDB-1F1 DB-1F1-MBA
SDB-2F2 DB-2F2-PAC
SDB-2F2 DB-2F2-PAC
SDB-2F1 DB-2F1-MPL1
SDB-2F1 DB-2F1-MPL1
SDB-2F1 DB-2F1-MPL2
SDB-2F1 DB-2F1-MPL2
SDB-2F1 DB-2F1-MPL3
SDB-2F1 DB-2F1-MPL3
SDB-2F1 DB-2F1-MPL4
SDB-2F1 DB-2F1-MPL4
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
SDB-2F2 DB-2F2-KM-P
DB-UPS-2F DB-2F2-UPS-KM
DB-UPS-2F
SDB-2F1 DB-2F1-MM-P
SDB-2F1 DB-2F1-MM-P
SDB-2F1 DB-2F1-MM-P
SDB-2F1 DB-2F1-MM-P
SDB-2F1 DB-2F1-MM-P
SDB-2F1 DB-2F1-MM-P
SDB-2F1 DB-2F1-MM-P
SDB-2F1 DB-2F1-PM
DB-UPS-2F DB-2F1-UPS-PM
DB-UPS-2F DB-2F1-UPS-PM
DB-UPS-2F DB-2F1-UPS-PM
DB-UPS-2F DB-2F1-UPS-PM
DB-UPS-2F
OF SDB-GF2 DB-GF2-O&M
OF SDB-GF1 DB-GF1-TDS
OF SDB-GF1 DB-GF1-TDS
LO SDB-GF1 DB-GF1-OL
LO SDB-GF1 DB-GF1-OL
LO SDB-GF1 DB-GF1-OL
STO SDB-GF2 DB-GF2-COR
M SDB-2F1 ISO-2F1-MM
M SDB-2F2 ISO-2F2-KM
OF SDB-2F2 DB-2F2-O&C1
OF SDB-2F2 DB-2F2-TFA1
CP LSDB ISO-GF2-VF
KIT SDB-GF2 DB-GF2-KIT
TO SDB-GF2 DB-GF2-O&M
TO SDB-GF2 DB-GF2-O&M
TO SDB-GF2 DB-GF2-O&M
TO SDB-GF2 DB-GF2-O&M
TO SDB-GF2 DB-GF2-O&M
TO SDB-GF2 DB-GF2-O&M
TO SDB-GF2 DB-GF2-O&M
N SDB-1F2 DB-1F2-TS-1
N SDB-1F2 DB-1F2-TS-2
N SDB-1F1 DB-1F1-MBA
N SDB-1F1 DB-1F1-MSM
N SDB-1F2 DB-1F2-MBL
N SDB-1F1 DB-1F1-MBL
TO SDB-2F1 DB-2F1-COR2
TO SDB-2F1 DB-2F1-COR2
N SDB-2F1 DB-2F1-MPL1
N SDB-2F1 DB-2F1-MPL3
N SDB-2F1 DB-2F1-MPL4
N SDB-2F2 DB-2F2-MSK
N SDB-2F2 DB-2F2-PAC
N SDB-GF1 ISO-GF1-WSB
MDB MSSB-RT-BP
SMDB MSSB-1MF-RWBP
SMDB MSSB-1MF-WTP
SDB-GF1 ISO-GF1-SLP1
SDB-GF1 ISO-GF1-SLP2
SDB-GF2 ISO-GF2-SLP3
LSDB MSSB-1MF-FP
LSDB MSSB-1MF-FP
LT MSSB-2F-LIFT1
LT MSSB-2F-LIFT1
LT MSSB-2F-LIFT2
LT MSSB-2F-LIFT2
LT MSSB-2MF-LIFT3
LT MSSB-2MF-LIFT3
LT MSSB-2MF-LIFT3
LT MSSB-2MF-LIFT3
LT MSSB-2MF-LIFT4
Total MEP Equipment Load (kVA)
quipment for DB Sizing
Demand Demand
Equipment Power (kVA) Qty
Factor (kVA)
1164.51
Operating
kWh per
Hours per
month
day
4 3,177.6 PF 0.8
4 3,177.6 DIVERSITY 0.8
2 35.5
2 17.8
4 3,177.6
4 3,177.6
0 0.0
4 384.0
10 216.0
10 480.0
10 540.0
18 1,728.0
4 384.0
18 648.0
10 540.0
4 28.8
10 2,880.0
4 172.8
10 2,880.0
4 172.8
10 1,920.0
4 115.2
10 1,920.0
4 115.2
18 4,032.0
24 2,384.6
18 5,184.0
2 384.0
2 1,382.4
10 640.0
12 1,728.0
12 172.8
12 115.2
4 72.0
1 7.2
12 691.2
12 17,280.0
12 768.0
0 0.0
12 2,304.0
12 797.2
4 1,664.0
18 1,112.8
10 1,440.0
10 384.0
1 360.0
12 2,496.0
18 2,808.0
1 61.2
4 384.0
18 4,320.0
0 0.0
VENTI. FAN/AC DIVERSITY 0.8
10 291.8
12 665.3
9 972.0
4 12.1
4 12.1
4 27.6
4 27.6
4 8.1
4 6.7
4 27.6
2 11.5
12 665.3
12 665.3
12 243.9
12 334.7
12 243.9
12 487.9
4 13.4
4 12.1
12 332.6
12 332.6
12 332.6
12 332.6
12 243.9
12 1,152.0
4 72.0
4 72.0
4 288.0
2 57.6
2 57.6
2 105.6
0 0.0
0 0.0
5 960.0
5 960.0
5 4,160.0
5 4,160.0
5 4,160.0
5 4,160.0
5 4,160.0
5 4,160.0
5 4,160.0
0.0
3 576.0
154,388.8 kWh
Calculation for the DB Sizing
Load with 15% Simultaneous Demand Electric System
Level DB-Name Load (kVA) Spare (kVA) Factor (kVA) Ib (A) In (A) (Ph/V/Hz) Ib (A) < In (A) 5 < kVA
T/F 800 1154.7 1200 3/400/50 1
ATS 800 1154.7 1200
MDB (summary) 825.32 1191.3 1200 3/400/50 1
MDB 983.88 1131.46 0.7 792.02 1143.2 1200 3/400/50 1
MDB SMDB 537.33 617.93 0.7 432.55 624.4 630 3/400/50 1
GEN-1 200 288.7 400 3/400/50 1
GEN-2 200 288.7 400 3/400/50 1
GEN-3 200 288.7 400 3/400/50 1
GEN-4 110 158.8 250 3/400/50 1
GEN-5 10 14.4 32 3/400/50 1 SDB SMDB MDB
GDB 710 1024.83 1200 3/400/50 1 SDB Load (kVA) D. F Demand Load (kVA) D. F Demand Load (kVA) D. F Demand
APFCR 250 541 630 3/400/50 1 SDB-GF2 131.42 0.6 78.85 638.08 0.7 446.65 1047.37 0.7 733.16
Ground Floor + Mezzanine SDB-1F2 76.46 0.8 61.17
MDB SDB-GF1 92.51 106.39 0.6 63.83 92.1 100 3/400/50 1 1 SDB-2F2 347.86 0.7 243.50
DB-GF1-OL 11.38 13.09 1 13.09 18.9 32 3/400/50 1 1 MSSB-1MF-RWBP 1.08 1 1.08
DB-GF1-MUB 1.11 1.28 1 1.28 5.6 32 1/230/50 1 0 MSSB-1MF-WTP 4.31 1 4.31
DB-GF1-OD 3.63 4.17 1 4.17 6.0 32 3/400/50 1 0 OD MSSB-2MF-LIFT3 199.33 1 199.33
DB-GF1-COR 45.33 52.13 1 52.13 75.2 100 3/400/50 1 1 MSSB-2MF-LIFT4 49.83 1 49.83
DB-GF1-TDS 6.39 7.35 1 7.35 10.6 32 3/400/50 1 1 SDB-GF1 106.39 0.6 63.83
DB-GF1-FCC 4.88 5.61 1 5.61 8.1 32 3/400/50 1 1 SDB-1F1 126.86 0.8 101.49
DB-GF1-TR 0.03 0.04 1 0.04 0.2 32 1/230/50 1 0 SDB-2F1 272.79 0.6 163.67
DB-GF1-SH 0.29 0.34 1 0.34 0.5 32 3/400/50 1 0 SH MSSB-2F-LIFT1 23.00 1 23.00
ISO-GF1-SLP1 1.50 1.73 0.8 1.38 2.0 16 3/400/50 1 0 ISO MSSB-2F-LIFT2 99.67 1 99.67
ISO-GF1-SLP2 1.50 1.73 0.8 1.38 2.0 16 3/400/50 1 0 ISO MSSB-RT-BP 1.08 1 1.08
ISO-GF1-WSB 5.00 5.75 1 5.75 8.3 16 3/400/50 1 1 DB-UPS-2F 89.87 0.9 80.88
81.05 92.51 LSDB 67.10 1 67.10
SMDB MSSB-1MF-WTP 3.75 4.31 0.8 3.45 5.0 16 3/400/50 1 0.00 MSSB
SMDB MSSB-1MF-RWBP 0.94 1.08 0.8 0.86 1.2 16 3/400/50 1 0 MSSB
E16 GEN-1 GDB 15 288.68 400 4Cx185 Sqmm Cu/XLPE/PVC without earth 456 1 1.00 456.00 1 456.00 0.26 1.13 0.28 0.28 1 0 1 Multcore, Cable Ladder System. One dia space.
E16 GEN-2 GDB 15 288.68 400 4Cx185 Sqmm Cu/XLPE/PVC without earth 456 1 1.00 456.00 1 456.00 0.26 1.13 0.28 0.28 1 0 1 Multcore, Cable Ladder System. One dia space.
E16 GEN-3 GDB 15 288.68 400 4Cx185 Sqmm Cu/XLPE/PVC without earth 456 1 1.00 456.00 1 456.00 0.26 1.13 0.28 0.28 1 0 1 Multcore, Cable Ladder System. One dia space.
E17 GEN-5 DB-GF2-FS 35 14.43 32 4Cx10 Sqmm Cu/PVC/PVC without earth 60 1 1.00 60.00 1 60.00 3.8 1.92 0.48 0.48 3 0 1 Multcore, Cable Ladder System. One dia space.
E1 GDB MDB 50 1024.83 1200 4Cx4x240 Sqmm AL/XLPE/PVC without earth 409 1 0.75 306.75 4 1227.00 0.31 3.97 0.99 1.27 2 0 1 Multcore, Cable Ladder System. One dia space.
F1 GDB LSDB 50 96.85 100 4Cx25 Sqmm Cu/FR 127 1 1.00 127.00 1 127.00 1.65 7.99 2.00 2.00 4 0 1
E0 TF MDB 110 1143.22 1200 4Cx6x240 Sqmm AL/XLPE/SWA without earth 418 1 0.53 221.54 6 1329.24 0.31 5.68 15.68 14.73 6.50 1.62 1.62 2 0 1 Multcore, Cable Tray System, In trench
TF ATS 15 1154.73 1200 4Cx4x240 Sqmm Cu/XLPE/SWA without earth 546 1 0.63 343.98 4 1375.92 0.21 0.91 0.23 0.23 1 0 1
GDB ATS 20 1024.83 1200 4Cx4x240 Sqmm Cu/XLPE/PVC without earth 538 1 1.00 538.00 4 2152.00 0.31 1.59 0.40 0.40 1 0 1
ATS MDB 65 1143.22 1200 3Cx4x240 Sqmm Cu/XLPE/PVC without earth 538 1 1.00 538.00 3 1614.00 0.31 7.68 1.92 2.32 2 0 0
F0 LSDB MSSB-1MF-FP 110 79.43 100 4Cx35 Sqmm Cu/FR 158 1 1.00 158.00 1 158.00 1.15 126.50 142.18 1.62 10.05 2.51 4.14 4 1 0 Multcore, Cable Ladder System. One dia space.
F2 LSDB ISO-GF2-VF 145 4.79 16 4Cx4 Sqmm Cu/FR 34 1 1.00 34.00 1 34.00 9.5 1377.50 1393.18 0.17 6.60 1.65 3.27 4 1 1 Multcore, Cable Ladder System. One dia space.
E4 MDB SMDB 70 624.35 630 4Cx3x240 Sqmm Cu/XLPE/PVC 538 1 1.00 538.00 3 1614.00 0.21 4.90 20.58 11.22 3.06 0.76 2.39 2.7 0 1 Multcore, Cable Ladder System. One dia space.
E6 MDB APFCR 10 541.28 630 4Cx2x120 Sqmm Cu/XLPE/PVC 346 1 1.00 346.00 2 692.00 0.37 1.85 17.53 13.17 1.00 0.25 1.87 3 0 1 Multcore, Cable Tray System. One dia space.
E8 MDB SDB-GF1 5 92.14 100 4Cx50 Sqmm Cu/XLPE/PVC 192 1 1.00 192.00 1 192.00 0.87 4.35 20.03 11.53 0.40 0.10 1.72 3 0 1 Multcore, Cable Ladder System. One dia space.
E8 MDB SDB-1F1 15 146.49 160 4Cx50 Sqmm Cu/XLPE/PVC 192 1 1.00 192.00 1 192.00 0.87 13.05 28.73 8.04 1.91 0.48 2.10 3 0 1 Multcore, Cable Ladder System. One dia space.
E5 MDB SDB-2F1 20 236.25 250 4Cx185 Sqmm Cu/XLPE/PVC 456 1 1.00 456.00 1 456.00 0.26 5.20 20.88 11.06 1.23 0.31 1.93 3 0 1 Multcore, Cable Ladder System. One dia space.
E13 MDB MSSB-2F-LIFT1 60 19.92 63 4Cx6 Sqmm Cu/PVC/PVC 43 1 1.00 43.00 1 43.00 6.4 384.00 399.68 0.58 7.65 1.91 3.54 4 0 1 Multcore, Cable Ladder System. One dia space.
E11 MDB MSSB-2F-LIFT2 40 86.32 250 4Cx16 Sqmm Cu/XLPE/PVC 100 1 1.00 100.00 1 100.00 2.5 100.00 115.68 2.00 8.63 2.16 3.78 4 0 1 Multcore, Cable Ladder System. One dia space.
E13 MDB MSSB-RT-BP 90 1.08 16 4Cx6 Sqmm Cu/PVC/PVC 43 1 1.00 43.00 1 43.00 6.4 576.00 591.68 0.39 0.62 0.16 1.78 4 1 1 Multcore, Cable Ladder System. One dia space.
E10 MDB DB-UPS-2F 65 116.75 160 4Cx25 Sqmm Cu/XLPE/PVC 127 1 1.00 127.00 1 127.00 1.65 107.25 122.93 1.88 12.52 3.13 4.75 4 0 0 Multcore, Cable Ladder System. One dia space.
E8 SMDB SDB-GF2 40 113.81 160 4Cx50 Sqmm Cu/XLPE/PVC 192 1 1.00 192.00 1 192.00 0.87 34.80 55.38 4.17 3.96 0.99 3.38 3 0 0 Multcore, Cable Ladder System. One dia space.
E10 SMDB SDB-1F2 5 88.29 100 4Cx25 Sqmm Cu/XLPE/PVC 127 1 1.00 127.00 1 127.00 1.65 8.25 28.83 8.01 0.73 0.18 2.57 3 0 1 Multcore, Cable Ladder System. One dia space.
E7 SMDB SDB-2F2 40 351.47 400 4Cx120 Sqmm Cu/XLPE/PVC 346 1 1.00 346.00 1 346.00 0.37 14.80 35.38 6.53 5.20 1.30 3.69 3 0 0 Multcore, Cable Ladder System. One dia space.
E13 SMDB MSSB-1MF-WTP 60 4.98 16 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 384.00 404.58 0.57 1.91 0.48 2.87 3 1 1 Multcore, Cable Tray System. One dia space.
E13 SMDB MSSB-1MF-RWBP 60 1.24 16 4Cx6 Sqmm Cu/PVC/PVC 43 1 1.00 43.00 1 43.00 6.4 384.00 404.58 0.57 0.48 0.12 2.51 3 1 1 Multcore, Cable Ladder System. One dia space.
E10 SMDB MSSB-2MF-LIFT3 40 172.63 400 4Cx25 Sqmm Cu/XLPE/PVC 127 1 1.00 127.00 1 127.00 1.65 66.00 86.58 2.67 11.39 2.85 5.24 4 0 0 Multcore, Cable Ladder System. One dia space.
E11 SMDB MSSB-2MF-LIFT4 110 43.16 100 4Cx16 Sqmm Cu/XLPE/PVC 100 1 1.00 100.00 1 100.00 2.5 275.00 295.58 0.78 11.87 2.97 5.36 4 0 0 Multcore, Cable Ladder System. One dia space.
E13 SDB-GF1 DB-GF1-OL 70 18.90 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 448.00 468.03 0.49 8.46 2.12 3.84 4 1 1 Multcore, Cable Tray System. One dia space.
E13 SDB-GF1 DB-GF1-OD 50 6.02 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 320.00 321.72 0.72 1.93 0.48 2.21 4 1 1
E10 SDB-GF1 DB-GF1-COR 25 75.25 100 4Cx25 Sqmm Cu/XLPE/PVC 127 1 0.91 115.57 1 115.57 1.65 41.25 42.97 5.37 3.10 0.78 2.50 4 1 1
E13 SDB-GF1 DB-GF1-TDS 15 10.61 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 96.00 97.72 2.36 1.02 0.25 1.98 4 1 1
Ground
E2 SDB-GF1 DB-GF1-SH 120 0.49 32 4Cx6 Sqmm Cu/PVC/SWA 43 1 0.91 39.13 1 39.13 6.4 768.00 769.72 0.30 0.37 0.16 1.89 4 1 1
E3 SDB-GF1 DB-GF1-TR 120 0.17 32 2Cx6 Sqmm Cu/PVC/SWA 51 1 0.91 46.41 1 46.41 7.3 876.00 877.72 0.15 0.15 0.06 1.79 4 1 1
E15 SDB-GF1 DB-GF1-MUB 110 5.57 32 2Cx6 Sqmm Cu/PVC/PVC 51 1 0.91 46.41 1 46.41 7.3 803.00 804.72 0.17 4.47 1.94 3.67 4 1 1
E13 SDB-GF1 ISO-GF1-SLP1 120 1.99 16 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 768.00 769.72 0.30 1.53 0.67 2.39 4 1 1
E13 SDB-GF1 ISO-GF1-SLP2 35 1.99 16 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 224.00 225.72 1.02 0.45 0.19 1.92 4 1 1
E11 SDB-GF1 ISO-GF1-WSB 35 8.30 16 4Cx16 Sqmm Cu/XLPE/PVC 80 1 0.91 72.80 1 72.80 2.4 84.00 85.72 2.69 0.70 0.30 2.03 4 1 1
E13 SDB-GF2 DB-GF2-O&M 20 7.93 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 128.00 183.38 1.26 1.02 0.25 3.63 4 1 1 Multcore, Cable Tray System. One dia space.
E10 SDB-GF2 DB-GF2-COR 10 81.11 100 4Cx25 Sqmm Cu/XLPE/PVC 127 1 0.91 115.57 1 115.57 1.65 16.50 71.88 3.21 1.34 0.33 3.71 4 1 1 (Table 4C4, Installation Method 31)
E13 SDB-GF2 DB-GF2-CAN 55 3.59 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 352.00 407.38 0.57 1.26 0.32 3.70 4 1 1
Ground
E13 SDB-GF2 DB-GF2-OD1 25 1.98 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 160.00 215.38 1.07 0.32 0.14 3.52 4 1 1
E15 SDB-GF2 DB-GF2-DRR 35 3.44 32 2Cx6 Sqmm Cu/PVC/PVC 51 1 0.91 46.41 1 46.41 7.3 255.50 310.88 0.43 0.88 0.38 3.76 4 1 1
E11 SDB-GF2 DB-GF2-KIT 50 31.52 40 4Cx16 Sqmm Cu/XLPE/PVC 80 1 0.91 72.80 1 72.80 2.4 120.00 175.38 1.32 3.78 0.95 4.32 4 1 0
E13 SDB-GF2 ISO-GF2-SLP3 70 3.65 16 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 448.00 503.38 0.46 1.64 0.41 3.79 4.2 1 1
E13 SDB-GF1 DB-GF1-FCC 15 8.09 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 96.00 116.03 1.99 0.78 0.34 2.06 4 1 1
1 Mezzanine
E13 SDB-GF2 DB-GF2-LO1 45 7.47 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 288.00 308.03 0.75 2.15 0.54 3.92 4 1 1
E13 SDB-GF2 DB-GF2-LO2 75 7.76 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 480.00 500.03 0.46 3.72 0.93 4.31 4 1 0
E15 SDB-GF2 DB-GF2-GR 65 4.33 32 2Cx6 Sqmm Cu/PVC/PVC 51 1 0.91 46.41 1 46.41 7.3 474.50 494.53 0.27 2.05 0.89 4.27 4 1 0
E13 SDB-GF2 DB-GF2-FS 25 17.37 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 160.00 180.03 1.28 2.78 0.69 4.07 4 1 0
E13 SDB-1F1 DB-1F1-MSM 25 5.55 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.98 42.14 1 42.14 6.4 160.00 188.73 1.22 0.89 0.22 2.32 4 1 1 Multcore, Cable Tray System. One dia space.
E11 SDB-1F1 DB-1F1-MBA 25 46.89 63 4Cx16 Sqmm Cu/XLPE/PVC 80 1 1.00 80.00 1 80.00 2.4 60.00 88.73 2.60 2.81 0.70 2.81 4 1 1 (Table 4C4, Installation Method 31)
1 Floor
E13 SDB-1F1 DB-1F1-MBL 40 11.00 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.98 42.14 1 42.14 6.4 256.00 284.73 0.81 2.82 0.70 2.81 4 1 1
E15 SDB-1F1 DB-1F1-COR 30 7.24 32 2Cx6 Sqmm Cu/PVC/PVC 51 1 0.98 49.98 1 49.98 7.3 219.00 247.73 0.54 1.59 0.69 2.79 4 1 1
E10 SDB-1F1 ISO-1F1-BM 50 93.37 100 4Cx25 Sqmm Cu/XLPE/PVC 127 1 1.00 127.00 1 127.00 1.65 82.50 111.23 2.08 7.70 1.93 4.03 4 1 0
E13 SDB-1F2 DB-1F2-MBL 45 7.64 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 288.00 316.83 0.73 2.20 0.55 3.12 4 1 1
1 Floor
E10 SDB-1F2 DB-1F2-COR 30 69.97 100 4Cx25 Sqmm Cu/XLPE/PVC 127 1 0.91 115.57 1 115.57 1.65 49.50 78.33 2.95 3.46 1.51 4.08 4 1 0
E13 SDB-1F2 DB-1F2-TS-1 50 10.02 32 4Cx6 Sqmm Cu/PVC/PVC 42 1 0.91 38.22 1 38.22 6.4 320.00 348.83 0.66 3.21 1.39 3.97 4 1 1
E13 SDB-1F2 DB-1F2-TS-2 20 8.34 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 128.00 156.83 1.47 1.07 0.27 2.84 4 1 1
E12 SDB-2F1 DB-2F1-MPL1 35 35.22 40 4Cx10 Sqmm Cu/PVC/PVC 60 1 0.91 54.60 1 54.60 3.8 133.00 153.88 1.50 4.68 1.17 3.10 4 1 1 Multcore, Cable Tray System. One dia space.
E12 SDB-2F1 DB-2F1-MPL2 30 31.08 32 4Cx10 Sqmm Cu/PVC/PVC 60 1 0.91 54.60 1 54.60 3.8 114.00 134.88 1.71 3.54 0.89 2.82 4 1 1 (Table 4C4, Installation Method 31)
E13 SDB-2F1 DB-2F1-MPL3 50 24.11 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 320.00 340.88 0.68 7.72 1.93 3.86 4 1 1
E13 SDB-2F1 DB-2F1-MPL4 25 23.26 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 160.00 180.88 1.28 3.72 0.93 2.86 4 1 1
E15 SDB-2F1 DB-2F1-MM-L 40 9.44 32 2Cx6 Sqmm Cu/PVC/PVC 51 1 0.91 46.41 1 46.41 7.3 292.00 312.88 0.42 2.76 1.20 3.13 4 1 1
2 Floor
E10 SDB-2F1 DB-2F1-MM-P 40 112.32 160 4Cx25 Sqmm Cu/XLPE/PVC 127 1 0.91 115.57 1 115.57 1.65 66.00 86.88 2.66 7.41 1.85 3.78 4 0 1
E15 SDB-2F1 DB-2F1-COR1 30 6.04 32 2Cx6 Sqmm Cu/PVC/PVC 51 1 0.91 46.41 1 46.41 7.3 219.00 239.88 0.55 1.32 0.58 2.51 4 1 1
E13 SDB-2F1 DB-2F1-COR2 50 2.90 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 320.00 340.88 0.68 0.93 0.23 2.16 4 1 1
E13 SDB-2F1 DB-2F1-PM 50 21.88 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 320.00 340.88 0.68 7.00 1.75 3.68 4 1 1
E10 SDB-2F1 ISO-2F1-MM 45 86.46 100 4Cx25 Sqmm Cu/XLPE/PVC 127 1 0.91 115.57 1 115.57 1.65 74.25 95.13 2.43 6.42 1.60 3.54 4 1 1
E11 DB-UPS-2F DB-2F1-UPS-PM 45 47.83 63 4Cx16 Sqmm Cu/XLPE/PVC 80 1 0.91 72.80 1 72.80 2.4 108.00 128.88 1.79 5.17 1.29 3.22 4 1 1
E14 SDB-2F2 DB-2F2-KM-L 40 12.74 32 2Cx10 Sqmm Cu/PVC/PVC 70 1 0.91 63.70 1 63.70 4.4 176.00 211.38 0.63 2.24 0.98 4.66 4 1 0 Multcore, Cable Tray System. One dia space.
E8 SDB-2F2 DB-2F2-KM-P 40 281.40 400 4Cx50 Sqmm Cu/XLPE/PVC 192 1 0.91 174.72 1 174.72 0.87 34.80 70.18 3.29 9.79 2.45 6.14 4 0 0 (Table 4C4, Installation Method 31)
E9 SDB-2F2 DB-2F2-MSK 45 73.46 100 4Cx35 Sqmm Cu/XLPE/PVC 158 1 0.91 143.78 1 143.78 1.15 51.75 87.13 2.65 3.80 0.95 4.64 4 1 0
2 Floor
E13 SDB-2F2 DB-2F2-PAC 35 11.02 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 224.00 259.38 0.89 2.47 0.62 4.31 4 1 0
E13 SDB-2F2 DB-2F2-O&C1 10 6.08 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 64.00 99.38 2.32 0.39 0.17 3.86 4 1 1
E10 SDB-2F2 ISO-2F2-KM 45 43.23 63 4Cx25 Sqmm Cu/XLPE/PVC 127 1 0.91 115.57 1 115.57 1.65 74.25 109.63 2.11 3.21 1.40 5.09 4.3 1 0
E13 DB-UPS-2F DB-2F2-UPS-KM 40 5.53 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.91 39.13 1 39.13 6.4 256.00 291.38 0.79 1.42 0.35 4.04 4 1 0
2 Mezzanine
E13 SDB-2F2 DB-2F2-TFA1 45 9.96 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.95 40.85 1 40.85 6.4 288.00 323.38 0.71 2.87 1.25 4.94 4.15 1 0 Multcore, Cable Tray System. One dia space.
E13 SDB-2F2 DB-2F2-TFA2 50 7.23 32 4Cx6 Sqmm Cu/PVC/PVC 43 1 0.95 40.85 1 40.85 6.4 320.00 355.38 0.65 2.31 1.01 4.70 4 1 0
Cable size (4C-sqmm) Runes Cable
200
50
50
75
50
200
100
300
75
50
150
100
100
75
50
50
150
50
75
200
50
150
100
50
75
50
50
100
50
450
100
75
50
50
50
75
50
50
450
450
300
450
75
50
450
450
450
50
50
50
200
50
100
75
50
75
50
50
50
50
50
POWER FACTOR CORRECTION CAPACITOR BANK
Uncompensated Power
Factor cos Φ of the
network 0.8
T/F
Loading (kVA) 825.32
Actual Power (kW) 660.26
Factor Qc (kVar) 278.18
Cap. Bank Rating (kVar) 250 0
Steps (kVar)
Generator kVA Fuel consumption at 100% (L/hr)
(Prime Rated)
182 44
182 44
182 44
100 23.8
Total Fuel requirement for 2 days
Selected Bulk Fuel tank capacity (L)
Total fuel for 48 hrs (L)
2112
2112
2112
1142.4
7478.4
15000
Cable Tray and Cable Ladder Calculation
Cable
Total Selecte
Tray /
From To Cables Number of d tray
Ladder
Cables size
Route
Cable Tray and Cable Ladder Calculation
Cable Total
No. of Total Cable With Selected
Cable Tray / Ladder Route Cables Diameter Number of
Cables Diameter Spare tray size
x2 Cables
Cable Ladder 4x1Cx240 Sqmm Cu/XLPE/SWA 16 32.8 524.8 16
(From T/F to MDB)
524.8 734.72 100 X 800
Cable Ladder 4Cx95 Sqmm Cu/XLPE/PVC 2 74 148
(From MDB to SDBs and MSSBs)
4Cx50 Sqmm Cu/XLPE/PVC 1 57.6 57.6
5
4Cx16 Sqmm Cu/PVC/PVC 1 39.6 39.6
4Cx10 Sqmm Cu/PVC/PVC 1 38.6 38.6
283.8 397.32 100 X 450
Cable Ladder 4Cx120 Sqmm Cu/XLPE/PVC 1 81.8 81.8
(From SMDB to SDBs,DBs and MSSBs) 1 74
4Cx95 Sqmm Cu/XLPE/PVC 74
4Cx50 Sqmm Cu/XLPE/PVC 1 57.6 57.6
4Cx35 Sqmm Cu/XLPE/PVC 1 50.6 50.6
4Cx25 Sqmm Cu/XLPE/PVC 2 45.8 91.6 14
4Cx10 Sqmm Cu/PVC/PVC 1 38.6 38.6
4Cx6 Sqmm Cu/PVC/PVC 4 36 144
2Cx16 Sqmm Cu/PVC/PVC 1 36.4 36.4
2Cx6 Sqmm Cu/PVC/PVC 2 26.4 52.8
627.4 878.36 100 X 900
Cable Tray 4Cx6 Sqmm Cu/PVC/PVC 4 36 144
(From SDB-GF1 to DBs) 1 32.2 8
2Cx10 Sqmm Cu/PVC/PVC 32.2
2Cx6 Sqmm Cu/PVC/PVC 3 26.4 79.2
255.4 357.56 50 X 450
Cable Tray 4Cx16 Sqmm Cu/PVC/PVC 1 39.6 39.6
(From SDB-GF2 to DBs at GF) 1 38.6
4Cx10 Sqmm Cu/PVC/PVC 38.6
4Cx6 Sqmm Cu/PVC/PVC 4 36 144 8
2Cx10 Sqmm Cu/PVC/PVC 1 32.2 32.2
2Cx6 Sqmm Cu/PVC/PVC 1 26.4 26.4
280.8 393.12 50 X 450
Cable Tray 4Cx6 Sqmm Cu/PVC/PVC 2 36 72
(From SDB-GF2 to DBs at GF-M) 4
2Cx6 Sqmm Cu/PVC/PVC 2 26.4 52.8
124.8 174.72 50 X 200
Cable Tray - 1 4Cx6 Sqmm Cu/PVC/PVC 2 36 72
(From SDB-1F1 to DBs) 4
2Cx6 Sqmm Cu/PVC/PVC 2 26.4 52.8
124.8 174.72 50 X 200
Cable Tray - 2 4Cx16 Sqmm Cu/PVC/PVC 1 39.6 39.6
(From SDB-1F1 to DBs) 2
4Cx25 Sqmm Cu/XLPE/PVC 1 45.8 45.8
85.4 119.56 50 X 150
Cable Tray 4Cx25 Sqmm Cu/XLPE/PVC 1 45.8 45.8
(From SDB-1F2 to DBs) 1 38.6
4Cx10 Sqmm Cu/PVC/PVC 38.6
7
4Cx6 Sqmm Cu/PVC/PVC 4 36 144
2Cx6 Sqmm Cu/PVC/PVC 1 26.4 26.4
254.8 356.72 50 X 450
Cable Tray 4Cx50 Sqmm Cu/XLPE/PVC 1 57.6 57.6
(From SDB-2F1 to DBs) 1 50.6
4Cx35 Sqmm Cu/XLPE/PVC 50.6
4Cx16 Sqmm Cu/PVC/PVC 3 39.6 118.8 10
4Cx10 Sqmm Cu/PVC/PVC 2 38.6 77.2
2Cx6 Sqmm Cu/PVC/PVC 3 26.4 79.2
383.4 536.76 50 X 600
Cable Tray 4Cx70 Sqmm Cu/XLPE/PVC 1 66.4 66.4
(From SDB-2F2 to DBs at 2F) 2 36 5
4Cx6 Sqmm Cu/PVC/PVC 72
2Cx10 Sqmm Cu/PVC/PVC 2 32.2 64.4
202.8 283.92 50 X 300
Cable Tray 4Cx25 Sqmm Cu/XLPE/PVC 1 45.8 45.8
(From SDB-2F2 to DBs at 2F-M) 1 38.6
4Cx10 Sqmm Cu/PVC/PVC 38.6
4
4Cx6 Sqmm Cu/PVC/PVC 1 36 36
2Cx16 Sqmm Cu/PVC/PVC 1 36.4 36.4
156.8 219.52 50 X 300
Cable Ladder 4Cx240 Sqmm Cu/XLPE/PVC 3 113.4 340.2
(From GENs to Duct) 4
4Cx10 Sqmm Cu/PVC/PVC 1 38.6 38.6
378.8 606.08 100 X 800
Cable Tray 4Cx10 Sqmm Cu/PVC/PVC 1 38.6 38.6 1
(From GDB to MDB)
38.6 54.04 50 X 75
V 400
S 800
Zs 5%
Z 0.010
635 1,165.14
46%
Bill Estimation
kWh/month LKR Per month
Lighting 12030 135,061.38
General power 969 10,884.36
MEP 154389 1,733,335.98
Total (Cost of energy) 167388 1,879,281.72