12 Pump shut-off head ft 714.16 695.80 » Based on FLOWSERVE online Affinity software (Curve
No.EC-1728), this model is having lowest head (Shut-off
head) rise from rated head which is 29.3% and efficiency of
pump is 73%
» Based on RUHRPUMPEN online software (Curve No.VTP-
30D-1440-1180), this model is having lowest head (Shut-off
head) rise from rated head which is 25.64% and efficiency
of pump is 67%.
13 Pump shut-off pressure PSIg 247.33 240.97
14 Maximum Pump Discharge PSIg 262.04 255.68 maximum suction pressure + the pump shut-off head [As
Pressure per BMPS-A3, Clause No. 7.1]
15 MAWP of Gasoline Pipe Line PSIg 250.0
(Sea Lines)
Conclusion: Based on online available pump model, maximum pump discharge pressure is exceeding the MAWP of gasoline pipe line.
Hence, we shall install a full flow relief valve in the discharge header.