INSTALLED PANEL WEIGHT NON-LOAD BEARING THERMAL EXPANSION PREMIERE SERIES

Refer to Table on page 8 for Glass block panels are non-load COEFFICIENT AND Thinline™ SERIES
weight of panels installed with bearing; adequate provisions The thermal expansion coefficient All glass block illustrated are
mortar. Glass block panels must be made for support of of glass block is 47 x 10–7 /(ºF). Premiere Series Glass Block,
installed with the KWiK’N EZ® construction above these the 4" nominal thick products.
Rigid Track Silicone System are panels. Panels are mortared at DETAILED DRAWINGS Modify as necessary for
up to 25% lighter (weigh 25% the sill, with jamb and head Structural members illustrated Thinline™ Series, the 3"
less per square foot) than details designed to provide for on page 14 and other “detail” nominal thick units or
panels installed with mortar. building movement and lintel pages indicate principles of VISTABRIK® Solid Glass Block,
Local building codes should be deflection. The compressive construction. Member sizes 3" actual thickness. Pittsburgh
checked for any limits on panel strength (for information should be determined by Corning recommends that the
sizes or installation details. purposes only) of all hollow structural analysis to avoid use of the Thinline™ Series units
glass block is 400 to 600 psi.; excessive deflections. be limited to light commercial
of all THICKSET® Series Glass Maximum deflection should and residential applications.
Block is 2500 psi.; and of all not exceed L/600.
VISTABRIK® Series is 80,000 psi.

FINISHING UNITS
PREMIERE SERIES THINLINE™ SERIES
EndBlock™ Finishing Units HEDRON® Corner Unit TRIDRON 45° Block® Unit ENCURVE® Finishing Unit ARQUE® Block Unit EndBlock™ Finishing Unit

73/4" 73/4" 73/4"


73/4"

73/4"
73/4" 73/4"
37/8"

37/8"
11/4" 37/8"
73/4" 41/2"
37/8"
3 /8
7

5/
3 "
4
"

37/8" 37/8" 3 7/8" 31/8"


37/8"
37/8"
73/4" 53/4" 2 1/4 " " 33/4"
2 /4
1
53/4" 73/4" 53/4"
DECORA® & DECORA® & DECORA® & IceScapes® DECORA® & IceScapes® DECORA® & DECORA® & DECORA® Pattern
IceScapes® Patterns IceScapes® Patterns Patterns Patterns IceScapes® Patterns IceScapes® Patterns 8" High
8" High 8" High 8" High 8" High 8" Square 8" High Thinline™ Series Only
Premiere Series Premiere Series Premiere Series Premiere Series Premiere Series Premiere Series

a
a = 0.415 s GLASS BLOCK BETWEEN MAXIMUM PANEL DIMENSIONS*
d = 1.083 s d TRIDRON 45° BLOCK® Premiere Series Thinline™ Series VISTABRIK®
a (in.) s (in.) d (in.) A H W A H W A H W
(Sq.Ft.) (Ft.) (Ft.) (Sq.Ft.) (Ft.) (Ft.) (Sq.Ft.) (Ft.) (Ft.)
s None 4.75 11.45 12.40
EXTERIOR** 144 20 25 85 10 15 100 10 10
1 - 4" x 8" x 4" 8.75 21.08 22.83
INTERIOR 250 20 25 150 10 15 150 10 15
1 - 6" x 8" x 4" 10.75 25.90 28.05
A = Area H = Height W = Width
1 - 8" x 8" x 4" 12.75 30.72 33.27 * Uniform Building Code (UBC) limits exterior height and width to 15 feet.
** All exterior areas and dimensions are based on 20 psf design windload with 2.7 safety factor.
1 - 4" x 8" x 4" + 1 - 8" x 8" x 4" 16.75 40.36 43.71
2 - 8" x 8" x 4" 20.75 50.00 54.15
1 - 4" x 8" x 4" + 2 - 8" x 8" x 4" 24.75 59.64 64.59 MORTAR MIX AND ESTIMATING TABLES
An optimum mortar mix for installing Pittsburgh Corning Glass Block is:
3 - 8" x 8" x 4" 28.75 69.28 75.03
Portland Cement Lime Sand
1
1 Part ⁄2 Part 3.4 Parts
1.0 cubic foot 0.5 cubic foot 3.4 cubic feet

Columns can be All-TRIDRON 45° Block® (left)


NUMBER OF BLOCK FOR 100 SQ. FT. PANEL
or interspersed with 4" x 8" or 8" x 8" glass block. Block Sizes (Nominal) 6" 8" 12" 4" x 8" 6" x 8"
NOTE: All mortar joints are 1/4." Number of Block 400 225 100 450 300

9
PHYSICAL & DESIGN DATA
INSIDE RADIUS MINIMUMS FOR CURVED PANEL WIND LOAD RESISTANCE – MORTAR SYSTEM
CONSTRUCTION (Based on Standard Nominal 4" Thick Premiere Series Glass Block.
Installed with mortar. Based on 2.7 Safety Factor)

lock)
ck)
lo

are B
rc
8" B

°A
160
90

Load, Wind Speed


"x

Squ
psf (V), mph
-4

)
lock
t 4' x 4'
Fla
6"
us

20 78
s-
di

eB
Ra Curved 40 111
iu

.
Min u ar
ad

60 135
(32"
.R

80 156
Sq
120
in

Max. Wind Load, Pounds/Sq. Ft.


M 100 175
8"

4' x 4'
/"
1 2 120 192
s-

(48 140 207


iu

160 221
R ad

PANEL
n.

i
M REINFORCING SAF
5" 80 ETY
P = 0.00327V2
(6
4' x 8' FAC
Intermediate Expansion Joints & Supports TO
5' x 10' R2
Curved .7
k)

10' x 10'
oc

Bl 40 6' x 12' 14' x 7'4"


e
NOT TO SCALE ar
qu 7'4" x 7'4"
"S 12' x 12'
12
iu s- 10' x 20'
16' x 16'
ad VISTABRIK® & THINLINE™ Series
.R
/" Min S.F. = 2.7 10' x 10'
1 2 Curved 0
(98
0 20 40 60 80 100 120 140 160 180 200 220 240 260

Area of Panel in Sq. Ft.


Intermediate Expansion Joints
F la & Supports
t t
Fla
Curved

160 WIND LOAD


Max. Wind Load in Pounds/Sq. Ft.
4' x 4'
RESISTANCE –
140
KWiK’N EZ® SYSTEM
120 (Based on Standard Nominal
4" Thick Premiere Series
NOTES: 100 Glass Block Installed with
RADIUS MINIMUMS 1. It is suggested that curved areas be KWiK’N EZ® Silicone System).
FOR CURVED PANEL CONSTRUCTION separated from flat areas by 4' x 8' Based on 2.0 Safety Factor.
80
Block Inside Number Vertical Joint Thickness intermediate expansion joints and
Size Radius of Blocks In Inches supports, as indicated in these 60 6' x 6'
Inches in 90º Arc Inside Outside drawings. S.
F=
4" x 8" 32 13 1
/8 5
/8 2. When straight, ladder-type reinforcing 40 2.
0 6' x 12'
is used on curved walls, the innermost
6" x 6" 483⁄8 13 1
/8 5
/8 parallel wire may be cut periodically 20 8' x 8'
1 5
8" x 8" 65 13 /8 /8 and bent to accommodate the
12" x 12" 981⁄2 13 1
/8 5
/8 curvature of the wall. 0
0 10 20 30 40 50 60 70 80 90 100

Area of Panel in Sq. Ft.

RESISTANCE TO SURFACE CONDENSATION


Outside Temperature in Degrees (°F)
ck -30.00 -20.00 -10.00 0.00 10.00 20.00 30.00 40.00
" Blo 80.00
x8
8" Premiere Series
th Thinline™ Series
wi VISTABRIK®
ck ck
% of Interior Relative Humidity

lo Blo flat glass single-glazed


8"
B

x
®

6" 60.00
E

th
QU

wi
AR

k Premiere Series
oc lock
Bl 8" B

x
®

4"
ius

Thinline™ Series
E

th
QU

wi
ad

k 40.00
AR
"R

oc
Bl
38

VISTABRIK®
®
ius

E
QU
Rad

flat glass single-glazed


AR
31"

s—

20.00
® Block
E
adiu

QU Chart based on inside


AR temperature of 70° F.
25" R

s—
diu

0.00
12" Ra

Example: At a relative humidity of 40%, an outside temperature of approximately -3 ºF will


cause condensation on Premiere Series Glass Block or approximately 3 ºF above zero on Thinline™
Series block. Under the same conditions, condensation will form on a single-glazed flat glass
ARQUE® Block used along with other Pittsburgh Corning Block sizes, allows you to form consistent
window at 34 ºF above zero.
curves of various radii. Radii shown are to inside face of curve.

10
FIRE RATINGS
FIRE RATINGS AND CODE INFORMATION
All sizes (exceptions listed below) of • THICKSET® 60 Block are listed for • Framing and support of the rated Laboratories current issue of the Fire
Premiere Series and Thinline™ Series use as 45- or 60-minute fire rated glass block window assembly shall Resistance Directory – Volume 3.
glass blocks have at least a 45 minute window assemblies in panels up to be provided with double-studding A listing of our products can also be
fire rating when used as a window 100 square feet. at the jamb locations with height of viewed on the Underwriters
assembly within a one hour fire-rated • THICKSET® 90 Block and supporting wall limited to no more Laboratories Website at www.ul.com.
wall assembly. All THICKSET® 90 VISTABRIK® Solid Glass Block than 3 feet. • U.L. Classification: R2556
(thick-faced) and solid glass blocks are all listed for use as 45-, 60- or (For Glass Block)
have fire ratings of up to 90 minutes, 90-minute fire rated window 90-MINUTE RATED CONSTRUCTION • Underwriters Laboratories of
and the THICKSET® 60 and ESSEX® assemblies in panels up to 100 Canada Guide Number 230I7
AA Pattern glass blocks have fire • Where permitted by building codes,
square feet. (For Glass Block)
ratings of up to 60 minutes, when all 90-minute rated Pittsburgh
• Where permitted by building codes, Corning Glass Block may be used • U.L. Classification: R18572
used as window assemblies and when glass block fire-rated window (For Plastic Spacers)
permitted by code. in masonry walls only.
assemblies having a fire resistance • In accordance with NFPA 80,
• 90-minute rated glass block
rating of not less than 45 minutes Chapter 14
window assemblies must be framed
Pittsburgh Corning Glass Block units may be used as “opening
and anchored with 1/4" thick steel
that are not fire-rated: protectives.” These assemblies
(not aluminum) channel-type CITY CODE APPROVALS
• All 12" x 12" sizes shall not exceed 25% of the wall
restraints or masonry chases. The • New York City Materials and
• All DELPHI®‚ pattern block areas separating a tenancy from
use of panel anchor construction Equipment Acceptance MEA
• All HEDRON® Corner block, a corridor or a corridor from an
is not permitted.
TRIDRON 45º Block® units, enclosed vertical opening or one 406- 90-M. Vol.IV
fire-rated area from another fire- • The use of a fire retardant type
EndBlock®, ENCURVE® and • Los Angeles Research Report
rated area. sealant for head and jamb locations
ARQUE® finishing units RR-24486
is required.
• All paver units • Exception: Although glass block • Eugene, OR, “Approved Glass
masonry systems have been tested • Specifications and construction
• VISTABRIK® Corner Block Products, Storm Windows, and
as window assemblies (not wall details of such panels are as per
Insulated Window Units”
assemblies), they may be used Pittsburgh Corning Corporation
recommendations. • Dade County Acceptance
PANEL SIZES AND DIMENSION as one hour fire partitions as
LIMITATIONS • Twice the typical thickness • State of Florida Approvals
required for corridors in the • Texas Department of Insurance
Pittsburgh Corning Glass Block listed enclosure of atriums only when (3/4" total) of expansion material
is required at head and jamb WIN #s 62, 63, and 64
above have been tested and classified sprinkler protection is provided
by Underwriters Laboratories® (UL®) on occupied sides. locations.
for use as fire-rated window BUILDING CODE AND NATIONAL
assemblies to panel sizes and 45-MINUTE RATED CURVED STANDARDS REFERENCES:
45- AND 60-MINUTE RATED
dimension limitations listed below: CONSTRUCTION CONSTRUCTION • The BOCA National Building Code
• With the exception of all • The glass blocks noted under (N.B.C.)
• All 45- and 60-minute rated
12" x 12" sizes, finishing blocks, 90-minute rating and those • The Standard Building Code
Pittsburgh Corning Glass Block
corner blocks and the DELPHI® 8" x 8" x 4" sized glass block (SBCCI)
may be used in both masonry and
pattern block, all Premiere Series non-masonry (steel or wood stud noted under 45-minute rating are • The Uniform Building Code
and Thinline™ Series glass blocks in framing with gypsum board) walls. classified for use in masonry walls (U.B.C.)
panels up to 120 square feet in as curved window assemblies, • International Building Code (IBC)
• These rated glass block windows
masonry walls or 94 square feet in provided that the radius of the • Canadian Standards Association
may be framed and anchored
non-masonry walls are classified by assembly is at least twice the (CSA) A371-94 “Masonry
with either PC® Panel Anchor
Underwriters Laboratories‚ for use opening width (i.e. chord length). Construction for Buildings”
construction or channel-type
as 45-minute rated window • Canadian Standards Association
restraints.
assemblies. CODE COMPLIANCE (CSA) S304.1-94 “Masonry Design
• The use of a fire retardant type
• The Uniform Building Code (U.B.C.) for Buildings.”
sealant for head and jamb locations All of our fire-rated glass block
limits the area of 45-minute rated • ACI 530/ASCE 5/TMS 402
is required. products are listed in the Underwriters
window assemblies to 84 square “Building Code Requirements for
feet, with no dimension exceeding • Specifications and construction
details for such panels are as per Masonry Structures”
12 feet. These panels are usually
Pittsburgh Corning Corporation • ISO 9001:2000 Certification:
acceptable as window assemblies
recommendations. Manufacture test and distribution
for use in fire separation walls that
• Non-masonry, fire-rated steel stud of Pittsburgh Corning Glass Block
are rated one hour or less.
with gypsum board wall assemblies products.
must conform to UL® listed wall
assembly #U465.

FIRE RATINGS — GLASS BLOCK ASSEMBLIES


Premiere Series Glass Blocks, THICKSET® 60 Blocks, THICKSET® 90 Blocks and VISTABRIK® Solid Glass Block units have been tested and
classified by Underwriters Laboratories (UL®) for use in fire-rated window assemblies to panel sizes and dimension limitations as listed.

Masonry Wall Construction Non-Masonry Wall Construction


Panel Limitations Fire Rating Panel Limitations Fire Rating
Product Max. Area/Panel Max Ht. or Width 45 Min. 60 Min 90 Min. Max. Area/Panel Max Ht. or Width 45 Min. 60 Min.
Premiere Series 120 12 X 94 10.75 X
THICKSET® 60 and
100 10 X X 94 10.75 X X
ESSEX® AA Pattern
THICKSET® 90 100 10 X X X* 94 10.75 X X
VISTABRIK® 100 10 X X X* 94 10.75 X X
*1/4" steel channel. 3/4" thick expansion material at head and jambs, and fire retardant sealant are required.

11
ACCESSORIES TYPICAL CONSTRUCTION DETAILS
PANEL CONSTRUCTION PANEL ANCHOR CONSTRUCTION
PC® EXPANSION
USING VeriTru® SPACERS STRIP
PC® PANEL
Lintel Plate
PC® PANEL REINFORCING Panel Anchor Expansion Strip
The one-piece, all plastic ANCHOR
Sealant
VeriTru® Spacer speeds SEALANT
Lintel Plate
construction, assures uniform MORTAR
Sealant
placement and helps keep panel VeriTru® SPACER
SEE NOTE
flush. Can now be used in fire-
Expansion Strip
rated panels. Special spacers are Pittsburgh Corning Panel Anchor
Glass Block Unit
available for the VISTABRIK® Pittsburgh Corning
Glass Block Unit
and ARQUE® Block. VeriTru® Spacer
NOTE: This dimension is
determined by the anticipated
Sealant deflection of the structural
PC® PANEL REINFORCING, PANEL member above the glass block.

ANCHORS & EXPANSION STRIPS Expansion Strip Panel Reinforcing

PC® Panel Reinforcing (top) — in panels Panel Anchor

— is embedded horizontally in the 1


/4" Exp. Bolts Pittsburgh Corning
mortar joints between every other Two Per Anchor Glass Block Unit

course. PC® Panel Anchors (middle) are Mortar


used to tie Pittsburgh Corning Glass Block panels into the surrounding
Panel Reinforcing
framework when channels are not used. PC® Expansion Strips (bottom),
Wall framing shown here Mortar
made of white polyethylene, are inserted at the head and jambs. The strips for illustrative purposes
only. Wall framing can
Asphalt Emulsion
replace mortar at these locations to cushion the glass block and allow the be concrete, masonry,
wood, steel or any other
panel to expand and contract freely. structural surround.

THE KWiK’N EZ® RIGID TRACK


SILICONE SYSTEM
The KWiK’N EZ® Rigid Track spacer
design system allows you to easily install
glass block in many areas. Precision cut CHANNEL-TYPE RESTRAINT CONSTRUCTION
vertical spacers combine with the Angle Fastener
Lintel Plate

horizontal spacers to make installing your Pittsburgh Corning Glass Block Sealant Metal Angle
Channel 1 1
4 /4"–4 /2" Clear Opening
Fastener Expansion Strip
panel quicker and easier than ever before. Rigid Track spacers are Packing
Expansion Strip
4 1/4"–4 1/2" Clear Opening
available for use with either Thinline™ Series or Premiere Series Glass Block. Material
Metal Expansion Strip
Channel Angle Lintel Plate
Fastener Metal Angle
OTHER ACCESSORIES Sealant
Pittsburgh Corning SEE NOTE
Packing
Glass Block Unit Material 1" Min.
Additional materials — such as mortar, channels or framing, packing, Channel
Restraint Detail Sealant Pittsburgh Corning
sealants and asphalt emulsion are available from other manufacturers. Angle
Glass Block Unit
Restraint Detail

ProVantage™ INSTALLATION SYSTEM


NEW! Metal Channel
NOTE: This dimension is
determined by the anticipated
deflection of the structural
member above the glass block.
Sealant
Panel Reinforcing
Expansion Strip

Channel Fastener Pittsburgh Corning


Glass Block Unit
Mortar
Wall framing shown here
for illustrative purposes Panel Reinforcing
only. Wall framing can
be concrete, masonry, Mortar
wood, steel or any other
Unlike previous systems using silicone and spacers, the new ProVantage™ structural surround. Asphalt Emulsion
Installation System for use with Premiere Series glass blocks, can turn
corners, make radius walls, build showers and is suitable for interior or
exterior applications. The system utilizes spacers to align and hold the
blocks in place for easy assembly, and silicone is used to bond the spacer
and blocks together. The consistent, even-spaced joints are then finished
with a special tile grout resulting in a clean, smooth professional look.
For smaller straight wall panels, with 3-side support, silicone can be used
in the joints to provide an all-glass look.

12 Please go to www.pittsburghcorning.com for fully downloadable specifications.