Insert Known Values Below into the YELLOW Cells: FACEBOOK GROUP
(I) AMPS 0
(V) VOLTS 0
(P) WATTS 0
( R ) OHMS 0
(I) AMPS
#DIV/0! Volts / Ohms
#DIV/0! Watts / Volts
#DIV/0! Square Root of Watts / Ohms
(V) VOLTS
0 SQ Root of Watts x Ohms
0 Watts / Amps
0 Amps x Ohms
(P) WATTS
0 Volts x Amps
0 (Amps x Amps) x Ohms
#DIV/0! (Volts x Volts) / Ohms
( R ) OHMS
#DIV/0! Watts / (Amps x Amps)
#DIV/0! (Volts x Volts) / Watts
#DIV/0! Volts / Amps
15 ZAR Productions, LLC.
WEBSITE
CEBOOK GROUP
CONDUIT FILL CALCULATOR
QTY THHN MM^2 Total MM^2 40% Total
0 #14 6.258 0 / 0.4 0
0 #12 8.581 0 / 0.4 0
FPLR (SHLD)
0 #18-2 11.68 0 / 0.4 0
0 #18-4 14.65 0 / 0.4 0
0 #16-2 14.65 0 / 0.4 0
FPLR
0 #18-2 12.65 0 / 0.4 0
0 #18-4 17.16 0 / 0.4 0
0 #16-2 13.94 0 / 0.4 0
0 #14-2 24.06 0 / 0.4 0
0 #12-2 34.26 0 / 0.4 0
FPLP (SHLD)
0 #18-2 11.68 0 / 0.4 0
0 #18-4 16.39 0 / 0.4 0
0 #16-2 16.06 0 / 0.4 0
FPLP
0 #18-2 12.65 0 / 0.4 0
0 #18-4 16.39 0 / 0.4 0
0 #16-2 16.39 0 / 0.4 0
0 #14-2 20.45 0 / 0.4 0
0 #12-2 33.23 0 / 0.4 0
Match Color with EMT Conduit MM Area for Correct Conduit Size
UIT FILL CALCULATOR
WIRE AND CABLE
APPRXIMATE DIAMETER (MM^2) EMT CONDUIT
FPLP Non-Shielded Shielded NOMINAL INTERNAL DIAMETER (MM^2)
#18-2 12.65 11.68
#16-2 16.39 16.06 EMT MM
#14-2 20.45 1/2" 196
#12-2 33.23 3/4" 343
#18-4 16.39 16.39 1" 556
FPLR Non-Shielded Shielded 1 1/4" 968
#18-2 12.65 11.68 1 1/2" 1314
#16-2 13.94 14.65 2" 2165
#14-2 24.06 2 1/2" 3783
#12-2 34.26 3" 5701
#18-4 17.16 14.65 3 1/2" 7451
THHN 4" 9521
#14 6.258 NEC Article 358
#12 8.581
WEBSITE
FACEBOOK GROUP
for Correct Conduit Size Copyright 2015 ZAR Productions, LLC.
System Sensor SpectrAlert Series Voltage Drop Calculation Worksheet
www.firealarmsonline.com
FACEBOOK GROUP
HornStrobe Current Draw (mA) for Ceiling Standard and High CD HornStrobe Current Draw (mA) for Wall Sta
Strobe Current Draw (mA) for Ceiling Standard and High CD Strobe Current Draw (mA) for Wall Standar
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 18 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 18 AWG Strand
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 16 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 16 AWG Strand
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 14 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 14 AWG Strand
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 12 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 12 AWG Strand
0 TOTAL CURRENT 0
0 TOTAL CURRENT 0
0 TOTAL CURRENT 0
y HC Sounder Strobe Current Draw (mA)
0 TOTAL CURRENT 0
sonline.com
Wheelock Exceder Series Voltage Drop Calculation Worksheet
www.firealarmsonline.com
FACEBOOK GROUP
HornStrobe Current Draw (mA) for Ceiling Standard and High CD HornStrobe Current Draw (mA) for Wall Stan
0 0
Strobe Current Draw (mA) for Ceiling Standard and High CD Strobe Current Draw (mA) for Wall Standard
0 0
Horn Current Draw (mA) Mini Horn and LF Sounder Current Draw (mA
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 18 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 18 AWG Strand
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 16 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 16 AWG Strand
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 14 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 14 AWG Strand
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 12 AWG Solid
20.4 VDC - 0.000000 = 20.4000 Voltage Drop On Circuit with 12 AWG Strand
0 0
0 0
0 0
Device Type Totals:
Strobes Ceiling 0
Horn/Strobe Wall 0
Horn/Strobe Ceiling 0
Horns 0
Mini Horns/ LF 0
msonline.com
STROBE CALCULATOR FOR CEILING MOUNTED APPLIANCES
INPUT DATA HERE:
CEILING HEIGHT 30 FT
SQUARE ROOM SIZE 20 FT X FT
PRODUCT RATED CANDELA 75 CD
CIRCUMSCRIBED CIRCLE RADIUS 14.14 FT
INSRIBED CIRCLE RADIUS 10.00 FT
CIRCUMSCRIBED INSCRIBED
2
ANGLE U.L. REQ. CANDELA DIST. FLOOR X LM/FT DIST. FLOOR X LM/FT2
0 75.00 30.00 0.00 0.0833 30.00 0.00 0.0833
5 67.50 30.11 2.62 0.0744 30.11 2.62 0.0744
10 67.50 30.46 5.29 0.0727 30.46 5.29 0.0727
15 67.50 31.06 8.04 0.0700 31.06 8.04 0.0700
20 67.50 31.93 10.92 0.0662 29.24 10.92 0.0790
25 67.50 33.10 13.99 0.0616 23.66 13.99 0.1206
30 56.25 28.28 17.32 0.0703 20.00 17.32 0.1406
35 56.25 24.66 21.01 0.0925 17.43 21.01 0.1851
40 56.25 22.00 25.17 0.1162 15.56 25.17 0.2324
45 56.25 20.00 30.00 0.1406 14.14 30.00 0.2813
50 41.25 18.46 35.75 0.1210 13.05 35.75 0.2421
55 33.75 17.26 42.84 0.1132 12.21 42.84 0.2265
60 30.00 16.33 51.96 0.1125 11.55 51.96 0.2250
65 26.25 15.60 64.34 0.1078 11.03 64.34 0.2156
70 26.25 15.05 82.42 0.1159 10.64 82.42 0.2318
75 22.50 14.64 111.96 0.1050 10.35 111.96 0.2099
80 22.50 14.36 170.14 0.1091 10.15 170.14 0.2182
85 18.75 14.20 342.90 0.0930 10.04 342.90 0.1861
90 18.75 14.14 22610879.85 0.0938 10.00 22610879.85 0.1875
VERTICAL
ANGLE UL REQ. DIST. WALL Y LM/FT2
0 75.00 35.00 0.00 0.0612
5 67.50 35.13 3.06 0.0547
10 67.50 35.54 6.17 0.0534
15 67.50 36.23 9.38 0.0514
20 67.50 37.25 12.74 0.0487
25 67.50 35.49 16.32 0.0536
30 67.50 30.00 20.21 0.0750
35 48.75 26.15 24.51 0.0713
40 34.50 23.34 29.37 0.0634
45 25.50 21.21 35.00 0.0567
50 20.25 19.58 41.71 0.0528
55 16.50 18.31 49.99 0.0492
60 13.50 17.32 60.62 0.0450
65 12.00 16.55 75.06 0.0438
70 11.25 15.96 96.16 0.0442
75 9.75 15.53 130.62 0.0404
80 9.00 15.23 198.49 0.0388
85 9.00 15.06 400.05 0.0397
90 9.00 15.00 26379359.83 0.0400
ghtest profile.
STI VALUES
0 0.30 0.45 0.60 0.75 1.00
BAD POOR FAIR GOOD EXCELLENT
0 0.48 0.65 0.78 0.88 1.00
CIS VALUES
BATTERY CALCULA
RPS Stby. Current 0.091
Appliance Current 0
RPS Alarm Current 0.145
2.635242 Total Alarm Current 0.145
BATT REQUIRED
FACEBOOK GROUP
Copyright 2015 ZAR Productions, LLC. www.firealarmsonline.com
NAC #4
TOTALS A/V APPLIANCE MODEL QTY DRAW TOTALS
0 0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 0 = 0
0 TOTAL DRAW 0
0 TOTAL DISTANCE IN FEET 0
0 0 X 0 X 21.6 = 0
VOLTAGE DROP
0 0 / 14 AWG 4110 = Voltage Drop of 0
0 0 / 12 AWG 6530 = Voltage Drop of 0
VOLTAGE DROP PERCENTAGE
0 0 / 20.4 X 100 = VD% of 0
0 0 / 20.4 X 100 = VD% of 0
TOTAL POWER ON CIRCUIT 0.00 WATTS 0.00 WATTS 0.00 WATTS 0.00
LOAD RESISTANCE 0 OHMS 0 OHMS 0 OHMS 0
TOTAL WIRE LENGTH 0 FT. FT. FT.
WIRE SIZE 12 AWG 14 AWG 14 AWG 14
TOTAL WIRE RESISTANCE 0 OHMS 0 OHMS 0 OHMS 0
POWER LINE LOSS (dB) dB dB dB
CIRCUIT LOCATION
SIGNAL CIRCUIT SIGNAL CIRCUIT SIGNAL CIRCUIT SIGNAL CIRCUIT SIGNAL CIRCUIT
SPARE SPARE SPARE SPARE SPARE QTY
WATTS QTY WATTS QTY WATTS QTY WATTS QTY WATTS TOTAL
FACEBOOK GROUP
Copyright 2015 ZAR Productions, LLC. www.firealarmsonline.com
www.firealarmsonline.com
FACEBOOK GROUP
dBA Loss Factors
Insert Your Starting dB in the YELLOW Cell
No Modifying Factors Solid Core Door -26 dBa
dB dB
dB @ 10' 90 dB @ 10' 64
dB @ 20' 84 dB @ 20' 58
dB @ 40' 78 dB @ 40' 52
dB @ 80' 72 dB @ 80' 46
dB @ 160' 66 dB @ 160' 40
Hollow-Core Door, Air Gap -14 dBa Hollow-Core Door, No Air Gap -20 dBa
dB dB
dB @ 10' 76 dB @ 10' 70
dB @ 20' 70 dB @ 20' 64
dB @ 40' 64 dB @ 40' 58
dB @ 80' 58 dB @ 80' 52
dB @ 160' 52 dB @ 160' 46
FACP INFO
FACP Manufacturer
FACP Model
Inputs:
ADDRESSABLE
How Many SLC Loops
What Protocol
Software Version
CONVENTIONAL
How Many Zones
Are the Detectors: 2-WIRE 4-WIRE
Outputs:
How Many Onboard Relays
How Many NAC Circuits
What Brand Appliances
Audible Type HORN SPKR CHIME BELL
Visible Lense CLEAR OPAQUE
Are the Appliances: RED WHITE
Are the Appliances: CEILING WALL
ANNUNCIATOR INFO
Will the Existing ANN
Back Box Work with New
Equipment YES NO
Will the Existing ANN
Wiring Work with New
Equipment YES NO
System Printer YES NO
Matrix/Graphic Annunciator YES NO
If Yes, How Many LEDs
BUILDING INFO
Occupancy Group
How Many Stories
EVAC Required? YES NO
Fireman's Phone Jacks YES NO
Smoke Control YES NO
If Yes how many LEDS
EMERGENCY/AUXILIARY FUNCTIONS
Elevator Recall YES NO
If YES: PRI ALT SHUNT HAT
Card Access Control YES NO
Door Holders YES NO
If YES, will Headers Require
additional Smoke Detectors YES NO
EQUIPMENT QUANTITIES
Pull Stations
Smoke Detectors
Heat Detectors
Duct Detectors
Waterflows
Tampers
Relays
Control Modules
Audible Appliances
Visual Appliances
Door Holders
ANSUL
Pre-Action Systems
Beam Detectors
INSTALLATION INFO
Scissor Lift Needed YES NO
Conduit or Open Wire
Plenum Rated Ceilings YES NO
Ceiling Construction BEAM T-BAR GYPSUM OPEN
Firewatch YES NO
SAMPLE ELE
www
Z1,Z4,Z44 * NOTE 1
* NOTE 2
Elev Hoistway Z3,Z4,Z44 Zones
Z1,Z24,Z44 Z1 = Primary Elevator Recall
R/PH Z44 Z24 RPS Z2 = Alternate Elevator Recall
Z1,Z23,Z43 Z3 = Elevator Shunt Trip
19th Z43 Z23 RPS Z4 = Elevator Fireman's Hat Light
Z1,Z22,Z42 Z5 - Z24 = Strobe/Voice Activation for Floors 1-PH
18th Z42 Z22 RPS Z25 - Z44 = Elevator Lobby/Door Release for Floors
Z1,Z21,Z41 Z45 = Shunt Trip Power Supervision
17th Z41 Z21 RPS
Z1,Z20,Z40
16th Z40 Z20 RPS
Z1,Z19,Z39 Device Types
15th Z39 Z19 RPS Smoke Detector
Z1,Z18,Z38 Heat Detector
14th Z38 Z18 RPS Control Module for Strobes and Voice
Z1,Z17,Z37 RPS
13th Z37 Z17 RPS Relay for Elevator Lobby Door Release
Z1,Z16,Z36 Relay for Primary Recall
12th Z36 Z16 RPS Relay for Alternate Recall
Z1,Z15,Z35 Relay or Control Module for Shunt Trip
11th Z35 Z15 RPS Relay for Fireman's Hat
Z1,Z14,Z34 PR-1 Interface Relay
10th Z34 Z14 RPS FACU
Z1,Z13,Z33 Addressable Monitor Module
9th Z33 Z13 RPS
Z1,Z12,Z32
8th Z32 Z12 RPS
Z1,Z11,Z31
7th Z31 Z11 RPS
Z1,Z10,Z30
6th Z30 Z10 RPS
Z1,Z9,Z29
5th Z29 Z9 RPS
Z1,Z8,Z28
4th Z28 Z8 RPS
Z1,Z7,Z27
3rd Z27 Z7 RPS
Z1,Z6,Z26
2nd Z26 Z6 RPS
Z2,Z5,Z25 Z2,Z4,Z5 Z3,Z4,Z5
1st Z25 Z5 RPS Z1 Z2 Z4
Elevator Equip Room
Elev Pit Z3,Z4,Z5 * NOTE 3
USE THIS METHOD OF SHUNT TRIP CONNECTION WHEN THE POWER USED
THIS METHOD WILL ALSO WORK IF YOU WANT T
ALL WIRING THROUGH THE CONTROL MODULE AND U
* Note = The Addressable Control Module switches voltage when active. When reversed in standby,
the wires are supervised via an EOL resistor. When active, the voltage will switch and supply power to
the PR-1 thus changing the state of the contacts.
SLC In + N.O
NAC - * EOL
SLC In - 24VDC Comm
NAC + * EOL
Comm N.C
PWR + PWR -
Normally OFF
Relay #1 = Used to trip the Shunt Trip Breaker with the 120 VAC (Activated via the Addressable Control Module *)
Relay #2 = Used to supervise the 120 VAC circuit to operate the Shunt Trip Breaker (via Monitor Module #1)
Addressable Control Module = Supplys Power to PR-1 (#1)
USE THIS METHOD OF SHUNT TRIP CONNECTION WHEN THE POWER USED T
THIS METHOD REQUIRES THE RELAY TO BE WITH
ALL WIRING UP TO THE ADDRESSABLE RELAY
SLC In - COMM
N.C
* NOTE 1 SD in the top of the elevator hoistway is not always required consult the
A17.1 and NFPA 72.
* NOTE 2 HD in the top of the elevator hoistway is not always required consult the
A17.1 and NFPA 72.
n's Hat Light * NOTE 3 HD in the pit of the elevator hoistway is not always required consult the
ice Activation for Floors 1-PH and NFPA 72
Lobby/Door Release for Floors 1-PH
wer Supervision All HD devices to be located within 2 feet of the sprinkler head in the elevator pit, e
or elevator machine room. Reference NFPA 72 2010 ed. 21.4.2*
Relay Module or
Pri Recall Relay Alt Recall Relay Fireman's Hat Rly Con Mod Shunt
Common Common Common
N.O. N.O. N.O.
N.C N.C N.C
ION WHEN THE POWER USED TO OPERATE THE SHUNT TRIP BREAKER EXCEEDS THE CURRENT RATINGS OF AN ADDRESSABLE RELAY
L ALSO WORK IF YOU WANT TO INSTALL THE RELAY MORE THAN 3 FEET FROM THE SHUNT TRIP BREAKER
THE CONTROL MODULE AND UP TO THE PR-1 #1 IS SUPERVISED ACCORDING TO NFPA 72 2010 SECTION 21.2.4*
#2 PR-1 Relay
Comm N.C
Alrm Con
Normally ON
#1 PR-1 Relay
Comm N.C
Alrm Con
Normally ON
SLC
Relay Module or
Con Mod Shunt Pwr Superv
PR-1 PR-1
AN ADDRESSABLE RELAY
2.4*
SLC In -
FACU
THE ADDRESSABLE RELAY
SLC In -
FACU