ELECTRICAL DETAIL FOR SELECTION OF MCB/MCCB & CABLE SIZE FOR SMMSe OUTDOOR MODULES

DESCRIPTION Calculation for Each CDU Type

8 10 12 14 14 16 18 20 22
18
(Heat-Cool (Heat-Cool (Heat-Cool (Heat-Cool (Heat-Cool (Heat - Cool (Heat-Cool (Heat-Cool
CDU HP (Space Saving- (Space Saving-
& & & & & & & &
Cooling Only) Cooling Only)
Cooling Only) Cooling Only) Cooling Only) Cooling Only) Cooling Only) Cooling Only) Cooling Only) Cooling Only)

MAP0806HT8P MAP1006HT8P MAP1206HT8P MAP1406HT8P MAP1606HT8P MAP1806HT8P MAP2006HT8P MAP2206HT8P


CDU MODEL (MMY-) MAP14B6T8P MAP18B6T8P
MAP0806T8P MAP1006T8P MAP1206T8P MAP1406T8P MAP1606T8P MAP1806T8P MAP2006T8P MAP2206T8P
No. of Fans 1 1 1 1 1 1 1 2 2 2
No. of Compressors 2 2 2 2 2 2 2 2 2 2
External Dimension - mm
1800/990/780 1800/990/780 1800/990/780 1800/990/780 1800/1210/780 1800/1210/780 1800/1210/780 1800/1600/780 1800/1600/780 1800/1600/780
(H/D/W)
Nominal Voltage 380-400-415 V
Phase & Frequency 3N~ 50 Hz
CDU MCA*2 20.50 21.50 26.10 31.00 35.80 35.80 40.60 40.60 44.90 49.30
Individual TPN MCB (Amp.) 25 25 32 40 40 40 63 63 63 63
Power Wiring (Copper) 4core X 6 Sqmm, 4mm earthing 4core X 10 Sqmm, 6mm earthing 4 core X 16 Sqmm, 8mm earthing
Header MCB / MCCB for Combination outdoor units (other than individual MOCP shown above)
Combination Outdoor HP 24/26 28/30/32 34/36/38 40/42/44/46/48 50/52/54/56/58/60
Main MCB / MCCB (Amp.) 63 80 100 125 160

*1 cooling: indoor air temp 270C DB/190C outdoor air temp. 350C
heating: indoor air temp 200C DB, outdoor air temp. 70C DB/60C WB
*2 MCA - for selecting wire size, it means the minimum wire diameter should be of such value that it
can carry given MCA current value without overheat or any electrical failure.
A) OUTDOOR SUPPLY 3 Phase 4 Line (L1,L2,L3,N) 380-464V & 50 Hz + 1Hz
B) in case of combination of 2 or more outdoor unit, calculate the main wire input size to Header
MCB/MCCB basis total KW load.
C) Please refer your local electrical standard also along with above mentioned values.
D) All control & power wiring including earth should be copper only & above table is basis the same.
4. The unit operating voltage range is 342-456 Volt.