1. There will be 3 three stages of the mushroom and each growth stage has a required environmental
condition meaning there is a desired temperature, humidity, light and Carbon dioxide concentration
in each stage. Below is the table of the required condition.
2. So in the arduino system, there will be three functions for each stage. There is a menu for selecting
the desired mushroom growth stage using a 4x4 keypad connected to the LCD
3. A TEXT MESSAGE ALERT should be sent to the smart phone when THERE IS CHANGES on the status
of the Relays/appliances together with the environmental data.
5. CHANGES ON THE Status of the relays/appliances should also be stored in the database
CONDITION
STAGE 1. SPAWN-RUN
IF humidity is less than 60% SWITCH ON the humidifier AND IF the humidity is greater than
75% , SWITCH OFF the RELAY for humidifier.
IF the Temperature is LESS THAN 22 °C, SWITCH OFF the RELAY for fan AND IF the
Temperature is GREATER THAN 26, SWITCH ON the RELAY for fan.
Light: The light is TURNED OFF
Carbon Dioxide (CO2) – The CO2 should be 10,000 ppm to 20,000 ppm
Just Monitor, record and send the data on the CO2 concentration, no other action needed
IF humidity is less than 85% SWITCH ON the RELAY (Sprinkler and/or Humidifier )AND IF the
humidity is greater than 90% , SWITCH OFF the RELAY (Sprinkler and humidifier).
IF the Temperature is LESS THAN 15 °C, SWITCH OFF the RELAY (sprinkler and Fan) AND IF
the Temperature is GREATER THAN 20, SWITCH ON the RELAY (sprinkler and fan).
Light: The luminosity of the light should be maintained to 80-210 lux for 12 hours
If the light luminosity is less than 80 lux and TIME IS 6 AM, SWITCH ON the lights/Bulbs. AND
IF the TIME IS 6 PM, SWITCH OFF the lights/Bulbs.
Carbon Dioxide (CO2) – The CO2 should be 800 ppm to 1,500 ppm
Just Monitor, record and send the data on the CO2 concentration, no other action needed
Controlling the CO2 will be done manually.
IF the humidity is LESS THAN 80%, SWITCH ON THE RELAY (HUMIDIFIER/SPRINKLER), AND IF
the humidity is greater than 85%, SWITCH OFF the RELAY (humidifier/sprinkler.)
IF the Temperature is LESS THAN 20 °C, SWITCH OFF the RELAY (sprinkler or Fan) AND IF the
Temperature is GREATER THAN 25, SWITCH ON the RELAY (sprinkler or fan).
Light: The luminosity of the light should be maintained to 500 lux and above for 12 hours
If the light luminosity is less than 500 and TIME IS 6 AM, SWITCH ON the RELAY
(lights/Bulbs). AND IF the TIME IS 6 PM, SWITCH OFF the RELAY (lights/Bulbs.)
Carbon Dioxide (CO2) – The CO2 should be less than 600 ppm
Just Monitor, record and send the data on the CO2 concentration, no other action needed
Controlling the CO2 will be done manually.