You are on page 1of 5

1 Introduction

Electrical installations almost always require and 4 are used. Two values of the short-circuit
protection against short-circuits wherever there current must be evaluated:
is an electrical discontinuity. This most often c The maximum short-circuit current, used to
corresponds to points where there is a change determine
in conductor cross-section. The short-circuit v The breaking capacity of the circuit breakers
current must be calculated at each level in the v The making capacity of the circuit breakers
installation in view of determining the v The electrodynamic withstand capacity of the
characteristics of the equipment required to wiring system and switchgear
withstand or break the fault current. The maximum short-circuit current corresponds
The flow chart in Figure 1 indicates the to a short-circuit in the immediate vicinity of the
procedure for determining the various short- downstream terminals of the protection device.
circuit currents and the resulting parameters for It must be calculated accurately and used with a
the different protection devices of a low-voltage safety margin.
installation. c The minimum short-circuit current, essential
In order to correctly select and adjust the when selecting the time-current curve for circuit
protection devices, the graphs in Figures 2, 3 breakers and fuses, in particular when

Upstream Ssc

HV / LV
transformer rating usc (%)

Isc
at transformer
terminals

b Power factor Conductor characteristics Breaking capacity


Main
b Coincidence factor b Busbars
ST and inst. trip setting circuit breaker
b Duty factor v Length
b Foreseeable expansion v Width Isc
factor v Thickness of main LV switchboard
outgoers
b Cables Main LV
v Type of insulation Breaking capacity switchboard
v Single-core or multicore
v Length ST and inst. trip setting distribution
circuit breakers
v Cross-section Isc
b Environment at head of secondary
v Ambient temperature switchboards
v Installation method Breaking capacity Secondary
v Number of contiguous circuits distribution
ST and inst. trip setting circuit breakers
b Feeder current Isc
ratings at head of final
b Voltage drops switchboards
Breaking capacity Final
distribution
Inst. trip setting circuit breakers
Load Isc
rating at end of final
outgoers

Fig. 1 : Short-circuit (Isc) calculation procedure when designing a low-voltage electrical installation (ST = short time; Inst. = instantaneous)

Cahier Technique Schneider Electric n° 158 / p.4


v Cables are long and/or the source impedance where A is the cross-sectional area of the
is relatively high (generators, UPSs) conductors and k is a constant calculated on the
v Protection of life depends on circuit breaker or basis of different correction factors for the cable
fuse operation, essentially the case for TN and installation method, contiguous circuits, etc.
IT electrical systems Further practical information may be found in the
“Electrical Installation Guide” published by
Note that the minimum short-circuit current Schneider Electric (see the bibliography).
corresponds to a short-circuit at the end of the
protected line, generally phase-to-earth for LV
and phase-to-phase for HV (neutral not
t
distributed), under the least severe operating
conditions (fault at the end of a feeder and not
just downstream from a protection device, one Design Cable or I2t
transformer in service when two can be current characteristic
connected, etc.).
Note also that whatever the case, for whatever
type of short-circuit current (minimum or
Circuit breaker
maximum), the protection device must clear the
Transient time-current
short-circuit within a time tc that is compatible curve
overload
with the thermal stresses that can be withstood
by the protected cable:

∫i
2
dt i k 2 A 2 (see Fig. 2, 3, and 4)

IB Ir Iz Isc BC I
t 1 2 (tri)
Fig. 3 : Circuit protection using a circuit breaker.

Cable or I2t
characteristic
a5 s

I2t = k2S2
Furse time-current
curve
Transient
overload

Iz1 < Iz2 I


Fig. 2 : The I2tcharacteristics of a conductor depending
on the ambient temperature (1 and 2 represent the rms
value of the current in the conductor at different
temperatures θ1 and θ2, with θ1 > θ2; Iz being the limit of IB Ir Iz I
the permissible current under steady-state conditions). Fig. 4 : Circuit protection using an aM fuse.

1.1 The main types of short-circuits


Various types of short-circuits can occur in c Origin
electrical installations. v Mechanical (break in a conductor, accidental
Characteristics of short-circuits electrical contact between two conductors via a
The primary characteristics are: foreign conducting body such as a tool or an
c Duration (self-extinguishing, transient and animal)
steady-state) v Internal or atmospheric overvoltages

Cahier Technique Schneider Electric n° 158 / p.5


v Insulation breakdown due to heat, humidity or v Fire and danger to life
a corrosive environment c On the faulty circuit
c Location (inside or outside a machine or an v Electrodynamic forces, resulting in
electrical switchboard) - Deformation of the busbars
Short-circuits can be: - Disconnection of cables
c Phase-to-earth (80% of faults) v Excessive temperature rise due to an increase
c Phase-to-phase (15% of faults). This type of in Joule losses, with the risk of damage to
fault often degenerates into a three phase fault insulation
c Three-phase (only 5% of initial faults) c On other circuits in the network or in near-by
These different short-circuit currents are networks
presented in Figure 5 . v Voltage dips during the time required to clear
the fault, ranging from a few milliseconds to a
Consequences of short-circuits few hundred milliseconds
The consequences are variable depending on v Shutdown of a part of the network, the extent
the type and the duration of the fault, the point in of that part depending on the design of the
the installation where the fault occurs and the network and the discrimination levels offered by
short-circuit power. Consequences include: the protection devices
c At the fault location, the presence of electrical v Dynamic instability and/or the loss of machine
arcs, resulting in synchronisation
v Damage to insulation v Disturbances in control / monitoring circuits
v Welding of conductors v etc.

a) Three-phase short-circuit b) Phase-to-phase short-circuit clear of earth

L3 L3

L2 L2

L1 L1

Ik" 3 Ik" 2

c) Phase-to-phase-to-earth short-circuit d) Phase-to-earth short-circuit

L3 L3

L2 L2

L1 L1

Ik" 2EL3 Ik" 2EL2 Ik" 1

Ik" E2E

Short-circuit current,
Partial short-circuit currents in conductors and earth.

Fig. 5 : Different types of short-circuits and their currents. The direction of current is chosen arbitrarily
(See IEC 60909).

Cahier Technique Schneider Electric n° 158 / p.6


1.2 Development of the short-circuit current
A simplified network comprises a source of the R / X ratio is between 0.1 and 0.3. The ratio
constant AC power, a switch, an impedance Zsc is virtually equals cos ϕ for low values:
that represents all the impedances upstream of R
the switch, and a load impedance Zs cos ϕ =
(see Fig. 6 ). R + X2 2

However, the transient conditions prevailing


In a real network, the source impedance is made while the short-circuit current develops differ
up of everything upstream of the short-circuit depending on the distance between the fault
including the various networks with different location and the generator. This distance is not
voltages (HV, LV) and the series-connected necessarily physical, but means that the
wiring systems with different cross-sectional generator impedances are less than the
areas (A) and lengths. impedance of the elements between the
In Figure 6, when the switch is closed and no generator and the fault location.
fault is present, the design current Is flows
through the network. Fault far from the generator
This is the most frequent situation. The transient
When a fault occurs between A and B, the conditions are those resulting from the
negligible impedance between these points application of a voltage to a reactor-resistance
results in a very high short-circuit current Isc that circuit. This voltage is:
is limited only be impedance Zsc. e = E 2 sin (ωt + α )
The current Isc develops under transient
Current i is then the sum of the two components:
conditions depending on the reactances X and
i = iac + idc
the resistances R that make up impedance Zsc:
c The first (iac) is alternating and sinusoidal
Zsc = R2 + X 2
iac = Ι 2 sin (ωt + α − ϕ )
In power distribution networks, reactance X = L ϕ E
is normally much greater than resistance R and where I = ,
Zsc
α = angle characterising the difference between
the initiation of the fault and zero voltage.
R X
c The second (idc) is an aperiodic component
R
- t
idc = - Ι 2 sin (α − ϕ ) e L
. Its initial value
depends on a and its decay rate is proportional
A
to R / L.
Zsc At the initiation of the short-circuit, i is equal to
zero by definition (the design current Is is
e Zs negligible), hence:
i = iac + idc = 0
Figure 7 shows the graphical composition of i as
B the algebraic sum of its two components iac and
idc
Fig. 6 : Simplified network diagram.

iac = I sin (ωt + α − ϕ) -


R t
idc = - I sin (α − ϕ) e L

I
t

α-ϕ
ω i = iac + idc

Fault initiation

Fig. 7 : Graphical presentation and decomposition of a short-circuit current occuring far from the generator.

Cahier Technique Schneider Electric n° 158 / p.7


a) Symmetrical The moment the fault occurs or the moment of closing,
with respect to the network voltage, is characterised by its
i closing angle a (occurrence of the fault). The voltage can
Ir therefore be expressed as: u = E 2 . sin (ωt + α ) .
The current therefore develops as follows:

E 2 
R 
- t
i = sin (ωt + α - ϕ ) - sin (α - ϕ ) e L 
u Z  
 
with its two components, one being alternating with a shift
equal to ϕ with respect to the voltage and the second
aperiodic and decaying to zero as t tends to infinity.
Hence the two extreme cases defined by:
c α = ϕ ≈ π / 2, said to be symmetrical (or balanced)
(see Fig. a )
b) Asymmetrical E 2
The fault current can be defined by: i = sin ωt
Z
i idc which, from the initiation, has the same shape as for
steady state conditions with a peak value E / Z.
ip c α = 0, said to be asymmetrical (or unbalanced)
(see Fig. b )
The fault current can be defined by:

E 2 
u R 
- t
i = sin (ωt - ϕ ) + sin ϕ e L 
Z  
 
Its initial peak value ip therefore depends on ϕ on
the R / X ≈ cos ϕ ratio of the circuit.

Fig. 8 : Graphical presentation of the two extreme cases (symmetrical and asymmetrical) for a short-circuit current .

Figure 8 illustrates the two extreme cases for The transient current-development conditions
the development of a short-circuit current, are in this case modified by the variation in the
presented, for the sake of simplicity, with a electromotive force resulting from the
single-phase, alternating voltage. shortcircuit.
R
For simplicity, the electromotive force is
− t assumed to be constant and the internal
The factor e L is inversely proportional to the
reactance of the machine variable. The
aperiodic component damping, determined by reactance develops in three stages:
the R / L or R / X ratios. c Subtransient (the first 10 to 20 milliseconds of
The value of ip must therefore be calculated to the fault)
determine the making capacity of the required c Transient (up to 500 milliseconds)
circuit breakers and to define the electrodynamic
c Steady-state (or synchronous reactance)
forces that the installation as a whole must be
capable of withstanding.
Its value may be deduced from the rms value of
the symmetrical short-circuit current Ιa using the
κ
equation:
2.0
ip = κ . r . Ia, where the coefficient κ is
indicated by the curve in Figure 9 , as a function 1.8
of the ratio R / X or R / L, corresponding to the
expression: 1.6
R 1.4
−3
κ = 1.02 + 0.98 e X
1.2
Fault near the generator
1.0
When the fault occurs in the immediate vicinity of 0 0.2 0.4 0.6 0.8 1.0 1.2 R/X
the generator supplying the circuit, the variation
in the impedance of the generator, in this case Fig. 9 : Variation of coefficient κ depending on
the dominant impedance, damps the short-circuit R / X or R / L (see IEC 60909).
current.

Cahier Technique Schneider Electric n° 158 / p.8

You might also like