Professional Documents
Culture Documents
Electrical installations almost always require and 4 are used. Two values of the short-circuit
protection against short-circuits wherever there current must be evaluated:
is an electrical discontinuity. This most often c The maximum short-circuit current, used to
corresponds to points where there is a change determine
in conductor cross-section. The short-circuit v The breaking capacity of the circuit breakers
current must be calculated at each level in the v The making capacity of the circuit breakers
installation in view of determining the v The electrodynamic withstand capacity of the
characteristics of the equipment required to wiring system and switchgear
withstand or break the fault current. The maximum short-circuit current corresponds
The flow chart in Figure 1 indicates the to a short-circuit in the immediate vicinity of the
procedure for determining the various short- downstream terminals of the protection device.
circuit currents and the resulting parameters for It must be calculated accurately and used with a
the different protection devices of a low-voltage safety margin.
installation. c The minimum short-circuit current, essential
In order to correctly select and adjust the when selecting the time-current curve for circuit
protection devices, the graphs in Figures 2, 3 breakers and fuses, in particular when
Upstream Ssc
HV / LV
transformer rating usc (%)
Isc
at transformer
terminals
Fig. 1 : Short-circuit (Isc) calculation procedure when designing a low-voltage electrical installation (ST = short time; Inst. = instantaneous)
∫i
2
dt i k 2 A 2 (see Fig. 2, 3, and 4)
IB Ir Iz Isc BC I
t 1 2 (tri)
Fig. 3 : Circuit protection using a circuit breaker.
Cable or I2t
characteristic
a5 s
I2t = k2S2
Furse time-current
curve
Transient
overload
L3 L3
L2 L2
L1 L1
Ik" 3 Ik" 2
L3 L3
L2 L2
L1 L1
Ik" E2E
Short-circuit current,
Partial short-circuit currents in conductors and earth.
Fig. 5 : Different types of short-circuits and their currents. The direction of current is chosen arbitrarily
(See IEC 60909).
I
t
α-ϕ
ω i = iac + idc
Fault initiation
Fig. 7 : Graphical presentation and decomposition of a short-circuit current occuring far from the generator.
E 2
R
- t
i = sin (ωt + α - ϕ ) - sin (α - ϕ ) e L
u Z
with its two components, one being alternating with a shift
equal to ϕ with respect to the voltage and the second
aperiodic and decaying to zero as t tends to infinity.
Hence the two extreme cases defined by:
c α = ϕ ≈ π / 2, said to be symmetrical (or balanced)
(see Fig. a )
b) Asymmetrical E 2
The fault current can be defined by: i = sin ωt
Z
i idc which, from the initiation, has the same shape as for
steady state conditions with a peak value E / Z.
ip c α = 0, said to be asymmetrical (or unbalanced)
(see Fig. b )
The fault current can be defined by:
E 2
u R
- t
i = sin (ωt - ϕ ) + sin ϕ e L
Z
Its initial peak value ip therefore depends on ϕ on
the R / X ≈ cos ϕ ratio of the circuit.
Fig. 8 : Graphical presentation of the two extreme cases (symmetrical and asymmetrical) for a short-circuit current .
Figure 8 illustrates the two extreme cases for The transient current-development conditions
the development of a short-circuit current, are in this case modified by the variation in the
presented, for the sake of simplicity, with a electromotive force resulting from the
single-phase, alternating voltage. shortcircuit.
R
For simplicity, the electromotive force is
− t assumed to be constant and the internal
The factor e L is inversely proportional to the
reactance of the machine variable. The
aperiodic component damping, determined by reactance develops in three stages:
the R / L or R / X ratios. c Subtransient (the first 10 to 20 milliseconds of
The value of ip must therefore be calculated to the fault)
determine the making capacity of the required c Transient (up to 500 milliseconds)
circuit breakers and to define the electrodynamic
c Steady-state (or synchronous reactance)
forces that the installation as a whole must be
capable of withstanding.
Its value may be deduced from the rms value of
the symmetrical short-circuit current Ιa using the
κ
equation:
2.0
ip = κ . r . Ia, where the coefficient κ is
indicated by the curve in Figure 9 , as a function 1.8
of the ratio R / X or R / L, corresponding to the
expression: 1.6
R 1.4
−3
κ = 1.02 + 0.98 e X
1.2
Fault near the generator
1.0
When the fault occurs in the immediate vicinity of 0 0.2 0.4 0.6 0.8 1.0 1.2 R/X
the generator supplying the circuit, the variation
in the impedance of the generator, in this case Fig. 9 : Variation of coefficient κ depending on
the dominant impedance, damps the short-circuit R / X or R / L (see IEC 60909).
current.