IPACK2005-730008
Joseph Yeh
Thermal Consultant
5810 Brushy Creek Trail
Dallas TX 75252
jjyeh2@aol.com
Exit Grille
850
Air
Flow
Table 1 Air Flow Rate for 4 Fans in Operation with Air Filter
The first step of the analysis is to optimize the location of the 3 Inch from Fan
air filter. The available space for the air filter is bounded
between the lower support and the top of the inlet as shown in Compartment Up-Stream Filter Down-Stream Filter
Figure 1. The height of this space is 5.5” that includes the fan Flow Rate (CFM) Flow Rate (CFM)
thickness. The air filter can be placed at either upstream or
down stream of the fan pack. The air filter can protect the fans OEM1 253 243
from dust in the former case, while the filter pressurizes the OEM2 208 248
plenum to achieve a better flow distribution to the OEM3 289 223
compartments in the latter case. Boards 78 125
Parametric studies are performed to examine the effect of the The results for the case with one fan failure are presented in
location of the air filter on the flow distribution. Figure 3 shows Figure 4. The optimum distance for both cases, (up- and down-
the results for the case with 4 fans in operation. The difference stream air filters) is found to be about 1” from the fan pack.
in the flow rate between the cases with the air filter being The difference in the system flow rate appears first to increase
located at up- and down-stream of the fans is small (less than and then to decrease as the distance from fan pack increases.
11 ft3/min (CFM)) regardless the location of the air filter. For The air filter location has a great effect on the flow distribution,
down stream air filter case, the total system flow rate increases especially for the case with one fan failure. This trend is clearly
as the distance from the fan pack increases. However, on the found in Tables 2. Table 2 lists the flow rates to individual
other hand, an optimum distance of 2” from the fan pack that compartments when the air filter is located at 3” in the up-
generates the maximum system flow rate is achieved for the up- stream and down-stream of the fan pack, respectively.
stream air filter.
Reversed Flow 270 321 The total flow generated by 4 fans at 36V is 839 CFM.
(Leakage from bad fan) However, the flow rate is reduced to 504 CFM when one fan
fails, and the reversed flow through the failed fan is 321 CFM
as listed in Table 2. The large flow leakage from a failed fan is
The failed fan is located just below OEM1 and OEM2. due to a series of high flow resistances such as air filter,
Therefore, little flow is supplied to these two modules when the perforate plates in the down stream of the fans. The net effect is
air filter is located upstream of the fans as illustrated in Figure to force the air flowing through the opening of the failed fan
5. Table 2 indicates that the filter located at the upstream of the because of less resistance in the path. Figure 7 illustrates the
fan provides uneven air flow to the compartments when one fan flow that leaks out from the opening of the failed fan.
fails. On the other hand, the case with the air filter placed in the
down stream of the fans gives a more uniform flow distribution Figure 8 shows the increasing air flow along the exit duct. This
to all compartments as given in Table 2. This is because the is because the exited flow from the compartments is
latter pressurizes the plenum due to a relatively high flow recombined as it leaves the shelf. It is often thought that adding
resistance of the air filter. a deflector at the dead end in the upper corner of the exit path
may increase the system flow by smoothing the flow path
The real concern is not at the total system flow rate but the flow (eliminating flow re-circulation). Figure 9 shows such
rate to individual modules. As can be seen from the above modification with an additional deflector in the exit path.
table, the flow rate to OEMs 1 and 2 for the case with the up- However, no actual improvement is found from the analysis.
stream air filter is much smaller than those with the down- The main reason may be that only a small amount of air from
stream air filter. This may lead to an overheating of the the compartments flows near the dead end section as illustrated
components inside OEMs 1 and 2. in Figure 7.
Air Exit
Air Deflector 4 fans in operation :
838CFM
Same flowrate as case
without deflector
Flow reversed
in failed fan
Failed Fan
Air Inlet