Professional Documents
Culture Documents
Document No._Rev.
Restricted
Main Data
Study Report
Bacatá Substation
Index of Revisions
Index:
1 Introduction ........................................................................................................... 4
List of Tables:
List of Figures:
Figure 4-4: Simplified single line for short circuit calculation on medium voltage busbar ...... 12
Figure 4-5: Simplified single line diagram of the SVC PLUS converter................................. 14
Figure 4-6: Simplified single line diagram of one converter submodule ................................ 14
Figure 4-7: Example of converter voltage waveform ............................................................ 15
Figure 4-8: Voltage and current waveform during capacitive output and switching states
of reference power module............................................................................ 16
Figure 4-9: V/I characteristic of the SVC PLUS at the HV-side of the SVC PLUS
transformer for degraded mode ..................................................................... 22
Figure 4-10: V/I characteristic of the SVC PLUS at the MV-side of the SVC PLUS
transformer for degraded mode ..................................................................... 23
Restricted © Siemens AG, 2014. All Rights reserved.
1 Introduction
One new SVC shall be installed at the Bacatá substation in Colombia. The STATCOMs proposed
by Siemens are state of the art Voltage Sourced Converters (VSC), also referred to as SVC PLUS.
Based on true multilevel VSC technology, the SVC PLUS concept provides highly dynamic contin-
uously adjustable reactive power support to the ac system. With a converter ac voltage comprising
a minimum at 81 voltage output levels, the converter generates a close to sinusoidal voltage wave
shape. A voltage wave shape like this is advantageous for two aspects:
The SVC PLUS has extremely low harmonic generation and therefore allows a safe design
with respect to possible harmonic interaction with the ac system. These advantages will be
achieved without necessary filter components.
The converters can be operated at a moderate switching frequency of the IGBTs resulting
in low power losses and thus low operational costs.
The two SVC PLUS will have continuously adjustable reactive power output from 200 Mvar capaci-
Restricted © Siemens AG, 2014. All Rights reserved.
tive to 200 Mvar inductive at the 500 kV point of common coupling as specified in [1]. Because of
the Voltage Sourced Converter technology, the SVC PLUS has a symmetrical Mvar output.
The present report describes the Main Data of the SVC PLUS system.
The aim of this chapter is to provide a general explanation of the working principle of a Voltage
Sourced Converter. In Figure 2-1 the simplified network for explanation on the left side and on the
right side the phasor diagram is shown. The network consists of a network voltage (VN), one trans-
former with a corresponding voltage drop ( VTr), a phase reactor with corresponding voltage drop
( VRe) and an artificial voltage source (VCon), which represents the Voltage Sourced Converter
voltage. Additional the current (I) is marked in red. In case of a capacitive output the current I is
leading in comparison to the network voltage VN. This can be identified in the phasor diagram with
the right angle between VN and I. This current produces a voltage drop across the inductive trans-
former and the inductive phase reactor. This voltage drop is leading in comparison to the current.
The addition of the voltages VN and VTr reflects the voltages on secondary side of the transformer
(VTR) and the additional summation of the voltage drop across the phase reactor defines the nec-
essary voltage of the Voltage Sourced Converter to drive the requested current I into the network.
It can be identified that the Voltage Sourced Converter voltage has the same phase shift as the
Restricted © Siemens AG, 2014. All Rights reserved.
voltage in the network and the only difference is the amplitude. In case of a higher voltage of the
Voltage Sourced Converter as the network voltage a capacitive current will be driven and in case
of a smaller Voltage Sourced Converter voltage an inductive current will flow. It is obvious that in
case of equal amplitude between network and Voltage Sourced Converter voltage no current will
flow.
The SVC PLUS is designed for continuous operation of 200 Mvar capacitive and 200 Mvar induc-
tive at a system voltage of 1.0 pu.
a) Voltages kVrms pu
b) System Frequencies
Nominal frequency Hz 60
1
assumed
Study Report STATCOM Bacatá
Main Data Contract: 39911
P-012752_E_D1_6010_B_0
Page 7 of 26
2
according to IEC 60071-2
3
according to [5]
4
according to [2]
Study Report STATCOM Bacatá
Main Data Contract: 39911
P-012752_E_D1_6010_B_0
Page 8 of 26
g) Environmental conditions
b) Temperature, (°C)
Annual media 79
Restricted © Siemens AG, 2014. All Rights reserved.
i) Seismic characteristics
j) Solar radiation
The SVC is designed to operate under the system voltage conditions shown in Figure 3-1 and Fig-
ure 4-2 (V/I -Characteristic).
Restricted © Siemens AG, 2014. All Rights reserved.
The arrangement of the SVC PLUS is shown in Figure 4-1. The SVC PLUS comprises a step down
transformer and two SVC PLUS converters with the corresponding phase reactors LVSC. The con-
verter is delta connected.
The nominal voltage of the SVC PLUS secondary busbar was optimized to 28 kV, the transformer
leakage reactance will be 0,15 pu based on 200 MVA rated power.
Point of
calculated Mvar Uprim= 500 kV
output Usec = 28 kV
uk= 0.15
Str = 200 MVA
YNd5
CSurge
28 kV 31 kA
LVSC LVSC
Restricted © Siemens AG, 2014. All Rights reserved.
The V/I characteristic of the SVC as seen from the primary side (Point of calculated Mvar output,
refer to Figure 4-1) is shown in Figure 4-2 based on a symmetrical voltage on primary side. The
relevant operating points are marked (please refer to Table 4-3: Operating Table). The operating
range marked with red continuous lines is valid for continuous operation in the voltage band be-
tween 425 kV to 550 kV on the PCC. The dashed blue lines represent time limited operating points
at undervoltages down to 200 kV and overvoltages up to 650 kV. The dashed green line shows the
0.05s overload condition at 750kV.
Figure 4-2: V/I characteristic of the SVC PLUS at the HV-side of the SVC PLUS transformer
In Figure 4-3, the V/I characteristic on the secondary side of the transformer is displayed.
Figure 4-3: V/I characteristic of the SVC PLUS at the MV-side of the SVC PLUS transformer
The maximum calculated short circuit current on the medium voltage side is limited by the highest
short circuit power of the AC system and the transformer impedance. The transformer tolerance of
-5% for the short circuit impedance and a safety factor of 1,1 were considered. The maximum short
circuit current on secondary side busbar is below 31 kA.
The following simplified single line can be used for the short circuit calculation on medium voltage
side of the transformer.
Figure 4-4: Simplified single line for short circuit calculation on medium voltage busbar
The calculation of the impedance values was carried out based on the secondary voltage level:
1,1 28
= = 26,5
2 (0,5586 + 0,0226 )
The basic data of the transformer is defined by the nominal power of 200 MVA and the following
parameters:
The capacitive design point of 200 Mvar at a primary voltage of 1.0 pu is reached by a converter
current of 1191 A inside the delta connection.
The inductive design point of 200 Mvar at a primary voltage of 1.0 pu is reached by a converter
current of 1191 A inside the delta connection.
In section 2 the general operating principle for generating reactive power output with a voltage
source converter was given. In the following Siemens solution SVC PLUS is explained in detail.
The voltage sourced converter consists of three identical phase legs connected in delta. The prin-
ciple equivalent circuit of an SVC PLUS converter phase leg is shown in Figure 4-5 and the Main
Data are documented in Table 4-1. The individual phase legs can be operated independently from
one another.
Restricted © Siemens AG, 2014. All Rights reserved.
Figure 4-5: Simplified single line diagram of the SVC PLUS converter
Each SVC PLUS phase leg is built up by 40+4 submodules connected in series. The main compo-
nents of each submodule are 4 IGBTs, 4 diodes and one DC-capacitor (see Figure 4-6). All speci-
fied operating points can be reached with a minimum of 40 submodules in service per phase leg,
i.e. each phase leg comprises 4 redundant submodules. The redundant submodules participate in
normal operation. In case of a submodule failure, the corresponding submodule will be bypassed
without interrupting SVC PLUS operation.
Additionally, a start-up resistor and an associated bypass switch are included in each phase leg for
converter energization. During energization each submodule will be charged to a certain DC volt-
age level.
To achieve an 81 level output voltage (Figure 4-7) wave shape VConv, 40 submodules are needed.
Each submodule can contribute to the total output voltage of the respective phase by three differ-
ent voltage levels, namely plus Vdc, minus Vdc and zero. What voltage level a submodule is con-
tributing at a time is determined by the switching states of the IGBT valves which are controlled by
the converter closed loop control accordingly.
SVC : Graphs
Conv12 Conv23 Conv31
50
40
30
20
10
0
y
-10
-20
Restricted © Siemens AG, 2014. All Rights reserved.
-30
-40
-50
0.790 0.800 0.810 0.820 0.830 0.840 ...
...
...
Symbol Unit
Number of units - - 2
Type - - 3-phase
Converter type - - 40-level VSC
Installed number of power modules inclusive spare 44
modules
Minimum number of power modules for service per 40
phase
Switchable solid state device - - IGBT
Maximum continuous output voltage VConv kVrms 40,34
Maximum continuous current IConv Arms 1191
Number of discrete voltage step of the output voltage - - 81
Average DC voltage Vdcavn kVdc 1,5
DC-capacitor CDC mF 7,5
Coupling reactor pro phase LVSC mH 15,0
In the following the different switching states of one reference power module during capacitive out-
put of the converter over one oscillation is shown. This will be done on an example for a 7-level
converter and capacitive output of the SVC.
Restricted © Siemens AG, 2014. All Rights reserved.
Figure 4-8: Voltage and current waveform during capacitive output and switching states of refer-
ence power module
In Figure 4-8 the reference voltage oscillation of the converter is marked with a red line (equivalent
of the black phasor in Figure 2-1) and the current output with a blue line. Additional the whole out-
put voltage of the converter is marked with a thin black line and the contribution of the reference
power module is marked with a blue-green line. The reference voltage (red line) defines the theo-
retical ideal converter output voltage which will be emulated by the individual voltage steps of the
power modules. The different switching states A1 to D2 will be explained in the following:
mum continuous current of each phase of the converter is -1191A. The power of both converters is
calculated by
Qconverter 2 3 1191A 38,94kV 278,268MVAr
The power of the reactor of both SVC PLUS units is calculated according to
2
Qreactor 2 3 2 60 1191A 48,128MVAr
The power on secondary side is calculated by
Qsec Qconverter Qreactor 278,288MVAr 48,128MVAr 230,14MVAr
The following table shows the contribution of the different SVC components to the capacitive and
inductive design point.
Table 4-2: Split up of total reactive power at the capacitive and inductive design point
Table 4-3: Operating Table shows the voltage and current stresses on the SVC PLUS compo-
nents. The column headings are abbreviated as follows:
OP Operating point
Qprim; Qsec Reactive power on 500 kV and 28kV terminals of the transformer
The operating points 1 and 2 state the current and voltage stresses at the design points of the SVC
PLUS installation at 1,0pu system voltage. OP 1 is the capacitive design point and OP 2 the induc-
Restricted © Siemens AG, 2014. All Rights reserved.
tive design point. Operating points 3 and 4 show the conditions at 1s undervoltage (0,4pu) and
overvoltage (1,3pu). OP 5 shows the conditions for maximum reference voltage and minimum
slope at full capacitive output. OP 6 shows the condition for maximum reference voltage and max-
imum slope at full inductive output. OP 7 shows the condition for minimum reference voltage and
maximum slope at full capacitive output. OP 8 shows the condition for minimum reference voltage
and minimum slope at full inductive output. OP 9 to OP 11 show the conditions when the output of
the SVC PLUS is zero. OP 12 shows the condition for an overvoltage of 1,5pu for 0,05s.
If one SVC PLUS branch is out of service, the SVC installation can operate in a degraded mode.
Table 4-4 shows the operating points for degraded mode. OP 1 and OP 2 show the conditions with
continuous converter current at 1,0pu system voltage. OP 3 and OP 4 show the conditions for
short-time under- and overvoltages at 0,4 and 1,3. OP 5 shows the conditions for maximum refer-
ence voltage and minimum slope at full capacitive output. OP 6 shows the condition for maximum
reference voltage and maximum slope at full inductive output. OP 7 shows the condition for mini-
mum reference voltage and maximum slope at full capacitive output. OP 8 shows the condition for
minimum reference voltage and minimum slope at full inductive output. OP 9 and OP 10 show the
conditions when the output of the SVC PLUS is zero. OP 11 shows the condition for an overvolt-
age of 1,5pu for 0,05s.
500 1,00 100,030 92,526 0,925 25,9 2062,59 1191 19,16 cont.
3 200 0,40 -40,020 -47,528 0,475 13,3 -2063,02 -1191 20,04 1s
4 650 1,30 130,034 122,53 1,225 34,3 2062,50 1191 27,56 1s
5 525 1,05 -105,064 -112,573 1,125 31,5 -2063,22 -1191 38,24 cont.
6 550 1,10 110,032 102,527 1,025 28,7 2062,56 1191 21,96 cont.
7 425 0,85 -85,049 -92,558 0,925 25,9 -2063,15 -1191 32,64 cont.
8 450 0,90 90,029 82,524 0,825 23,1 2062,62 1191 16,36 cont.
9 525 1,05 -0,016 -0,016 1,050 29,4 -0,32 0 29,40 cont.
10 450 0,90 -0,012 -0,012 0,900 25,2 -0,27 0 25,20 cont.
11 750 1,50 150,034 142,531 1,425 39,9 2062,44 1191 33,16 0,05s
The following figures show the V/I characteristics for degraded mode on primary and secondary
side.
Restricted © Siemens AG, 2014. All Rights reserved.
Figure 4-9: V/I characteristic of the SVC PLUS at the HV-side of the SVC PLUS transformer for
degraded mode
Figure 4-10: V/I characteristic of the SVC PLUS at the MV-side of the SVC PLUS transformer for
degraded mode
Sub-Bank VSC
Number required 2x3
Type Dry-Type Air-core
Arrangement Side by side
Inductance per phase mH 15,0
Manufacturing tolerance
% -1,0/+1,0
(excluding taps)
Loss evaluation
Restricted © Siemens AG, 2014. All Rights reserved.
Nominal Data
Rated voltage (line to line)
Primary Winding (HV): 500 kV (1,0 pu)
Secondary Winding (MV): 28 kV (1,0 pu)
Normal Operating Voltage Range
Primary Winding: 0,85 to 1,10 pu
Secondary Winding: 0,75 to 1,20 pu
Maximum negative sequence voltage content: 2%
Nominal power (three-phase):
HV – MV 200 MVA
Transformer Connection (three phase): YNd5
Leakage impedance
HV – MV (based on 200 MVA): 0,15 pu
Tap changer range no tap changer
Restricted © Siemens AG, 2014. All Rights reserved.
5 List of References
6 List of Appendices
Restricted © Siemens AG, 2014. All Rights reserved.
7 List of Enclosures