You are on page 1of 2

12/29/13

500kVA 11/.433kV

Ads not by this site

500kVA 11/.433kV
RATED POWER (kVA) - Distribution Transformer Voltage Ratio at No Load (V) Off Circuit Tapping at HV (%) Withstand Voltage at 50Hz for 1min Frequency Vector Group Type of Cooling (kVrms) (Hz) No. of Phase
. .

500kVA 11,000 /433 2.5, 5.0 28 75 50/3 Dyn11 ONAN 500kVA 12 28 75 50/3 2 630 1 200
50

Impulse Wistand Voltage 1.2/50 ps (kV peak)

RATED POWER (kVA) - Ring Main Unit Rated Voltage Withstand Voltage at 50Hz for 1min Frequency Load Break Switch Rated Current of Switch Disconnector Fuse Switch Rated Current of FuseSwitch Fuse Rating for FuseSwitch (kV) (kVrms) (Hz)/No. of Phase (nos) (A) (nos) (A) (A)

Impulse Witstand Voltage 1.2/50 ps (kV peak)

RATED POWER (kVA) - LV Switchboard Rated Current Rated Voltage Incoming Disconnector Frequency Outgoing Fuseway Fuseway Outgoing Fuse Rating Current Transformer Ratio Ammeter Max. Demand Indication Power Factor Meter Kilowatt Hour Meter (Class 2) RATED POWER (kVA) Length Width Height (mm) (mm) (mm) (A) (V) (A) (Hz)/No. of Phase (A) (at 20C) Nos (A)
. .

500kVA 800 1000 800 50/3 400 6 160A-NH1 800/5A Class 1 3 nos 1 no 1 no

(30mins) (Induction Type)

500kVA 2745 1725 1815


1/2

www.ewt.com.my/index.php?view=article&id=83%3A500kva-11433kv&tmpl=component&print=1&layout=default&page=&option=com_content&Itemid=89

12/29/13

500kVA 11/.433kV

Total Weight

(kg)

3795

Ads not by this site

www.ewt.com.my/index.php?view=article&id=83%3A500kva-11433kv&tmpl=component&print=1&layout=default&page=&option=com_content&Itemid=89

2/2