Protection
Devices
7SG118 Argus 8
Voltage & Frequency Relay
Indication
These relays have extensive protection functions, which are The last 10 fault records are available from the fascia with time
and date of trip, measured quantities and type of fault.
supplemented by advanced metering, data storage and
communications. Supervisory and self monitoring features
Disturbance recorder
give added confidence to the user as well as reduced
maintenance and down time. A menu-based interface gives
user-friendly access to relay settings, meters and operational The waveform recorder may be triggered from a protection
function or external input and has a configurable pre-fault
data.
trigger. Up to 5 fault waveforms may be stored.
Function Overview AC voltage waveforms are stored together with the digital
states of the status inputs and output relays.
Undervoltage and overvoltage Relay variants with two voltage inputs have a '2 Systems A/B‘
Four independent elements are supplied, each of which can connection setting. This allows the voltage of two different
be set to operate for under or over voltage conditions. Each systems each to be assigned two of the under/overvoltage
has separate definite time delay elements. These can be elements.
used to protect generators against over-voltages, motors
against loss of supply or applied as backup protection in the This feature could be used as part of a local generation
event of defective system regulating equipment. scheme with islanding capability, where one input is
allocated to the local system, and the other to the grid.
Negative sequence overvoltage
Two independent elements are supplied, each of which has a Note that in this mode the frequency elements are disabled.
definite time delay element. These can be used to monitor
the quality of the supply and protect plant against system Blocking operation
unbalance. Each protection element can be blocked from operation by a
user-defined status input signal. In addition, the voltage,
Neutral voltage displacement frequency and NPS elements can be protected against
Two independent elements are supplied, each of which has a maloperation during system de-energisation using the
definite time delay element. These can be used to detect Voltage Blocking Threshold. Each frequency element may
earth faults in high impedance earthed or isolated systems. also be blocked by any combination of the voltage elements
For this feature, the residual voltage can be measured starting.
directly from an open delta tertiary winding or (for 3-phase
variants) calculated internally from the phase voltage inputs. Trip circuit supervision
The trip circuit connections can be monitored by a status
These elements include a third harmonic filter, which de- input. This is linked to an alarm and may be configured to
sensitises the elements to any superimposed third harmonic operate an output relay.
frequencies.
Circuit breaker maintenance
Underfrequency and overfrequency A circuit breaker operations counter is provided. An
Four independent elements are supplied, each of which can operations count level can be set which, when reached, can
be set to operate for under or over frequency. Each has be used as an input to a condition-based maintenance
separate definite time delay elements. These can be applied regime.
wherever frequency protection is required to maintain
system stability e.g. in load shedding schemes. The accuracy
and security of operation of the numeric algorithms enables
the relay to be employed to detect any frequency
abnormalities.
Attribute Value
Min. DC Current for
Operation:
30/48V 10mA
110/220V <5mA
Reset/Operate voltage ratio ≥ 90 %
Typical response time 5 ms
Typical response time when
programmed to energise an < 15 ms
output relay contact
Recommended Minimum 40ms with setting of 20ms
pulse duration PU delay for a.c. rejection
Electrostatic Discharge
IEC 60255-22-2 class III
Fast transient
IEC 255-22-4 class IV
Operating Time
Operate 0 V to 1.1xVs ≤ 85 ms
0 V to 2.0xVs ≤ 85 ms
Reset 1.1x to 0.9x ≤ 80 ms
Vs:
1.1xVs to 0 Vs: ≤ 70 ms
7SG1182
1 7
BO 1
See 8
connection 2
9
diagrams BO 2
10
below 3
16
4
BO 3 18
17
+ve 11
5
-ve BI 1 BO 4
6 12
+ve 19
27
BI 2 BO 5
20
+ve 21
26
BI 3 BO 6
22
+ve 23
25
BI 4 BO 7
-ve 24
28
+ve
+ve
13
OPTIONAL
GND
RS485
-ve
14
-ve
15 Earth
Term
Case
earth
Va
1
1
A B C 3 Vab
Va 2
4
Vb
Phase-earth + 3Vo connection
Vc
3
Vbc
4
A B C
Va
1 2 Phase-phase connection
Vb
Note
A B C 3 For the phase-phase and phase-earth
connections, any phasing may be used
4
Phase-phase + 3Vo connection
+ve
13
55 7SG1183 -ve
14
56 Earth 15
See Case
53 earth
connection
diagrams 7
below 54
BO 1 5
51 6
8
52
BO 2 10
+ve 16
3
-ve BI 1 BO 3 18
4
17
EXPANSION PCB 11
EXPANSION PCB
BO 4
+ve 12 +ve
35 35
-ve BI 2 19
BI 2 -ve
36 36
BO 5
+ve 20 +ve
33 33
-ve BI 3 BI 3 -ve
34 21 34
BO 6
31 22 31
-ve BI 4 BI 4 -ve
32 23 32
+ve
BO 7
29 24 +ve
29
-ve BI 5 BI 5 -ve
30 30
+ve
43 37
-ve BI 6 BO 8
44 38
41 40
-ve BI 7 BO 9
42 41
+ve
39
41
-ve BI 8 BO 10
40
42
+ve
37
43
-ve BI 9 BO 11
38
44
Note
For the phase-phase and phase-earth
connections, any phasing may be used
Va
55 55
Vae Vab
56 Va 56
Vb Vb
53 53
Vbe Vc Vbc
54 54
51 51
Vc A B C
A B C
Vae Vac
52 52
3 Phase-earth
connection 3 Phase-phase connection
1) High burden 110V & 220V binary inputs compliant with ESI48-4 ESI 1 available via external dropper resistors with 48V binary input version
for 5 binary inputs and 110 V application, order resistor box VCE:2512H10065 in addition
for 5 binary inputs and 220 V application, order resistor box VCE:2512H10067 in addition
Refer to website for application note about ESI48-4 compliance
2) An additional unit is required for use with capacitor cones, order 7XG2100-1AA00-0AA0
1) High burden 110V & 220V binary inputs compliant with ESI48-4 ESI 1 available via external dropper resistors with 48V binary input version
for 1 binary input and 110 V application, order resistor box VCE:2512H10066 in addition
for 5 binary inputs and 110 V application, order resistor box VCE:2512H10065 in addition
for 9 binary inputs and 110 V application, order resistor box VCE:2512H10064 in addition
for 1 binary input and 220 V application, order resistor box VCE:2512H10068 in addition
for 5 binary inputs and 220 V application, order resistor box VCE:2512H10067 in addition
for 9 binary inputs and 220 V application, order two resistor boxes VCE:2512H10067 in addition
Refer to website for application note about ESI48-4 compliance
2) An additional unit is required for use with capacitor cones, order 7XG2100-1AA00-0AA0
www. siemens.com/energy