1 Input Data: Hilti PROFIS Engineering 3.0.61
1 Input Data: Hilti PROFIS Engineering 3.0.61
61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HST3-R M12 hef2
Return period (service life in years): 50
Item number: 2105870 HST3-R M12x115 40/20
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef = 70.0 mm, hnom = 80.0 mm
Material: A4
Evaluation Service Report: ETA-98/0001
Issued I Valid: 10/2/2019 | -
Proof: SOFA design method + fib (07/2011) - after ETAG testing
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm
Anchor plate :
R lx x ly x t = 285.0 mm x 235.0 mm x 12.0 mm; (Recommended plate thickness: 9.0 mm)
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
1 2
max. concrete compressive strain: 0.05 [‰]
max. concrete compressive stress: 1.54 [N/mm ]
2 Tension
resulting tension force in (x/y)=(-68.3/-67.5): 3.079 [kN]
resulting compression force in (x/y)=(-68.3/62.4): 3.079 [kN]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
Group anchor ID
1, 2
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
Group anchor ID
1, 2
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.053 0.440 2.000 20 OK
concrete 0.121 0.704 1.500 64 OK
a a
bN + bV <= 1
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• The anchor plate overlaps the concrete plate edges. A local concrete spalling due to compression has to be checked separately!
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999
8.2 Results
Stress distribution s 11
2
99.18 [N/mm ]
2
-53.14 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
Stress distribution s 22
2
28.70 [N/mm ]
2
-148.76 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
Deformations (z-direction)
1.1 [mm]
-0.4 [mm]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
9 Installation data
2 2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm Anchor type and diameter: HST3-R M12 hef2
Profile: Double flat bar, ; (L x W x T) = 72.0 mm x 35.0 mm x 5.0 mm Item number: 2105870 HST3-R M12x115 40/20
Hole diameter in the fixture: df = 14.0 mm Installation torque: 60 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: 9.0 mm Hole depth in the base material: 88.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 140.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
Hilti HST3 stud anchor with 80 mm embedment, M12 hef2, Stainless steel, installation per ETA-98/0001, with annular gaps filled with Hilti
Filling set or any suitable gap solutions
118.0
y
142.5 142.5
117.5
77.0
185.0
x
117.5
1 2
50.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.61
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11