ADDITIONAL INFORMATION (FAST ENTRY)

for AS800, 2000T, TH02 and 600T SAFETY TX HANDLING


Device: AS800
The AS800 device is an EEPROM Control device and two possible status can be set: BURN to EEPROM and NOT
BURN to EEPROM; BURN to EEPROM means that when a parameter (or a set) is changed, the data are copyed
from RAM to EEPROM by executing the Hart command 39 making changes permanent; NO BURN to EEPROM
means that parameters are changed only in RAM so when the device is reset, data are lost. The operator is
requested to set the BURN or NOT BURN mode in all the menus where data can be changed (CONFIG, TRIM).
Menù Structure:
PV:
Pressure (Default)
Sensor Temperature (F1)
Free Variable (PV in process engineering units not only pressure) (F2)
REVIEW:
TX Info (F1)
Model, Tag, Descriptor, Message, Date, Device Number, Write Lock, Unit (PV), Range (PV URV/
LRV) , Damping, Minimum Span, URL-LRL, Current Limits (NAMUR limits for 4-20 signal),
Current Alarms (Alarm limits on the analog output), Threshold (Integration Constant in %), Zero
Adjuster (Limit for linear function), Cuf Off , Fail Mode, Transfer Function, Meter Option, Local
Keys, Free Var Unit and limits (like the PV but in Process Engineering units instead of inPressure
units), Hardware Revision, Software Revision, UCD, TSD, Final Assembly number,Flange Type,
Flange Material, Vents, Remote Seal Number, Remote Seal Type, Remote Seal Fill Fluid, Remote
Seal Isolator Material, Module Fill Fluid, Module Isolator Material, Modul Range , Module Type.
CONFIG:
Chng IO (F1)
Diff. Pressure Units, Range (Urv, Lrv), Damping, Transfer Function, Current Limits (NAMUR),
Current Alarms, Threshold, Free Variable Units, Free Var. Range, Fail Mode, Cut Off, Zero
Adjuster, Meter Option, Local Keys
Xmtr Info (F2)
Tag, Date, Descriptor, Message
Gen Conf (F3)
Polling Address
Dbase Mem (F4)
Tag List (F1)
Save Conf (F2)
Send Conf (F3)
Delete Conf (F4)
Data Stored:Tag, Manufacture, TX Type, UID, PV Units, Stat P Units, Sensor T Units,
Message, Descriptor, Date, PV Lrv, PV Urv, Damping, TFR Function, Current
Limits, Current Alarms, Threshold, Meas type, AD Convert, Free Var Units, Free
Var Range, Cut Off, Trip Point, Alarm Selection
SERIAL:
Load Prog (F1)
Dbase Mode (F2)
Modem Mode (F3)
TRIM:
Sensor Trim (F1)
Full Trim (F1)
Zero Trim (F2)
Temp Trim (Only zero trim) (F3)
4-20 mA Trim (F2)
Other Scale (F1)
4 to 20 mA (F2)
Loop Test (F3)
4 mA (F1)
20 mA (F2)
Other (F3)

-1-
. . . ADDITIONAL INFORMATION (FAST ENTRY)
for AS800, 2000T, TH02 and 600T SAFETY TX HANDLING

Device: 2000T (P, DP, MV)


Depending on the primary element, some parameters can be visualized or not. A note is where this selection is done.
Menù Structure:
PV:
Free Variable (Default)
Pressure (F1)
Static Pressure (F2)
Sensor Temperature (F3)
Process Temperature (F4)
REVIEW:
TX Info (F1)
Model, Tag, Descriptor, Message, Date, Device Number, Write Lock, Unit (Press ) Range (Press
URV/LRV) , Damping, Minimum Span, URL-LRL, Current Limits (NAMUR limits for 4-20 signal),
Current Alarms (Alarm limits on the analog output), Threshold (Integration time Constant ), Zero
Adjuster (Limit for linear function), Cuf Off , Fail Mode, Free Var Units, Free Var Range (Urv,Lrv),
Transfer Function, Alarm Limits, Warning Limits, Alarm Histeresys, Meter Option, Local Keys,
Static Pressure Units (DP Only), Static Press. Range (Lrv,Urv DP Only), Sensor Temperature
Units, Hardware Revision, Software Revision, UCD, TSD, Final Assembly number, Flange Type,
Flange Material, O-Ring, Vents, Remote Seal Number, Remote Seal Type, Remote Seal Fill Fluid,
Remote Seal Isolator Material, Module Fill Fluid, Module Isolator Material, Modul Range , Module
Type.
CONFIG:
Chng IO (F1)
Write Enable, Press Unit (Not for MV), Press Range (Lrv-Urv Not for MV), Free Var Units (Not for
MV), Free Var Range (Lrv-Urv Not for MV), Static Press Units (Only DP), Temperature Units (Not
for MV), Transfer Function (Not for MV), Damping, Zero Adjuster, Cut Off, Current Limits, Current
Alarms, Fail Mode, Meter Option, Local Keys, Threshold, Alarm Limits (low-High), Warning Limits
(low-High), Histeresys (low-high).
Xmtr Info (F2)
Tag, Date, Descriptor, Message
Gen Conf (F3)
Polling Address
Dbase Mem (F4)
Tag List (F1)
Save Conf (F2)
Send Conf (F3)
Delete Conf (F4)
Data Stored:Tag, Manufacture, TX Type, UID, PV Units, Stat P Units, Sensor T Units,
Message, Descriptor, Date, PV Lrv, PV Urv, Damping, Temp Units, Temp Range,
TFR Function, Current Limits, Current Alarms, Threshold, Meas type, AD
Convert, Free Var Units, Free Var Range, Cut Off, Trip Point, Alarm Selection,
Static Pressure Range.
SERIAL:
Load Prog (F1)
Dbase Mode (F2)
Modem Mode (F3)
TRIM:
Sensor Trim (F1)
Full Trim (F1)
Zero Trim (F2)
Static Press Trim (F3)
Temp Trim (Only zero trim) (F4)
4-20 mA Trim (F2)
Other Scale (F1)
4 to 20 mA (F2)
Loop Test (F3)
4 mA (F1)
20 mA (F2)
Other (F3)
-2-
. . . ADDITIONAL INFORMATION (FAST ENTRY)
for AS800, 2000T, TH02 and 600T SAFETY TX HANDLING

Device: TH02
The TH02 device is an EEPROM Control device and two possible status can be set: BURN to EEPROM and NOT
BURN to EEPROM; BURN to EEPROM means that when a parameter (or a set) is changed, the data are copyed
from RAM to EEPROM by executing the Hart command 39 making changes permanent; NO BURN to EEPROM
means that parameters are changed only in RAM so when the device is reset, data are lost. The operator is
requested to set the BURN or NOT BURN mode in all the menus where data can be changed (CONFIG, TRIM).
Menù Structure:
PV:
Primary Variable - Temp. + Analog Output
Sensor Temperature (F1)
Sensor 1 (F2)
Sensor 2 (F3)
REVIEW:
TX Info (F1)
Tx type, Manufacturer, Tag, Descriptor, Message, Date, Device Number,H/W Write Protection,
Units, Range (LRV, URV), Damping, Limits Units, Minimum Span, Limits (LRL, URL), Sensor type,
Select Input, Channels, Main Supply, Wires, Serial Sensor, Break Monitoring, Short Monitoring (1
and 2) Cold Junction Compensation Temperature, Max temperature for Sensor, Limits (High, Low)
for saturation output, Threshold (1 and 2), ST1+Rel+led, ST2+Rel+led, Sensor error, Device Error,
Text 1, Text 2, Final Assembly number, H/W, S/W, UCD, TSD.
CONFIG:
Chng IO (F1)
Sensor type, Units, Range (LRV, URV), Damping limits (High, Low), Threshold (1 and 2)
Xmtr Info (F2)
Tag, Date, Descriptor, Message
Gen Conf (F3)
Polling Address
Dbase Mem (F4)
Tag List (F1)
Save Conf (F2)
Send Conf (F3)
Delete Conf (F4)
Data Stored: same as for Generic Hart device: see APPENDIX "D"
SERIAL LINK:
Dbase Mode (F1)
Modem Mode (F2)
Load Prog (F3)
TRIM:
4-20 mA Trim (F2)
Other Scale (F1)
4 to 20 mA (F2)
Factory Preset (F3)
Reset factory trim (F4)
Loop Test (F3)
4 mA (F1)
20 mA (F2)
Other (F3)

-3-
. . . ADDITIONAL INFORMATION (FAST ENTRY)
for AS800, 2000T, TH02 and 600T SAFETY TX HANDLING

Device: 600T Safety


Menù Structure:
PV:
Pressure + Analog Output
Static Pressure (F1)
Sensor Temperature (F2)
REVIEW:
TX Info (F1)
Tx type, Manufacturer, Tag, Descriptor, Message, Date, Device Number, Max Working Pressure,
Max Sensor Temperature, Min Sensor Temperature, H/W Write Protection, Units, Range (LRV,
URV), PV Bias Value, Damping, Output transfer function, SQR(x) out linear, Limits Units, Minimum
Span, Limits (LRL, URL), Operating Limits (LRL, URL), Up/Down Scale, Polynomial Coefficients,
Double Polynomial Coefficients, 1st Polynomial High Limits, Flange type, Flange Material, O-
Rings, Vents, Nr of Remote Seal, Remote Seal type, Remote Seal fill, Run Seal Isolator, Sensor
Fill Fluid, Sensor Isolator Material, Model type, Sensor Range, Local adjustment, Local Keys
Control, Final Assembly Number, PV Sensor Serial Number, Status, Calibration type, Procedure
type, Product Code, Sep. &/or Services, Manifold or Orifice, H/W and S/W release.
CONFIG:
Chng IO (F1)
Status, Units, Range (LRV, URV), Damping, Output transfer function, SQR (x) Cut Linear,
Polynomial Coefficients, Double Polynomial Coefficients, Sensor Temperature Units, Static
Pressure Units.
Xmtr Info (F2)
Tag, Date, Descriptor, Message
Gen Conf (F3)
Local Keys
Database Memory (F4)
Tag List (F1)
Save Configuration (F2)
Send Configuration (F3)
Delete Configuration (F4)
Data Stored: same as for 600T EN Series transmitter: see APPENDIX "D"
SERIAL LINK:
Dbase Mode (F1)
Modem Mode (F2)
Load Prog (F3)
TRIM:
Sensor Trim (F1)
Full Trim (F1)
Zero Trim (F2)
Stat Trim (F3)
Factory Trim (F4)
4-20 mA Trim (F2)
Other Scale (F1)
4 to 20 mA (F2)
Factory trim (F3)
Loop Test (F3)
4 mA (F1)
20 mA (F2)
Other (F3)
Calibration (F4)
PV Scale (F1)
SUPP_IME691HT (Feb02)

Out % Reranging (F2)


Reranging (F3)
Clock Monit. test (F4)