www.invertek.co.uk
Company Overview
UK Head Office
Welshpool
ii www.invertek.co.uk
Global sales, service & application support
network in over 80 countries
UK
Head Office
RUSSIA
CZECH REPUBLIC
SPAIN
USA CHINA
Service Centre
SINGAPORE
SOUTH AFRICA
AUSTRALASIA
yy Conveyors
yy HVAC
yy Machine Tools
yy Manufacturing
yy Pumping
yy Process Control
yy Elevators
yy Cranes
iii
AC Variable Speed Drives
Global Drive Solutions
Pages 2–7
Options
IP66 : 40°C
V/F, Energy Optimised, Sensorless & Closed Loop
Control Modes
Vector, Open Loop Permanent Magnet
OPTIDRIVE P2 & HVAC OPTIONS 22 Maximum Output Hz
Linear / Variable Torque Control
500
Linear
Plug-in Modules, Mains Isolator 150% - 60 Secs
200% - 3.75 Secs
Overload Capacity
250% - 1.8 Secs
CONFIGURATION / MONITORING 23 300% (max) - 1.25 Secs
Optiport 2, Optipad Internal EMC Filter Unit Available All models provided with Internal EMC filter
Standard Frame Sizes 2-5
Internal Brake Transistor
Optional Frame Sizes 6 and above
SOFTWARE / COMMISSIONING 24 3 x Programmable Digital Inputs
IP66: Power Isolator only (Optional Factory Fit) IP55: Optional Factory Fit IP66: Optional Factory Fit
Optional Factory Fit
IP55: Power Isolator only (Option) IP66: Optional Factory Fit Note: Reverse not possible
No No No No
24VDC @ 100mA 24VDC @ 100mA 24VDC @ 100mA
24VDC @ 100mA
10VDC @ 10mA (for potentiometer) 10VDC @ 10mA (for potentiometer) 10VDC @ 10mA (for potentiometer)
IP20: 7 Segment LED
7 Segment led 7 Segment LED None
IP55 & IP66: OLED
7-Seg = 5 button (start, stop, up, down, Navigate)
5 button (start, stop, up, down, Navigate) 5 button (start, stop, up, down, Navigate) Optional Remote
OLED = 7 button (start, stop, up, down, Navigate,Hand, Auto)
Yes No No No
Yes (PID) Yes (PI) Yes (PI) Yes (PID)
Yes Yes No Yes
Yes Yes, Frames 2-3 No Yes
Yes No No No
Yes No No Yes
Yes No No No
Yes No No No
IP55: External Option
IP66: Factory Fit Option IP66: Factory Fit Option No
IP66: Factory Fit Option
Yes (Requires Optistick) Yes (Requires Optistick) Yes (Requires Optistick) No
OptiStick OptiStick OptiStick No
Modbus RTU / BACnet Modbus RTU Modbus RTU No
Optistore V3 Optistore V3
Optitools Studio Optistore V3
OptiTools Studio (OTS) OptiTools Studio (OTS)
Licensed Software Tool No No No
Not Available OptiWand OptiWand OptiWand
OPT-2-OPORT, OPTIPAD OPT-OPORT, OPT-2-OPORT OPT-OPORT, OPT-2-OPORT OD-OPRTP
OPT-2-CASCD-IN
OPT-2-EXTIO-IN OPT-HVACO-IN OPT-HVACO-IN
OPT-2-BACNT-IN ODP-2ROUT-IN ODP-2ROUT-IN
None Available
OPT-2-PROFB-IN OPT-LOGIP-11-IN OPT-LOGIP-11-IN
OPT-2-ETHNT-IN OPT-LOGIP-23-IN OPT-LOGIP-23-IN
OPT-2-DEVNT-IN
CE, UL, cUL CE, UL, cUL, C-Tick, Gost CE, UL, cUL, C-Tick, Gost CE, UL, cUL, C-Tick, Gost
1.02
Powerful PC based
commissioning software
OptiTools Studio allows parameter
upload, download and storage and access OPTISTICK
Up to 160kW Up to 7.5kW to Optidrive P2 Simple PLC functionality. Fast parameter copying between drives
See Page 24
2 www.invertek.co.uk
Processing Plants Chemical
Conveyer SystemsPlastics
Manufacturing Rubber
Pumping Machine Tools Elevators Cranes
Convenient
Help Card
Pluggable
Terminals
High Quality
Long-life Fans
3
High Performance | Easy to Use
Supply Supply
Optidrive P2 features a safe torque off function to allow
Input Contactor
simple integration into machine critical safety circuits. Machine
Safety Circuit
NOT required Machine
Safety Circuit
Input
Contactor
Optidrive
yy Simple machine design reduces component costs, saves panel space P2
4 www.invertek.co.uk
Advanced Motor Control
Invertek has developed advanced
mathematical algorithms and uses the
very latest hardware technology to ensure
Optidrive P2 provides exceptional motor
control with a simple interface to help
users easily apply the benefits to their
applications.
IP20 IP55 IP66
Panel mount units Wall mount units Wall mount units
available up to 11kW available up to 160kW available up to 7.5kW
With today’s ever increasing energy costs, efficiency Furthermore, Optidrive P2 has been designed and The blue line represents what will be considered a
has long been a key factor in relation to drive system developed to work with all PM motors, and control “high efficiency” solution using an efficient IM motor,
component selection. In many cases, an efficiency them with Optimum efficiency, providing the most a modern AC drive and efficient gearbox.
figure can be arrived at by simply multiplying the efficient PM motor control available.
efficiencies of the various components together The red line represents efficiency of a typical PM
to find a combined efficiency figure, however this The graphs below clearly demonstrate these two motor and drive solution. Efficiency is improved at
may not tell the whole story. The efficiency of factors: high speeds and loads, however it is actually reduced
components such as drives, motors and gearboxes yy The overall efficiency of the system varies with at very low loads, and output torque cannot be
can vary considerably with speed and load, hence speed and load and is not a constant maintained at low speeds.
simply combining the ‘headline’ efficiency figures can
yy Motor control efficiency significantly affects The green line represents the Optidrive P2
often be very misleading. In reality, the efficiency
overall system efficiency controlling the same PM motor. Efficiency is
curves for the whole system should be overlaid, to
provide a true efficiency figure for the system across improved at all speeds and loads.
The graphs are generated by measuring the electrical
the desired speed and load range.
power drawn from the mains supply compared to In simple terms, Optidrive P2 PM motor control
the torque generated at the output shaft. These produces the maximum amount of output shaft
Modern AC inverters will typically have an electrical
are based on a system requirement of 2.2kW torque per electrical kW consumed across all speed
efficiency of around 98%, which represents the
motor power. and torque ranges.
different between the electrical output power
compared to electrical input power only. A further
factor that is often overlooked is the efficiency of the
motor control strategy employed by the drive. This
can have a significant effect on the overall system Improvement in Efficiency at Improvement in Efficiency at
efficiency, and is often not considered when energy 100% Rated Speed Output 10% Rated Speed Output
saving calculations are made. 83.0%
Comparative Efficiency
Comparative Efficiency
57.0%
47.0%
Standard IM Standard IM
meet the IE2 efficiency standards currently in 68.0%
Typical PM Drive
37.0%
Typical PM Drive
58.0%
0 20 40 60 80 100 0 20 40 60 80 100
can be purchased now, allowing for a future update
of the motor without requiring a change to the Load (%) Load (%)
installed drive.
5
r
y isplay
s to
ing
a l B r a ns sto r
nsi
oat
a ke i s t o r
ed
Dis D D
Tra
l C d C o ng
i
ma g
lC
i tc h
I n t r a ke a n s
on atin
on d
i
ED t LE
ns
ns
-s w
t
pla
re
6 N he
a
r
T
tio
tio
fo r
N o ke T
St a C o
r
IP6 Switc
IP2 su
e
OL en
7 S l ay
e
Op
Op
od
od
r
egm
clo
e
e
r R ge
r R ge
a
sp
B
er n
a ng
a ng
g
nd
uil d
uil d
lC
B
lC
EM er Tyses
EM er Tyses
a
lta
lta
atin
atin
C F pe
C F pe
0
0
6
5
Fr a a t i o n
Fr a a t i o n
PC
ply ze
ply ze
En
Br
r
IP6
IP5
IP4
Di
Fu l
ct R
ct R
Vo
Vo
i l te
i l te
yB
yB
w a
w a
de
de
S up e S i
S up e S i
Po Ph
Po t Ph
r
r
to r
to r
du
du
Mo
Mo
we
we
ne
ne
ut
m
u
kW HP Amps Size Factory Build Options
Pr o
Pr o
Fa c
Fa c
Inp
Inp
Ge
Ge
Po
Po
kW
HP
0.75 1 4.3 2 ODP - 2 - 2 2 075 - 1 K F 4 # - # # ODP - 2 - 2 2 010 - 1 H F 4 # - # # 4 2 X Y S T N C
200 – 240V ± 10%
1.5 2 7 2 ODP - 2 - 2 2 150 - 1 K F 4 # - # # ODP - 2 - 2 2 020 - 1 H F 4 # - # # 4 2 X Y S T N C
1 Phase Input
2.2 3 10.5 2 ODP - 2 - 2 2 220 - 1 K F 4 # - # # ODP - 2 - 2 2 030 - 1 H F 4 # - # # 4 2 X Y S T N C
kW Models: Factory Settings HP Models: Factory Settings Replace # in model code with colour-coded option
Motor Rated Frequency: 50Hz Motor Rated Frequency: 60Hz IP20 units are available with 7 Segment LED Display only
Motor Rated Voltage: 400V Motor Rated Voltage: 460V
NOT TO SCALE
Size 2 2 3 3 4 5 6 7 8
Enclosure IP20 IP66 IP20 IP66 IP55 IP55 IP55 IP55 IP40
Height (mm) 221 257 261 310 440 540 865 1280 2000
Width (mm) 112 188 131 211 173 235 330 330 516
Depth (mm) 185 239.5 205 251.5 230 270 340 370 500
Weight (kg) 1.8 4.8 3.5 7.3 11.5 22.5 50 80 270
D
W
6 www.invertek.co.uk
Drive Specification
Input Ratings 200 – 240V ± 10% Programming Built-in Keypad as standard I/O 24 Volt DC, 100mA, Short Circuit
Supply Voltage Keypad
380 – 480V ± 10% Optional remote mountable keypad Specification Power Supply Protected
10 Volt DC, 5mA for Potentiometer
Supply Optional OLED or LED display (OLED
48 – 62Hz Display
Frequency Display Multi Language) 5 Total as standard (Optional additional 3)
Programmable
Displacement PC OptiTools Studio
> 0.98 Inputs 3 Digital (Optional additional 3)
Power Factor
2 Analog / Digital Selectable
Control V/F Voltage Vector
Phase
3% Maximum allowed Specification Energy Optimised V/F 10 – 30 Volt DC, internal or external
Imbalance
Sensorless Vector Speed Control Digital Inputs supply, NPN
Inrush Current < rated current Sensorless Vector Torque Control Response time : < 4ms
Control
Closed Loop (Encoder) Speed Control
Power Cycles 120 per hour maximum, evenly spaced Method Resolution : 12 bits
Response time : < 4ms
Closed Loop (Encoder) Torque Control Analog Inputs
Output Ratings 230V 1 Phase Input: 0.75–2.2kW (1–3HP) Accuracy : < 1% full scale
230V 3 Phase Input: 0.75–75kW (1–100HP) Parameter adjustable scaling and offset
Output Power Open Loop PM Vector Control
400V 3 Phase Input: 0.75–250kW 4 Total (Optional additional 3)
460V 3 Phase Input: 1–350HP PWM Programmable
4 – 32kHz Effective 2 Analog / Digital
Frequency Outputs
Overload 2 Relays (Optional additional 3)
150% for 60 seconds Ramp to Stop : User Adjustable 0.1 – 600
Capacity Maximum Voltage : 250 VAC, 30 VDC
Stopping Mode seconds
Output Relay Outputs Switching Current Capacity : 6A AC,
0 – 500Hz, 0.1Hz resolution Coast to Stop
Frequency 5A DC
Motor Flux Braking
Typical 0 to 10 Volt
98% Braking Built-in Braking Transistor (Optional for
Efficiency Analog Outputs 0 to 20mA
frame sizes 6 & 7)
4 to 20mA
Ambient Storage : −40 to 60°C Skip Frequency Single point, user adjustable
Temperature Hoist
Conditions Operating : −10 to 40°C 0 to 10 Volts Control Dedicated Hoist Operation Mode
Features Operation
Up to 1000m ASL without derating 10 to 0 Volts
Up to 2000m maximum UL Approved −10 to 10 Volts PID Control Internal PID control with feedback display
Altitude Analog
Up to 4000m maximum (non UL) 0 to 20mA
Signal
Above 1000m : Derate by 1% per 100m 20 to 0mA Maintenance & Fault Memory Last 4 Trips stored with time stamp
4 to 20mA Diagnostics
Humidity 95% Max, non-condensing 20 to 4 mA Logging of data prior to trip for diagnostic
Setpoint
purposes :
Control Data Logging
IP20 (Size 2, 3) Motorised Potentiometer Output Current, Drive Temperature,
Enclosure
Ingress IP40 (Size 8) (Keypad) DC Bus Voltage
Digital
Protection IP55 (Size 4, 5, 6, 7) Modbus RTU
CANopen Maintenance Indicator with user adjustable
IP66 (Size 2, 3) Maintenance
maintenance interval
Indicator
Profibus DP, DeviceNet, Onboard service life monitoring
Optional
EthernetIP
Hours Run Meter
Monitoring
Resettable & Non Resettable kWh meters
Key Features
Input to
Optidrive HVAC
yy Dedicated HVAC drive for centrifugal fan and
pump applications
yy Built-in EMC Filter as standard
yy IP55 Enclosed
Flow (%)
yy Multi Language Plain Text OLED display
yy Energy optimisation maximises operating
efficiency Example savings based on a
yy BACnet and Modbus RTU provided as standard 45kW load
yy Built-in Hours Run kWh meters 35000
Up to 160kW Up to 7.5kW
8 www.invertek.co.uk
Service
Indicator
Hand/Auto
Selection
High Quality
Long-life Fans
Fire override mode ignores In the event of a fire, stairwells Energy Optimisation and
signals and alarms, keeping the are often essential escape Monitoring
The advanced optimisation function
Optidrive HVAC operating for routes. intelligently matches energy usage to the
as long as possible. driven load to ensure your fan operates
Optidrive HVAC can be used to control
air flow and pressure to help keep at maximum efficiency. The in-built
This feature is crucial for ensuring smoke energy consumption meters allow energy
extraction from buildings in the event of stairwells clear of smoke to allow safe
evacuation and give firefighters safe access consumption to be clearly displayed and
a fire. savings to be calculated.
to buildings.
Selectable logic means that the Optidrive
HVAC can be easily configured to the Intelligent Standby
signal produced by your fire management To reduce energy used by slow-running
system. fans, Optidrive HVAC has an intelligent
standby/sleep function to shut off output
With an independently set speed for from the drive until demand for air flow
fire mode operation, selectable as increases.
either forward or reverse direction,
the Optidrive HVAC has the flexibility
to match the needs of your fire control Broken Belt Detection
system. Optidrive HVAC intelligently monitors
current/speed to provide immediate
warning of broken belts between motors
and ventilation fans.
Resonance Avoidance
Optidrive HVAC can be easily configured
PID Control to avoid frequencies that cause resonance
in ventilation systems, preventing
The Optidrive HVAC has a PID controller built in that is fully integrated with both unnecessary noise and mechanical damage
HVAC and energy efficient features and is packaged in a user friendly way to to motors and fans.
ensure ease of use and fast commissioning.
9
Energy Efficient Pump Control
A standard feature on
every Optidrive HVAC
Setpoint Control
10 www.invertek.co.uk
Pump Efficiency Drive Controlled Bypass Avoid Pump Downtime
In-built Sleep Mode with Intelligent features within the Optidrive Blockage Detect/Clear
Auto-boost HVAC allow a bypass circuit to be Optidrive HVAC can detect pump
Sleep mode saves energy by detecting
implemented. Activation of Bypass blockages and trigger a programmed
when a pump is running inefficiently and mode can be determined intelligently cleaning cycle to automatically clear them,
producing little useful work. Optidrive by the Optidrive HVAC drive based preventing downtime.
HVAC can be programmed to enter on a command from the building
into a sleep/disabled mode until the management system. The drive can be Pump Clean/Stir Cycle
demand increases. To help prevent sleep set to automatically select bypass mode
Triggered by a settable period of inactivity,
mode oscillation, Optidrive HVAC can when entering into a trip condition
a configurable cleaning cycle can be run to
automatically initiate a boost cycle to ensuring minimal disruption to service. clear sediment, ensuring the pump is ready
increase pressure on starting or stopping. to run when needed.
Relay Cascade Control (requires optional cascade module) Motor Preheat Function
Optidrive HVAC features a motor preheat
3-Phase Mains Input Supply With Additional Relay Module function to help ensure moisture is not
Variable speed duty pump permitted to collect on the motor in
with up to 4 assist pumps periods of inactivity and prior to motor
Optidrive HVAC can provide automatic start up. In addition, the motor preheat
operating time monitoring and balancing function can be used to keep condensation
Relay 1 Output
for assist pumps to share duty cycle. Run from developing on the motor as the
Relay 2 Output
Relay 3 Output time clocks for all fixed speed assist pumps motor cools down immediately following
Relay 4 Output
are maintained and visible within the a stop. The feature is fully configurable,
Sensor
feedback to Master Slave Slave Slave Slave Optidrive HVAC for integration into the meaning the pump can be always available
drive PID Pump Pump 1 Pump 2 Pump 3 Pump 4
pump system maintenance schedules. the instant it is required.
Sensor
Pump Output Channel
11
y isplay
g
atin
o
Dis D D
r
Fu l a r d C t i n g
ma g
lC
a to
on oatin
ED t LE
ns
ns
pla
re
I so
a
tio
tio
fo r
St a B C o
IP2 su
e
OL en
7 S p l ay
e
i th
Op
Op
od
r
od
s to
s to
egm
clo
e
e
r R ge
r R ge
6w
a ng
a ng
g
lC
nd
uil d
uil d
lC
lC
EM er Tyses
EM er Tyses
lta
nsi
lta
nsi
atin
atin
C F pe
B r a F i l te e
0
0
6
5
s
Fr a a t i o n
Fr a a t i o n
C
ply ze
ply ze
En
p
ke r
ke r
IP6
IP6
IP5
IP4
Di
ct R
ct R
Vo
Vo
B r a i l te
Tra
Tra
yB
yB
w a
w a
de
P
de
S up e S i
S up e S i
Po Ph
Po t Ph
r
r
to r
to r
du
du
Mo
Mo
we
we
ne
ne
ut
m
C
u
kW HP Amps Size Factory Build Options
Pr o
Pr o
Fa c
Fa c
Inp
Inp
Ge
Ge
Po
Po
kW
HP
0.75 1 4.3 2 ODV - 2 - 2 2 075 - 1 K F 1 # - # # ODV - 2 - 2 2 010 - 1 H F 1 # - # # 2 X D S T N C
200 – 240V ± 10%
1.5 2 7 2 ODV - 2 - 2 2 150 - 1 K F 1 # - # # ODV - 2 - 2 2 020 - 1 H F 1 # - # # 2 X D S T N C
1 Phase Input
2.2 3 10.5 2 ODV - 2 - 2 2 220 - 1 K F 1 # - # # ODV - 2 - 2 2 030 - 1 H F 1 # - # # 2 X D S T N C
kW Models: Factory Settings HP Models: Factory Settings Replace # in model code with colour-coded option
Motor Rated Frequency: 50Hz Motor Rated Frequency: 60Hz IP20 units are available with 7 Segment LED Display only
Motor Rated Voltage: 400V Motor Rated Voltage: 460V
NOT TO SCALE
Size 2 2 3 3 4 5 6 7 8
Enclosure IP20 IP66 IP20 IP66 IP55 IP55 IP55 IP55 IP40
Height (mm) 221 257 261 310 440 540 865 1280 2000
Width (mm) 112 188 131 211 173 235 330 330 516
Depth (mm) 185 239.5 205 251.5 230 270 340 370 500
Weight (kg) 1.8 4.8 3.5 7.3 11.5 22.5 50 80 270
D
W
12 www.invertek.co.uk
Drive Specification
Input Ratings 200 – 240V ± 10% Control Control Variable Torque V/F Control Selectable direction
Supply Voltage Fire Mode
380 – 480V ± 10% Specification Method Variable Torque Energy Optimised V/F Features Selectable speed reference
Supply PWM Broken Belt Under load monitoring with autotune
48 – 62Hz 4 – 32kHz Effective
Frequency Frequency Detection configuration
Displacement Ramp to Stop : User Adjustable 1 – 600 PID Control Internal PID control with feedback display
> 0.98
Power Factor Stopping Mode seconds
Coast to Stop Pump Control Pump Blockage Pump load monitoring with autotune
Phase
3% Maximum allowed Features Detection function, user configurable
Imbalance Braking Motor Flux Braking
Pump Cleaning Adjustable Pump Cleaning Cycle operation
Inrush Current < rated current Skip Frequency Single point, user adjustable
Control of fixed speed assist pumps via
Power Cycles 120 per hour maximum, evenly spaced 0 to 10 Volts
optional cascade control module
10 to 0 Volts Multi-pump
Control of Duty, Assist and Standby variable
Output Ratings 230V 1 Phase Input: 0.75–2.2kW (1–3HP) −10 to +10 Volts Control
Analog speed pumps via internal Master – Slave
230V 3 Phase Input: 0.75–75kW (1–100HP) 0 to 20mA
Output Power Signal network
400V 3 Phase Input: 0.75–250kW 20 to 0mA
460V 3 Phase Input: 1–350HP 4 to 20mA Pump Stir Automatic pump stir function
Setpoint 20 to 4 mA
Overload
110% for 60 seconds Control Maintenance & Fault Memory Last 4 Trips stored with time stamp
Capacity Motorised Potentiometer
(Keypad) Diagnostics Logging of data prior to trip for diagnostic
Output Digital
0 – 120Hz, 0.1Hz resolution Modbus RTU purposes :
Frequency BACnet Data Logging
Output Current, Drive Temperature,
Typical DC Bus Voltage
98% BACnet/IP, Profibus DP,
Efficiency Optional
DeviceNet, EtherNet/IP Maintenance Indicator with user adjustable
Maintenance
maintenance interval
Ambient Storage : −40 to 60°C Indicator
Temperature I/O 24 Volt DC, 100mA, Short Circuit Onboard service life monitoring
Conditions Operating : −10 to 40°C Power Supply Protected
Specification Hours Run Meter
Up to 1000m ASL without derating 10 Volt DC, 5mA for Potentiometer Monitoring
Resettable & Non Resettable kWh meters
Up to 2000m maximum UL approved 5 Total as standard (Optional additional 3)
Altitude
Up to 4000m maximum (non UL) Programmable
Above 1000m : Derate by 1% per 100m Standards EN 61800- Adjustable speed electrical power drive
Inputs 3 Digital (Optional additional 3)
Compliance 3:2004 systems. EMC requirements.
Humidity 95% Max, non-condensing 2 Analog / Digital Selectable
10 – 30 Volt DC, internal or external
Enclosure IP20 (Frame sizes 2 & 3) Digital Inputs supply, NPN
Ingress IP66 (Frame sizes 2 & 3; up to 7.5kW) Response time : < 4ms
Protection IP55 (Frame sizes 4 – 7)
IP40 (Frame size 8) Resolution : 12 bits
Response time : < 4ms
Analog Inputs
Programming Built-in keypad as standard Accuracy : < 1% full scale
Keypad Parameter adjustable scaling and offset
Optional remote mountable keypad
Built-in multi language OLED display 4 Total (Optional additional 3)
Programmable
Display (except IP20) 2 Analog / Digital
Outputs
LED display (IP20 only) 2 Relays (Optional additional 3)
General Purpose
Dedicated to low power applications, Optidrive E2 combines
innovative technology, reliability, robustness and ease of use in
a range of compact IP20 & IP66 enclosures
Key Features
55
Intuitive Keypad Control 55
Brake Chopper (Sizes 2 & 3)
Precise digital control at the touch of a button. Dynamic & compact options with heatsink
mounted resistor.
55
Simple Commissioning
12 parameter basic setup. Default settings 55
High Overload Capability
suitable for most applications. Contactor style 150% overload for 60 seconds.
connection for simple wiring. 175% overload for 2 seconds.
55
Integral RFI Filter 55
Industrial Ambient Ratings
Options for built-in and external filters for full IP20 Enclosure: 50°C
EMC compliance. IP66 Enclosure: 40°C
55
Modbus RTU
Easy integration with your control & monitoring
systems.
55
Compact Enclosures
Small mechanical envelopes to help minimise
your space requirements.
14 www.invertek.co.uk
Processing Plants Chemical Conveyer Systems
Bottling HVAC Woodworking
Pumping Baggage Handling Agricultural Mining
IP20 IP66
Available up to 11kW Available up to 7.5kW
Convenient
Help Card
Optistick
Programming
Optional Braking
Resistor
15
ed
i l te e r
E M a ge e r
i tc h
C F Fil t
No Volt e Filt
r
Hig Volt a er
on d
-s w
e
6 N he
r
w Fi l t
g
IP6 Switc
IP2 losu
e
e
od
e or
e or
od
e
e
r R ge
r R ge
C
sur is t
sur is t
a ng
a ng
g
g
lC
lC
EM er Tyses
EM er Tyses
c
lta
lta
h
atin
atin
C F pe
C F pe
0
6
cl o a n s
cl o a n s
EM
Fr a a t i o n
Fr a a t i o n
ply ze
ply ze
En
En ke Tr r
En ke Tr r
IP6
ct R
ct R
Vo
Vo
Lo
B r a i l te
B r a i l te
w a
w a
de
de
S up e S i
S up e S i
Po Ph
Po Ph
r
r
du
du
Mo
Mo
we
we
ne
ne
ut
ut
m
m
kW HP Amps Size Factory Build Options
Pr o
Pr o
Inp
Inp
Ge
Ge
Po
Po
kW
HP
110 – 115V ± 10% – 0.5 2.3 1 N/A ODE - 2 - 1 1 005 - 1 H 0 1 # 0 2 X Y
(230V 3 Phase Output) – 1 4.3 1 N/A ODE - 2 - 1 1 010 - 1 H 0 1 # 0 2 X Y
1 Phase Input – 1.5 5.8 2 N/A ODE - 2 - 2 1 015 - 1 H 0 4 # 0 2 X Y
16 www.invertek.co.uk
Model Code Guide Drive Specification
Input Ratings 110 – 115V ± 10% Control Control V/F Voltage Vector
Supply Voltage 200 – 240V ± 10% Specification Method Energy Optimised V/F
ODE-2-12037-3K#1# Supply
380 – 480V ± 10%
PWM
Frequency
4 – 32kHz Effective
48 – 62Hz
Frequency
Ramp to Stop : User Adjustable 0.01 – 600
Product Family Displacement Stopping Mode seconds
> 0.98
Generation Power Factor Coast to Stop
Frame Size Phase Motor Flux Braking
3% Maximum allowed Braking
Imbalance Built-in Braking Transistor (Frames 2 & 3)
110-115V = 1 Supply
200-240V = 2 Voltage Inrush Current < rated current Skip Frequency Single point, user adjustable
380-480V = 4
Power Cycles 120 per hour maximum, evenly spaced 0 to 10 Volts
Power Rating Code
10 to 0 Volts
Single Phase = 1 Input Output Ratings 110V 1 Phase Input: 0.5–1.5HP Analog 0 to 20mA
3 Phase = 3 Phases (230V 3 Phase Output) Signal 20 to 0mA
230V 1 Phase Input: 0.75–4kW (1–5HP) 4 to 20mA
kW = K Power Type Output Power
HP = H 230V 3 Phase Input: 0.75–4kW (1–5HP) Setpoint 20 to 4 mA
400V 3 Phase Input: 0.75–11kW Control
400 Volt EMC Filter = A EMC Filter 460V 3 Phase Input : 1–15HP Motorised Potentiometer
200 Volt EMC Filter = B Digital (Keypad)
No Internal EMC Filter = 0 Overload Modbus RTU
150% for 60 seconds, 175% for 2 seconds
Capacity
No Internal Brake Transistor = 1 Brake Optional Profibus DP, DeviceNet,
Internal Brake Transistor = 4 Transistor Output Gateway EthernetIP
0 – 500Hz, 0.1Hz resolution
Frequency
IP20 = 2 Enclosure
IP66 Non-switched = X I/O Specification 24 Volt DC, 100mA, Short Circuit
IP66 Switched = Y Ambient Storage : −40 to 60°C Power Supply Protected
Temperature
Conditions Operating : −10 to 40°C 10 Volt DC, 5mA for Potentiometer
Up to 1000m ASL without derating 4 Total as standard
Up to 2000m maximum UL Approved Programmable
Altitude 2 Digital
Up to 4000m maximum (non UL) Inputs
2 Analog / Digital Selectable
Above 1000m : Derate by 1% per 100m
10 – 30 Volt DC, internal or external
Humidity 95% Max, non-condensing Digital Inputs supply, NPN
Response time : < 4ms
Control Features PID Control Internal PID control with feedback display
Maintenance & Fault Memory Last 4 Trips stored with time stamp
Diagnostics
Logging of data prior to trip for diagnostic
purposes :
Data Logging
Output Current, Drive Temperature,
DC Bus Voltage
Hours Run Meter
Monitoring
Energy Consumption meter
NOT TO SCALE
D
W
Size 1 2 3 1 2 3
Enclosure IP20 IP20 IP20 IP66 IP66 IP66
Height (mm) 173 221 261 232 257 310
Width (mm) 82 104 131 161 188 210.5
Depth (mm) 123 150 175 175 187 243
Weight (kg) 1.1 2.6 4 2.8 4.6 7.4
Fixings 4 x M4 4 x M4 4 x M4 4 x M4 4 x M4 4 x M4
17
Single Phase 0.37kW – 1.1kW / 0.5HP – 1.5HP
AC Variable Speed Drive 110 – 240V
18 www.invertek.co.uk
ed
i l te r
C F F i l te
i tc h
r
No Volt ter
on d
-s w
e
6 N he
Single Phase
E M a ge
r
w Fi l
IP6 Switc
IP2 su
e
e
od
O u s u r e s i s to r
O u s u r e i s to r
od
clo
es
e
es
e
r R ge
r R ge
C
a ng
a ng
g
g
lC
lC
ha s
ha s
EM er Tyses
EM er Tyses
lta
lta
atin
atin
C F pe
B r a F i l te e
0
6
cl o a n s
EM
Fr a a t i o n
Fr a a t i o n
ply ze
ply ze
cl o a n
En
p
En ke Tr r
En ke Tr r
IP6
ct R
ct R
Vo
Vo
Lo
B r a i l te
w a
w a
de
tP
tP
de
S up e S i
S up e S i
Po Ph
Po t Ph
tpu
tpu
r
r
du
du
Mo
Mo
we
we
ne
ne
ut
m
C
u
kW HP Amps Size Factory Build Options
Pr o
Pr o
Inp
Inp
Ge
Ge
Po
Po
kW
HP
110 – 115V ± 10% – 0.5 7 1 N/A ODE - 2 - 1 1 005 - 1 H # 1 # -01 0 2 X Y
1 Phase Input – 0.75 10.5 2 N/A ODE - 2 - 2 1 007 - 1 H # 4 # -01 0 2 X Y
ODE-2-12037-1K#1#-01
Product
Family
Generation
Frame Size
H
110-115V = 1 Supply
NOT TO SCALE 200-240V = 2 Voltage
380-480V = 4
Drive Specification
Input Ratings 110 – 115V ± 10% Programming Built-in Keypad as standard I/O 24 Volt DC, 100mA, Short Circuit
Supply Voltage Keypad
200 – 240V ± 10% Optional remote mountable keypad Specification Power Supply Protected
10 Volt DC, 5mA for Potentiometer
Supply Display Built-in LED display
48 – 62Hz
Frequency 4 Total as standard
Programming OptiTools Studio / OPTISTICK Programmable
2 Digital
Displacement Inputs
> 0.98 2 Analog / Digital Selectable
Power Factor Control Control
Single Phase V/F with Starting Boost
Specification Method 10 – 30 Volt DC, internal or external
Phase
3% Maximum allowed Digital Inputs supply, NPN
Imbalance PWM
4 – 32kHz Effective Response time : < 4ms
Frequency
Inrush Current < rated current
Resolution : 12 bits
Ramp to Stop : User Adjustable 0.1 – 600 Response time : < 4ms
Power Cycles 120 per hour maximum, evenly spaced Analog Inputs
Stopping Mode seconds Accuracy : < 1% full scale
Coast to Stop Parameter adjustable scaling and offset
Output Ratings Output Power 110V 1 Phase Input: 0.5–0.75HP
230V 1 Phase Input: 0.75–1.1kW (1–1.5HP) Motor Flux Braking 2 Total
Braking Programmable
Built-in Braking Transistor (Size 2 only) 1 Analog / Digital
Overload Outputs
150% for 60 seconds, 175% for 2 seconds 1 Relay
Capacity Skip Frequency Single point, user adjustable
Output 0 to 10 Volts Maximum Voltage : 250 VAC, 30 VDC
0 – 120Hz, 0.1Hz resolution Relay Outputs Switching Current Capacity : 6A AC,
Frequency 10 to 0 Volts
Analog 0 to 20mA 5A DC
Ambient Storage : −40 to 60°C Signal 20 to 0mA Analog Outputs 0 to 10 Volt
Temperature
Conditions Operating : −10 to 40°C 4 to 20mA
Setpoint 20 to 4 mA
Up to 1000m ASL without derating
Control
Control
Up to 2000m maximum UL Approved Motorised Potentiometer PID Control Internal PID control with feedback display
Altitude Features
Up to 4000m maximum (non UL) Digital (Keypad)
Above 1000m : Derate by 1% per 100m Modbus RTU
Maintenance & Fault Memory Last 4 Trips stored with time stamp
Humidity 95% Max, non-condensing Optional Profibus DP, DeviceNet, Diagnostics Logging of data prior to trip for diagnostic
Gateway EthernetIP
purposes :
Enclosure Ingress IP20 Data Logging
Output Current, Drive Temperature,
Protection IP66 DC Bus Voltage
Hours Run Meter
Monitoring
Energy Consumption meter
19
Up to 1.5kW / 2HP
200 – 240V I Phase Input
AC Variable Speed Drive 380 – 480V 3 Phase Input
Key Features
20 www.invertek.co.uk
Model Reference Drive Specification
200 – 240V ± 10 % 1 Phase Input Input Ratings 200 – 240V ± 10%
Supply Voltage
380 – 480V ± 10%
Switched Version Non-switched Version
Supply
Output 48 – 62Hz
Frequency
With EMC Filter Without Filter With EMC Filter Without Filter Current
(A) Displacement
> 0.98
Power Factor
OPC-1-12075-1KB1S OPC-1-12075-1K01S OPC-1-12075-1KB1N OPC-1-12075-1K01N 4.5
OPC-1-12150-1KB1S OPC-1-12150-1K01S OPC-1-12150-1KB1N OPC-1-12150-1K01N 7 Phase
3% Maximum allowed
Imbalance
Inrush Current < rated current
380 – 480V ± 10 % 3 Phase Input
Switched Version Non-switched Version Power Cycles 120 per hour maximum, evenly spaced
Output Output Ratings Output Power 230 Volt 1 Phase Input : 0.75 – 1.5kW (1 – 2HP)
With EMC Filter Without Filter With EMC Filter Without Filter Current 400 Volt 3 Phase Input : 0.75 – 1.5kW (1 – 2HP)
(A)
Overload
OPC-1-14075-3KA1S OPC-1-14075-3K01S OPC-1-14075-3KA1N OPC-1-14075-3K01N 2.2 150% for 60 seconds, 175% for 2 seconds
Capacity
OPC-1-14150-3KA1S OPC-1-14150-3K01S OPC-1-14150-3KA1N OPC-1-14150-3K01N 4.1 Output
0 – 500Hz, 0.1Hz resolution
Frequency
Programmable PC Optistore V3
Control
PID Control Internal PID control with feedback display
Features
Maintenance & Fault Memory Last 4 Trips stored with time stamp
Diagnostics Monitoring Energy Consumption meter
21
OPTIDRIVE P2 & HVAC OPTIONS
22 www.invertek.co.uk
CONFIGURATION / MONITORING
OPTIPORT 2 OPTIPAD
Remote Keypad & LED Display Remote Keypad & OLED Display
Optiport 2 and Optipad units act as the remote keypad and display
for the Optidrive on the network which has the same serial address.
The physical layout and the operation of the Optiport keypad and
display mimic the Optidrive exactly.
Specification
Configuration
Depending on the requirement of the application, Optiport 2 and Optipad keypads can be used in the following different ways:
23
SOFTWARE / COMMISSIONING
OPTISTICK
Rapid Commissioning Tool
Product code: OPT-2-STICK-IN
Powerful PC Software
Drive commissioning and parameter backup
yy Powerful PC based commissioning and programming software yy Allows rapid copying of parameters
yy Multi Drive Network Support between multiple drives
yy Supports two key functions yy Provides Bluetooth wireless interface to a
PC running OptiTools Studio
yy Drive Programming & Commissioning
• Parameter Upload, Download & Storage
yy Backup and restore of drive parameters
• Changed Parameter Highlighting
• Parameter List Printing
Compatible with:
Windows XP, Windows Vista & Windows 7
24 www.invertek.co.uk
DATA CABLES & ACCESSORIES
485AD
PC Connection Kit
Product code: OD-485AD
Configuration
USB Cable
USB-RS485
485AD PC Connection Kit is an isolated USB to RS485 communications Adaptor
Drive Cable
adaptor designed for use with OptiTools Studio
Product code: OPT-RJ45SP (RJ45 1 - 2 way) RJ45 to RJ45 RS485 Data Cable, 0.5m length, Blue
Product code: OPT-J4505
RS485 data cable splitter RJ45 to RJ45 RS485 Data Cable, 1.0m length, Blue
Product code: OPT-J4510
is an R545 1 to 2-way
connection block RJ45 to RJ45 RS485 Data Cable, 3.0m length, Blue
Product code: OPT-J4530
25
INSTALLATION OPTIONS
INPUT CHOKES Input chokes are available for the complete range
of Optidrive products, and are recommended for
Product Codes
OPT-2-L1016-00
use in all installations and in particular: OPT-2-L1025-00
Reduce supply harmonic current distortion and increase protection against
OPT-2-L1035-00
mains voltage spikes and notches yy where the local mains supply quality may be
OPT-2-L3010-00
poor or unknown
Input chokes can be used to reduce the supply line harmonic currents and OPT-2-L3016-00
yy where high current switching loads such as OPT-2-L3036-00
voltage distortion generated by almost all inverter drives on the market
large DC drives or soft starts are operating OPT-2-L3050-00
today. Invertek Drives have selected a range of chokes matched to the
Optidrive range to provide the best reduction in supply current harmonics yy where the mains supply impedance is low OPT-2-L3090-00
whilst also providing enhanced protection for the Optidrive against transient yy in remote areas prone to lightening strikes OPT-2-L3200-00
voltages (‘spikes’) or other mains borne interference. OPT-2-L3300-00
26 www.invertek.co.uk
COMPATIBILITY REFERENCE
Optidrive Compatibility
27
Call Invertek Drives
+44 (0)1938 556868
Crane Control Machine Tool OEM Manufacturing Food Processing Amusement Parks
Demanding application UK machine tool supplier IP66 washdown duty Precision conveyor Reliable control of
at South African mine specifies Optidrive drives in Singapore control in Spain difficult loads in Spain
Invertek Drives Ltd adopts a policy of continuous improvement and whilst every
effort has been made to provide accurate and up to date information, the information
contained in this catalogue should be used for guidance purposes only and does not
form part of any contract.