Professional Documents
Culture Documents
A-CNT-CON-00282
REVISION HISTORY
Revision Changes
Holds
Hold No. Location Description
Page 2 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
Contents
1 INTRODUCTION 5
1.1 Purpose 5
1.2 Project overview 5
1.3 Scope 5
1.4 Regulatory requirements 5
2 REFERENCES 6
2.1 Related engineering specifications and document 6
2.2 Algerian regulations 6
2.3 Codes 6
2.4 Order of Precedence 8
2.5 Standard drawings 8
2.6 Units 8
3 DEFINITIONS 9
4 DESIGN 9
5 MATERIALS 10
5.1 Structural steel and steel pipe 10
5.2 Bolts, nuts and washers 10
5.3 Welding materials 11
5.4 Certificates 11
6 CONNECTIONS 12
6.1 General 12
6.2 Bolted connections 13
6.3 Bracing 14
6.4 Drainage holes 14
6.5 Detail calculations of connections 14
7 DRAWINGS AND CALCULATIONS 14
7.1 General 14
7.2 Marking plan drawings 16
7.3 Shop drawings 17
8 FABRICATION 17
8.1 General 17
8.2 Workmanship 18
8.3 Welding 19
8.4 Inspection and testing 20
8.5 Inspection of cold formed components and sheeting fasteners 21
8.6 Surface protection 22
8.7 MARKING 22
9 PACKING, TRANSPORTATION AND STORAGE 23
9.1 General 23
Page 3 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
Page 4 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
1 INTRODUCTION
1.1 PURPOSE
The scope of this specification is to identify the minimum quality and technical
requirements for materials, equipment, labour, inspection, and necessary testing to
accomplish the fabrication, to deliver and to erect the structural and miscellaneous steel.
1.3 SCOPE
This Specification covers the minimum requirements for the materials, fabrication and
erection of steel frame buildings (defined as an enclosed structure), steel structures,
supporting steel for equipment, steel pipe racks and miscellaneous structural steel, such
as steel platforms, stairs, ladders, grating, trolley beams, etc., but excluding steel (sheet)
piling and fencing.
Page 5 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
C.T.C. may carry out site visit’s to inspect the preparation of steel structures and inspect
the erection of the steel work.
The CONTRACTOR shall agree the requirements and procedures for submission and
approval of documentation and for the visits and shall conclude a contract with C.T.C.
for their services.
2 REFERENCES
2.3 CODES
Page 6 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
Page 7 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
ASTM A153M Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware.
ASTM A307 Standard Specification for Carbon Steel Bolts, Studs and Threaded
Rod.
ASTM A325 Standard Specification for Structural Bolts
ASTM F436M Standard Specification for Hardened Steel Washer inch and Metric
Dimensions
ASTM A563 Standard Specification for Carbon and Alloy Steel Nuts
Algerian Legislation.
Algerian Regulatory Authorities Regulations.
International codes and standards.
COMPANY Philosophy documents.
Project Specifications.
2.6 UNITS
Elevations : Metre (m).
Dimensions : Millimetre (mm).
Force : Kilo Newton (kN).
Mass : Kilogramme (kg).
Moment : Kilo Newton metre (kNm).
Page 8 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
3 DEFINITIONS
The terms and definitions as used within this document are listed below.
4 DESIGN
The CONTRACTOR shall provide as a minimum the following design documents
approved by COMPANY and C.T.C. to fabrication sub-contractor:
Project specifications
Page 9 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
5 MATERIALS
5.1.1 All material shall be new stock and each structural member or column shall be cut
from a rolled or cold formed structural section. No substitution of materials shall be
allowed without written approval from the COMPANY.
For grade of structural steel and steel pipes, refer doc no-A-CIV-BOD-000-30001
(Civil & Structural Design Basis).
Any structural member or column shall be spliced subject to below requirements
No member less than 4m shall contain splice
No member shall contain more than one (1) splice.
Length of spliced member shall be minimum 1.5m
All splice welds to be carried out in offsite fabrication shop under
controlled environment.
5.2.1 Each bolt assembly shall consist of one heavy semi-finished hexagon structural
bolt, one heavy semi-finished hexagon nut and one hardened washer, to be used
under the nut. The assembly shall conform to BS EN 15048 or equivalent.
Two nuts are required for structures supporting vibrating equipment and for anchor
bolts.
Hardened washers are required to provide adequate bearing area. Where the
surfaces of bolted parts, which are in contact with the bolt head or nut, have a
slope of more than 1:20 with respect to a plane normal to the bolt axis (e.g.
channels and/or I- beams), a smooth tapered washer shall be used to compensate
for the slope.
The bolt shall be long enough that a minimum of three (3) threads shall be protrude
through the nut.
Page 10 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
5.2.2 Threads of bolts and nuts shall be metric, as per BS ISO 68-1 and BS ISO 261 or
equivalent.
5.2.3 High strength bolts shall conform to EN-ISO 898-1 or equivalent, property class
8.8 or equivalent.
5.2.4 Nuts shall conform to BS ISO 4035 or equivalent, property class A & B.
5.2.6 Plain washers shall conform to ISO 7089 and 7091 or equivalent. Taper washers
shall conform to DIN 434 and DIN 435 or equivalent.
5.2.7 Bolts, nuts and washers shall be hot-dip galvanized conforming to BS ISO 1461
sherardized to BS 7371.Bolts and nuts shall be hot-dip galvanized as per BS ISO
10684. Washers shall be hot-dip galvanized as per either BS ISO 10684 or BS ISO
1461.
5.2.8 Where bolts are galvanised or sherardized, nuts of a higher property class shall be
used e.g. for grade 8.8 galvanised bolts the nuts shall be class 10.
5.2.9 The use of different grade bolts of the same diameter should be avoided.
5.2.10 Each bolt and nut assembly shall be supplied by one manufacturer and the bolt
and nut shall be identified with the manufacturers mark. The coating of the nut and
bolt assembly shall be carried out under the control of the manufacturer.
5.2.11 CONTRACTOR shall verify that bolts, nuts and washers are compatible with each
other.
5.3.1 Welding electrodes shall conform to BS EN ISO 14341, BS EN ISO 2560 and BS
EN ISO 5182. Minimum electrode tensile strength shall be 480 MPa.
5.3.2 Materials for submerged arc welding shall conform to EN ISO 14171 or equivalent.
5.3.3 Materials for gas shielded metal arc welding shall conform EN ISO 14341 or
equivalent.
5.3.4 Minimum requirements for welding material, such as yield strength, tensile
strength, etc., shall be the same as for the parent material.
5.4 CERTIFICATES
Mill certification of materials shall be provided for all structural steel materials as
per BS EN 10204 type 3.1 as per Table A.1 annex A, and based on the material
type, the use and requirements.
Page 11 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
6 CONNECTIONS
6.1 GENERAL
6.1.1 All shop connections shall be welded, except shop connections for light platform
framing, etc. which may be bolted. Shop fillet welds shall have a minimum 4 mm
throat thickness. However, if the thickness of the parent material is less than 6 mm,
the minimum throat thickness of the fillet weld can be reduced to 3 mm.
6.1.3 Field welding shall be kept to the absolute minimum, especially when parts are
galvanised.
6.1.4 Fabrication sub-contractor shall take into account possible deviations of profile
shapes when working out the theoretical dimensions given on CONTRACTOR’s
design drawings.
6.1.5 Purlins shall be fixed to the roof beams or trusses by means of angle steels. Fixing
purlins by means of bent flats is not permitted.
6.1.6 Double angle members shall have fillers plates at a maximum spacing not more
than 50 times the minimum radius of gyration of the combined assembly.
6.1.7 Gusset plates shall not be thinner than the members to be connected and shall
have a thickness of at least 8 mm.
6.1.8 End plates for a beam shall not be thinner than the flange thickness of that beam.
6.1.9 Columns shall have full bearing at splices and at end plates. Design splices for the
full strength of the column. Weld base plate to column all round, unless otherwise
shown on drawings.
6.1.10 Connections of hand-rails, stairs, ladders, bracing (for angle only), etc., to
fireproofed beam/columns shall be outside the fireproofing.
6.1.11 For splices in structural steel other than those shown on the design drawings,
CONTRACTOR’s approval is required, in writing, prior to starting fabrication. Such
Page 12 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
splices shall be full penetration butt welds. All such splices shall be shown on
fabrication sub-contractor’s shop drawings.
6.1.12 Holes in gusset plates shall be so arranged to minimize moments in beams due to
eccentricity.
6.2.2 Bolted connections shall be made with a minimum of two bolts, except that one
bolt connection between non-stressed tie or bracing members is permissible when
specifically shown on design drawings.
6.2.3 Except otherwise noted on design drawings, hole diameter for bolts shall be as
follows:
Page 13 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
6.2.5 Slotted hole connections are to be executed in such a way, that these connections
may perform their design function, as indicated on the design drawings, and shall
be provided with washers.
6.2.6 High-strength bolts, grade 8.8, or equivalent shall be used for structural steel-to-
steel connections.
6.2.8 Practical length of bracing under tension shall be shorter than theoretical to give
some pretension after erection.
6.2.9 Burning of steelwork to form or enlarge holes shall not be not allowed.
6.3 BRACING
Suitable deductions shall be made on the theoretical computed lengths in all
diagonal bracing longer than 3 m to provide for draw in order to prevent visible
sagging.
7.1 GENERAL
7.1.1 Shop drawings shall include clear position and mark numbers. Shop drawings shall
have cross-references to the mark drawings and erection drawings. Each shop
drawing shall have a key plan, indicating mark numbers made from that drawing.
7.1.2 Shop drawings shall show position, mark and bolt, washer, nut and shim lists with
reference to the shop drawings, mark drawings, erection drawings and design
drawings. Bolt, washer, nut and shim lists have references to the marks that are to
be bolted together.
Approved templates shall be used for preparation of Fabrication drawings.
Page 14 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
7.1.3 The shop drawings shall only be started on the basis of the “ Issued for
Construction (IFC) CONTRACTOR’s design drawings and design calculations.
Page 15 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
7.1.5 The shop drawings shall follow as per approved schedule by the CONTRACTOR.
7.1.6 The fabrication sub-contractor shall provide a regular updated drawing list, during
preparation of shop drawings, with the latest revisions.
7.1.7 Units for dimensions and elevations shall be similar to the units as given on the
CONTRACTOR’s design drawings.
7.1.8 All shop drawings and documents which have to be submitted to the authorities
shall be presented in appropriate language as per Purchase order.
7.1.9 A list with a description of all used abbreviations shall be given on at least one
drawing. For the other drawings, a reference to that particular drawing is sufficient.
7.1.10 Grade of used materials shall be given on the drawing (e.g. grade of steel, grade
of bolts).
7.1.11 The applied surface preparation, with reference to the applicable specification,
shall be given on the drawing.
7.1.12 Revisions on drawing shall be clouded with an indication of the revision number in
a triangle or as per Project guidelines. After a new issue previous clouds and
revision number shall be removed.
7.1.13 The sub-contractor shall provide a bolt list for steel-to-steel connections.
7.1.14 When CONTRACTOR require bolts for fixing equipment on steel, fabrication sub-
contractor shall provide a bolt list for these bolts as well.
7.2.1 A marking plan shall show the locations, elevations, marks and profile sizes of all
members, handrail, ladders, stairways, etc.
7.2.2 A marking system shall follow the AISC standard or a similar system as approved
by CONTRACTOR.
7.2.5 Preferably relevant shop drawing numbers shall be incorporated in the marking
numbering system.
Page 16 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
7.3.2 Top of steel elevations of all members shall be given on the shop drawing, as
specified on the applicable design drawings.
7.3.3 Reference dimensions on the applicable design drawings shall be given on the
shop drawing. Therefore, all dimensions and elevations as given on the design
drawings shall be duplicated on the shop drawings.
7.3.4 For floor panels the span direction and location of splices for holes shall be given
on the shop drawings.
7.3.5 Deviations from the design drawings shall only be permitted after written approval
from CONTRACTOR.
7.3.6 Scheme lines for connections shall be given on the shop drawing in accordance
with design drawings.
7.3.7 The sizes of all used shapes shall be given on the shop drawing.
7.3.8 Reference shall be made to the relevant marking plan drawing (s).
8 FABRICATION
8.1 GENERAL
8.1.3 The size of members indicated on design drawings shall be strictly followed.
However, where the fabrication sub-contractor has difficulty in obtaining the
Page 17 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
8.1.4 All welding shall be in accordance with the requirements of code BS EN-ISO 3834
1, 2, 3 & 4 and BS EN-1011 1, 2, 3 & 4/ AWS D1.1 or equivalent international
standard. Welding shall only be carried out by suitably qualified welders.
8.2 WORKMANSHIP
8.2.1 The workmanship and finish shall be equal to the best in modern shop practice
and shall be in accordance with regulatory requirements.
8.2.2 Only new material shall be used, which shall be straightened in the shop by
methods that will not cause damage before it is laid off or worked in any way.
8.2.3 All cutting and shearing shall be neatly done and all surfaces/edges exposed to
view shall have a neat and workmanlike finish. Sharp edges shall be removed and
rounded off with a minimum radius of 1 2 mm.
8.2.4 Structural steel elements shall be constructed plumb and level and shall be aligned
within the tolerances in accordance with AISC.
8.2.5 Horizontal beams placed in such a way that they form rain pockets shall be
provided with drain holes of 30 mm diameter, centre to centre 1000 mm, with a
minimum of two holes.
8.2.7 Stairways, ladders and hand-rails shall be in accordance with the standard
drawings. Ladders, stairs and platforms shall be assembled in the shop to the
Page 18 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
8.3 WELDING
8.3.1 The CONTRACTOR shall carry out welding operations in accordance with the
requirements of BS EN 1090-2 or AWS D1.1. Verification of all welding shall be as
per clause no-8.1.4 of this document.
8.3.2 Fabrication sub-contractor shall, within one week after notification of award of
contract, provide welding procedures for comment and/or review. Review of
welding procedures by CONTRACTOR and COMPANY is required before the start
of welding.
8.3.3 The welding procedure shall be qualified using the same material, process and
type of equipment to be used for production. The welder shall be tested to meet
the requirement of BS EN 287 or equivalent. If the welder performing the
production welding is not the same welder used in qualification of the procedure,
he shall be qualified separately.
8.3.5 Electroslag welding and electrogas welding procedures shall not be used for
structural steelwork.
8.3.6 Welding shall be of good quality and shall comply with the requirements of
applicable codes. All welders employed shall be tested for the required procedure
in accordance with the applicable regulations. Test samples of all tests shall be
available for inspection.
8.3.7 All welding shall be an arc process in accordance with BS EN 1011-1 or equivalent.
All welding procedures submitted shall be qualified by tests in accordance with BS
EN ISO 15609 or equivalent and shall comply with the guidance of BS EN 1011-2
or equivalent.
8.3.9 Welding starts and stops on all passes shall be held to a minimum. When starts
and stops are unavoidable, each position shall be properly conditioned before
proceeding with the adjacent welding. The use of starting and stopping plates is
recommended.
8.3.10 All fillet welds shall be minimum 4 mm. However, if the thickness of the parent
material is less than 6mm, the minimum throat thickness of the parent material
Page 19 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
8.3.11 All welds shall be visually inspected after completion. Welds shall be free of cracks,
excessive porosity and slag inclusion and undercutting. The weld acceptance
criteria shall be as per the appropriate international code/standard.
8.4.1 All structural steel materials and fabrication shall be subject to inspection by
CONTRACTOR. All inspections shall be carried out by suitably qualified personnel
and shall be documented and recorded.
8.4.2 All connections shall be visually checked when they have been tightened after the
structure has been aligned locally.
8.4.3 A minimum 10% check of bolt fastenings in each connection shall be carried out
by the CONTRACTOR. Any connection that is found to contain loose bolts shall
be subject to a full inspection.
8.4.4 After checking and acceptance of a connection, the erection drawing shall be
marked to indicate acceptance.
8.4.5 CONTRACTOR’s inspector shall have free access to the materials and to all parts
of the steel structure which is being fabricated. Material which is found to be
defective or contrary to this specification and requirements of the purchase shall
be rejected.
8.4.6 Where pre-erection is specified, the members of the structure or parts thereof shall
be laid out on the shop floor for inspection.
Page 20 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
8.4.8 In order to verify that welding procedures are producing conforming welds, routine
testing shall be carried out as required by EN 1090 part 2 or equivalent.
8.4.10 All critical butt welds shall have a full visual inspection and shall also be inspected
by either radiographic or ultrasonic methods as follows:
Radiographic:
Make one spot radiograph per 500 mm of butt weld. Take the radiographs
on the flange sections of the beam with a minimum of one radiograph per
welded connection, in accordance with relevant regulatory requirements.
Ultrasonic:
Entire length of butt weld, including the webs, shall be tested. The ultrasonic
examination shall be done in accordance with regulatory requirements.
8.4.11 All full penetration corner and T-joint welds, used in beam column connections
shall have full visual inspection and shall also be inspected by ultrasonic methods
in accordance with the thickness schedule below:
Thickness of thinnest section being Percent of weld length to be tested
welded
Less than 25 mm None
25 mm to 50 mm 5
Over 50 mm 20
8.4.12 All fillet welds size 25 mm (leg length) or over in size shall be inspected by
magnetic particle testing or liquid penetrant inspection for 10% of their length.
8.5.1 Where self-tapping or self-drilling screws are used, sample holes shall be
measured periodically by spot checks to ensure that they are in accordance with
the manufacturer’s recommendations.
8.5.2 Sample screws shall be checked periodically to verify thread integrity after
installation. Screws which exhibit a deformation of thread exceeding the limits
Page 21 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
8.5.3 For blind rivets sample holes shall be measured periodically by spot checks to
ensure that they are in accordance with manufacturer’s recommendations.
8.5.4 Holes with burred edges which could adversely affect the drawing together of the
connected parts shall be rectified before the rivet connection is made.
8.5.5 Cartridge fired pins shall not be permitted without written approval from
COMPANY. Where approval has been given inspection shall be carried out to
ensure that no pins have been under-driven or over-driven and that the
manufacturer’s mark on the pin is still recognisable after the pins have been driven.
8.6.1 All structural steel except grating, stair treads and raised pattern plate and steel to
which fireproofing treatment shall be applied, shall receive a complete painting
system or shall be galvanised.
8.6.2 Surface treatment, painting system and galvanisation shall be in accordance with
project specification be treated in accordance with the project specification A-MTL-
SPE-000-30003 “Specification for Surface preparation and painting”.
8.6.3 Bolts, nuts and washersBolts and nuts shall be hot-dip galvanized as per BS ISO
10684. Washers shall be hot-dip galvanized as per either BS ISO 10684 or BS ISO
1461, grating, stair treads and raised pattern floor plate shall be hot-dip galvanized
in accordance with BS ISO 1460 and BS ISO 1461 or ASTM 123/123M. The
average weight of the zinc layer shall be 610 g/m2 of galvanized surface for
sections not less than 6 mm thick, equivalent to an average coating thickness of
85 µm.
8.6.4 If a galvanized coating is damaged, repair shall be done in accordance with the
project specification A-MTL-SPE-000-30003 “Specification for Surface preparation
and painting”.
8.6.5 Before painting or galvanising all structural steel items shall receive surface
preparation (blasting and cleaning) accordance with the project specification A-
MTL-SPE-000-30003 “Specification for Surface preparation and painting”.
8.6.6 Grating, stair treads and raised pattern floor plate shall be hot-dip galvanised.
8.7 MARKING
8.7.1 All structural steel members, grating, hand-rails, stairways, stringers, stair treads,
etc., shall be marked with identification marks and such other marks as may be
Page 22 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
8.7.2 Erection marks shall be clearly painted with a white weather-resistant paint on all
structural members and loose parts (except grating) in symbols at least 50 mm
high. In addition, they shall be stamped on all structural members, in symbols at
least 12 mm high and 1 mm deep.
8.7.3 Painted marking shall not be applied until the final paint coat is thoroughly dry or
after galvanizing.
8.7.4 Marks will have references to the relevant mark and erection drawings and to the
relevant bolt-nut-washer shim lists.
8.7.5 Marking will be done on the same locations as the marks shown in the mark and
erection drawing(s).
8.7.6 All members to be marked “TOP” where the possibility exists of erecting the
member in an inverted position.
8.7.7 All columns to have the mark painted on the outside face of the flange and to be
marked “North” or” East”. For spliced columns, column marks shall carry a level
suffix.
8.7.8 Gratings shall be tagged with a metal plate having raised letters so that the mark
shall be visible after galvanizing. This metal plate shall be seal welded to the
grating prior to galvanizing. Fabrication sub-contractor may submit alternate
proposal for marking galvanized members, subject to CONTRACTOR’s written
approval.
8.7.9 Hard stamps, punched or drilled marks shall only be permitted with
CONTRACTOR’s approval and in no case shall it be permitted on steels above
grade S355 or on cold formed components or on coated members.
9.1 GENERAL
9.1.1 Packing and shipping will be carried out in such a way that during transportation,
lifting and storage outside, no damage or loss of parts can occur. Particular
Page 23 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
9.1.2 Packed items will have clear identification references concerning contents and
weights.
9.1.3 Bolts for field connections shall be shipped to the jobsite together with the steel
members they are intended to be used with.
9.1.5 Prior to shipment, the fabrication sub-contractor shall transmit the shop drawings
in order to be able to identify steelwork members as they are delivered.
9.1.6 If any confusion is likely to arise in reception, sorting or distribution of the goods,
all parts shall have painted on them a further distinctive mark in addition to any
erection or transportation marks. Such additional marking shall consist of a
coloured band or other mark.
9.1.7 All identification marks shall be applied on at least two sides of each package.
9.1.8 All packing and transportation shall be in accordance with the approved packing
and marking procedure.
9.2.1 Upon receipt and concurrent with unloading, the structural steel shall be inspected
insofar as possible for conformance to bills of loading and determination of damage
in transport.
9.2.4 Columns and beams shall be laid out to facilitate identification and erection.
9.2.5 Smaller components, such as bracing, ladders, cantilevers, platforms, etc., shall
be segregated and stored clear of the main structural members.
10 ERECTION
The method statement shall describe the procedures to be used to safely erect
the steelwork and shall take into account technical requirements, available
access to the jobsite location and the need to coordinate the erection work with
other sub-contractors working in the vicinity.
10.2.2 The location and orientation of already installed anchor bolts shall be checked
against the base plates of the main columns before such columns are lifted for
installation.
10.2.3 If they do not match, CONTRACTOR’s approval is required before the proposed
correction is executed.
10.2.4 Before setting of base plates, concrete surfaces shall be roughened and cleaned.
Shims to be installed for levelling the supported members. Tighten the anchor bolts
after supported members have been positioned, plumbed, levelled and aligned.
Shims shall be located at least 10 mm inward from the base plate edge to secure
grouting cover and prevent rust bleeding.
10.3.1 Field welding and flame cutting is only allowed after approval by COMPANY. Sub-
contractor shall take all necessary precautions for protection of other materials and
equipment.
10.3.2 Field welding shall be kept to the absolute minimum, especially when parts are
galvanized.
10.3.3 Welding of structural steel shall be done only with qualified welders and approved
welding procedure.
Page 25 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
After welding, the specimens shall be held at a temperature not less than 10oC
for a period not less than 72 hours and shall then be sectioned and examined
for cracks and other defects.
10.3.5 In welded structures, the welding foreman or inspector shall mark all connections,
to show welding details ahead of welding crews.
10.3.6 Field welding of structural and miscellaneous steel shall be performed at the
locations indicated on the drawings.
10.3.7 Welding shall be carried out only under the direction of an experienced and
competent supervisor. A record shall be kept to enable butt welds to be identified
with the welders responsible for the work. All welds shall be marked with the
responsible welder.
10.3.8 Butt welds, which are shown on drawings to have complete penetration, shall be
produced with the aid of backing material or shall have the root of the initial layer
Page 26 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
gouged out on the back before welding is started from that side and shall be so
welded as to secure sound metal and complete fusion.
10.3.9 Weld lengths called for on the shop drawings are the net effective lengths,
excluding the un-fused start and the crater.
10.3.10 Welding shall be carried out sheltered from rain or wind. Welding shall be
stopped when the temperature inside the welding station is 0oC or below.
10.3.11 Slag shall be removed and the weld shall be wire-brush cleaned.
10.4 ASSEMBLY
10.4.1 The erection of the steelwork shall be carried out in accordance with the erection
method statement provided by the CONTRACTOR.
10.4.2 Stability of the steelwork shall be ensured at all times. Foundation bolts shall not
be used to secure un-guyed columns against overturning unless they have been
checked, by calculation, for this mode of use.
10.4.3 All temporary bracing and restraints shall be left in position until erection is
sufficiently advanced to allow its safe removal.
10.4.4 All temporary anchoring devices shall be made secure against unintentional
release.
10.4.5 Each part of the structure shall be aligned and levelled as soon as practicable after
it has been erected and final assembly shall be completed as soon as possible
thereafter.
10.4.6 Permanent connections shall not be made between components until a sufficient
portion of the structure has been aligned, levelled, plumbed and temporarily
Page 27 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
10.4.7 Before setting of baseplates, concrete surfaces shall be roughened and cleaned.
Shims shall be made of flat steel unless specified otherwise.
10.4.9 In case of misalignment of bolt holes the method of correction shall be subject to
approval by the COMPANY. Correction of misalignment by reaming or using a
hollow milling cutter is preferred; burning of holes shall not be permitted.
10.4.10 All steelwork shall be plumb and level. Thoroughly fasten brace and guy
structures permanently bolting, so as to keep the structural members plumb and
true during erection.
10.4.11 During erection, temporary bracing and guys shall be used to maintain structural
integrity.
10.4.12 At-least one daily contact should be made with local weather bureau, so as to
be forewarned for possible high winds.
10.4.13 Sufficient temporary wind bracing should be used overnight and during
weekends and holidays to prevent collapse by wind.
Page 28 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
10.4.15 Access is forbidden for personnel not engaged in the erection of steelwork, until
the structure is finally bolted up and hand-rails and stair treads are installed.
10.4.16 Erection cranes shall be so positioned that booming up or down and “walking”
are kept to a minimum.
10.4.17 Auxiliary cranes, cherry pickers, trailers, etc., shall be used as required to feed
columns, beams, reassembled units, etc., for the erection crane.
10.4.18 The sequence of erection shall be as described in the erection method statement
with the general principle that members furthest from the crane are installed first,
or as dictated by safety requirements.
10.4.19 Normal procedure should be to plumb main columns and beams between
splices, before starting to dress the elevations of the structure with the secondary
members.
10.4.20 Temporary planking and installation of temporary protective railing for erection
purposes shall be executed by erection sub-contractor and in accordance with
safety regulations.
10.4.22 The use of platforms and walkways as storage areas for material shall be
carefully controlled from the standpoint of safety, accessibility and allowable
design loads.
10.4.23 As soon as possible after plumbing the structure, erection with permanent bolts
and all connections shall be completed.
10.4.25 Fit-up clips shall be removed carefully to avoid tearing structural members and
all weld marks shall be ground smooth after which the coating in the area shall be
repaired.
Page 29 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
10.5.1 Anchor bolts shall be firmly tightened as soon as columns are set and grouted.
They shall be fully tightened after the first level has been plumbed.
10.6.1 Erection tolerances shall be in accordance with the limits stated in Appendix D of
EN 1090: Execution of steel structures and aluminium structures. Part 2: Technical
requirements for structures or AISC guidelines.
10.6.2 Correction of fabrication deviations, which involve flame cutting, heating, additional
holes, relocation of clips, etc., shall not be undertaken without approval of
CONTRACTOR.
10.6.4 Where flame cutting is done it shall be mandatory to finish all surfaces smooth and
rounded with no corners or points of sharp curvature remaining as a possible
source of stress concentration.
10.7 SAFETY
10.7.1 Safety for erection of structural steelwork shall be in accordance with COMPANY
and regulatory requirements.
10.7.2 Scaffolding used for erection of structural steel shall be installed and inspected in
accordance with project and regulatory requirements by qualified personnel.
10.8.1 Galvanized surfaces shall not be painted. For repair to damaged areas refer to
project specification A-MTL-SPE-000-30003 “Specification for Surface preparation
and painting”.
10.8.2 Steel surfaces on which the shop coatings have been damaged shall be thoroughly
cleaned and shall be touched up with primer and painted, all in accordance with
project specification A-MTL-SPE-000-30003 “Specification for Surface preparation
and painting”.
11 FIELD INSPECTION
The CONTRACTOR reserves the right to inspect the erection of the structural steel
at any time to assure that the materials and workmanship are in accordance with
this specification and contract.
Page 30 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
12 QUALITY CONTROL
12.1.1 The purpose of this section is to assure that the fabrication and erection and
delivery of the structural steel is in agreement with the COMPANY requirements,
this specification and fabrication sub-contractor’s shop fabrication drawings and
that quality control procedures for structural material handling, storage and
erection are carried and documented out as prescribed herein.
12.1.2 CONTRACTOR shall submit his quality plan for fabrication and erection of
structural steel in accordance with ISO 9000, to COMPANY, before commencing
the steelwork. It shall include but not be limited to:
An organisation chart
The allocation of tasks and responsibilities during the various phase of
the works
The procedures and methods to be applied including welding procedures
The procedure for providing certificates for constituent products and
consumables
The procedure for dealing with changes and modifications
The procedure for dealing with non-conformities
An inspection plan specific to the works
Pro forma copies of execution records that will be used to document
inspection and compliance with specifications for the elements of the
works
12.2 MATERIAL
12.2.1 All structural steel items shall be accompanied by certificates in accordance with
this specification.
12.2.2 Bolts, nuts and washers shall be accompanied by documents as require by this
specification.
12.3.1 Drawings, shop fabrication, inspection reports, including the material certificates
and documents, shall be at site and checked against this specification and shop
fabrication drawings.
Page 31 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
12.3.3 CONTRACTOR’s inspector shall assure that care is taken to prevent the steel
members from being damaged or soiled during storage and handling.
12.3.4 No welding of structural steel may be done without qualified welders and approved
welding procedure.
12.4 ERECTION
The method used for erection of structural steel depends upon:
The type and size of structure.
The risks involved.
Whether the structure is to be erected without interference with other
work or operations.
Availability of lifting devices.
Local conditions.
12.4.1 All tools, equipment and ropes used for erection shall be currently certified for the
purpose intended.
12.4.2 The CONTRACTOR shall submit to the COMPANY an erection plan, complete
with data on heavy lifts and shipping weights.
12.4.3 Approval of this erection plan by the COMPANY does not relieve the erection
Contractor from his full responsibility for the erection of the structure in a safe and
orderly manner.
12.4.4 CONTRACTOR shall submit an erection plan procedure for bolting and welding
procedures before commencing erection. Welders shall be qualified as per
applicable standard and shall be approved and accepted by COMPANY
12.4.5 Verticality, level and alignment shall be checked. Corrections and/or alterations
required as result of poor fit shall be reported and approved by the
Page 32 of 33
Specification for Structural Steel Fabrication and Erection
Document No : A-CIV-SPE-000-30007
Revision 0
12.4.6 All bolt connections shall be checked by erection sub-contractor to be sure that all
temporary erection bolts, etc., are removed and replaced by construction bolts.
12.4.7 After checking of connection, the erection drawing shall be marked to indicate
acceptance.
12.4.9 Loose bolts will be brought to the attention of the CONTRACTOR and re-inspected
for compliance.
12.4.10 Checking of bolted connections shall be done with a calibrated impact wrench.
12.5.1 Before the steel structure will be accepted for final inspection, the following
requirements shall be verified:
All temporary provisions and temporary materials not required for access
for inspection have been removed.
Quality records are available and have been approved and signed off by
all parties.
Page 33 of 33