Configure/Setup of 04/27/2017 15:44:21.347 [8800D Rev.

2]
(Current) 4/28/2017 1:54:22 PM

Basic Setup:
Transmitter Mode Without Temp Snsr
Process Fluid Gas/Steam
Fixed Process Temp 26.0 degC
Fixed Process Density 0.320000 kg/Cum
Reference K Factor 4.6567
Flange Type PN100
Pipe I.D. 4.026 in
LSL 0.000 Cum/h
USL 2703.607 Cum/h
Tag 20-FT-01
PV is Volume Flow
SV is Vortx Freq
TV is Pulse Freq
4V is Vel. Flow
Unit Cum/h
LRV 0.000 Cum/h
URV 843.000 Cum/h
Min Span 45.0601 Cum/h
Flow Damping 2.0 s
Proc Temp Damping 2.0 s

Units:
Volume Flow Units Cum/h
Velocity Flow Units m/s
Velocity Meas Base Mating Pipe
Mass Flow Units kg/h
Base Volume Unit Cum
Conversion Number 42.000000
User Defined Unit BBL
User Flow Unit BBLS
Base Time Unit s
Proc Temp Units degC
Elec Temp Units degC
Proc Dens Units kg/Cum

4/28/2017 1:54:46 PM Page 1 of 4


Configure/Setup of 04/27/2017 15:44:21.347 [8800D Rev. 2]
(Current) 4/28/2017 1:54:22 PM

Std/Nml Units:
Fixed Process Temp 26.0 degC
Proc Press (abs) 42 bar
Proc Compress. 1
Base Temp 15 degC
Base Press (abs) 101.32 kPa
Base Compress. 1
Density Ratio 39.9286

Sensor:
Pipe I.D. 4.026 in
Process Fluid Gas/Steam
Reference K Factor 4.6567
Compensated K Factor 4.6565
Install. Effect 0.00 %
T/C Failure Mode Go To Alarm
USL 2703.607 Cum/h
LSL 0.000 Cum/h
Fixed Process Temp 26.0 degC
Wetted Material 316 SST
Meter Body # 258425
Flange Type PN100
Meter Body S/N 258425
Body # suffix B
Fixed Process Density 0.320000 kg/Cum

Outputs:
Hi Sat. 20.80 mA
Lo Sat. 3.90 mA
Total 8467310.0000 Cum
Totalizer Control Start
Totalizer Config Volume Flow
Alrm Level Select Rsmt Standard
Hi Alarm 21.75 mA
Lo Alarm 3.75 mA
Puls Out 0.000000 Hz

4/28/2017 1:54:46 PM Page 2 of 4


Configure/Setup of 04/27/2017 15:44:21.347 [8800D Rev. 2]
(Current) 4/28/2017 1:54:22 PM

Unit Cum/h
PV is Volume Flow
LRV 0.000 Cum/h
URV 843.000 Cum/h
USL 2703.607 Cum/h
LSL 0.000 Cum/h
Min Span 45.0601 Cum/h
Pulse Output Mode Off
Pulse Scaling 0.0000000 None

Filtering:
Flow 464.810 Cum/h
Shed Frq 158.511 Hz
Shed Freq at URV 288.051 Hz
Sig/Tr: 499.384
LFC(in Eng Unit) 97.7794647 Cum/h
LFC Setting 33.4 Hz
LFC Response Step
Lowpass Corner Frequency 77.310997 Hz
Lowpass Filter 77 Hz
Trigger Level 4
Min LFC 384.087 Cum/h

Device:
Model 8800D
Manufacturer Rosemount
Hardware rev 1
Software rev 5
Write protect No
Final Assembly # 258425
Date 11/6/2013 12:00:00 AM
Descriptor GAZE_SOT_TOTAL
Message

Display:
Local Display : PV ACTIVE

4/28/2017 1:54:46 PM Page 3 of 4


Configure/Setup of 04/27/2017 15:44:21.347 [8800D Rev. 2]
(Current) 4/28/2017 1:54:22 PM

Local Display : Percent of Range ACTIVE


Local Display : Loop Current ACTIVE
Local Display : Total ACTIVE
Local Display : Shedding Freq Inactive
Local Display : Mass Flow Inactive
Local Display : Velocity Flow ACTIVE
Local Display : Volume Flow ACTIVE
Local Display : Pulse Freq Inactive
Local Display : Electronics Temp Inactive
Local Display : Process Temp Inactive
Local Display : Process Density Inactive

HART:
Tag 20-FT-01
Poll Address 0
Device ID 178085
Burst mode Off
Burst option PV
Universal rev 5
Transmitter Rev 2
# of Req Preams 5
Num resp preams 5
Physicl signl code Bell 202 current
Xmtr Var, Slot 1 Volume Flow
Xmtr Var, Slot 2 Vortx Freq
Xmtr Var, Slot 3 Pulse Freq
Xmtr Var, Slot 4 Total

4/28/2017 1:54:46 PM Page 4 of 4