Professional Documents
Culture Documents
747−400
(PW 4000)
Issue: APR2006
Easa Part 66
B1
B747−4 PW 36 B1 E
For training purposes only.
Copyright by Lufthansa Technical Training.
LTT is the owner of all rights to training documents and training
software.
Any use outside the training measures, especially reproduction
and/or copying of training documents and software − also extracts
thereof −in any format all (photocopying, using electronic systems
or with the aid of other methods) is prohibited.
Passing on training material and training software to third parties
for the purpose of reproduction and/or copying is prohibited without
the express written consent of LTT.
Copyright endorsements, trademarks or brands may not be re-
moved.
A tape or video recording of training courses or similar services is
only permissible with the written consent of LTT.
In other respects, legal requirements, especially under copyright
and criminal law, apply.
ATA 36 PNEUMATIC
For Training Purposes Only
36-00 GENERAL
The pneumatic system controls the flow, pressure, and temperature of the The engine bleed control system includes the following components:
bleed air on ground or in flight. Air Supply Control and Test Unit (ASCTU) 36−11−30
Pneumatic is delivered from the following subsystems: High Pressure Shutoff Valve (HPSOV) 36−11−05
Each engine supplies compressed air to the pneumatic system. High Pressure Controller (HPSOVC) 36−11−06
There are two sources of bleed air available from the engine, intermediate
Intermediate Pressure Check Valve, 36−11−02
pressure (8th−stage) and high pressure (15th−stage).
Pressure Regulating Valve (PRV) 36−11−19
The pneumatic system can also be pressurized with the APU. The APU is
also used as a secondary pressure source in flight up to an airplane altitude Pressure Controller (PRVC) 36−11−20
of 15 000ft. Engine Bleed Air Precooler 36−12−01
When the airplane is on the ground, a pneumatic ground cart can supply air Fan Air Temperature Sensor (FATS 36−12−02
for the pneumatically operated systems. The ground cart supplies com- Fan Air Modulating Valve (FAMV) 36−12−04.
pressed air through two 3−inch diameter connectors on the aft side of the
Pressure Regulating and Shutoff Valve (PRSOV) 36−11−04
left air−conditioning bay door.
CAUTION: DO NOT FAIL TO ENERGIZE THE ELECTRICAL NETWORK The following valves in the pneumatic system are :
BEFORE YOU PRESSURIZE THE AIRPLANE PNEUMATIC
springloaded closed :
SYSTEM. DAMAGE OF THE ENVIRONMENTAL CONTROL
SYSTEM (ECS) CAN RESULT. − High Pressure Shutoff Valve (HPSOV)
The system supplies air for the following pneumatically operated airplane − Pressure Regulating Valve (PRV)
systems: − Pressure Regulating Shutoff Valve (PRSOV)
ATA 21 Airplane pressurization and environmental control system (ECS)
ATA 21 cargo heating springloaded open :
ATA 26 smoke detection − Fan Air Modulating Valve (FAMV)
ATA 27 wing leading edge flap drives
electrically controlled :
ATA 29 hydraulic reservoir pressurization
− High Pressure Shutoff Valve Controller (HPSOVC)
For Training Purposes Only
APU
WATER SYSTEM
PRESSURIZATION
WING ISOLATION
VALVES
APU
(2 LOCATIONS) PNEUMATIC
DUCT
AIR CONDITIONING
AFT CARGO HEAT
PACKS
(3 LOCATIONS)
WING
PNEUMATIC
MANIFOLD
For Training Purposes Only
LEADING EDGE
CONTROL
AND PNEUMATIC
INDICATION HYDRAULIC
DRIVE UNIT WING
RESERVOIR
ANTI−ICING
PRESSURIZATION
AIR DRIVEN
HYDRAULIC
PUMPS
Figure 1 Pneumatic Manifold System
FRA US/T ReF 12.12.05 Page 3
Lufthansa Technical Training
PNEUMATIC B 747 − 400
GENERAL PW 4000
36 − 00
The ASCTU monitors the position of the components and the pressure and
the temperature of the system.
This information is processed and sent to EICAS.
If the ASCTU determines that there is a system failure, the BIT part of the
ASCTU will send the component fault to the CMC.
The indication part of the ASCTU will send a signal to the SYS FAULT light
on the bleed control module and to EICAS.
E/E RACK
E−2
P6 − 4 FWD
31 32 33 34 35 36 E/E RACK
LOCATION OF E−1
AIR SUPPLY CONTROL
TEST UNIT ( M 7957 )
(E2−4)
21/2 21/2 21/2 21/2 21/2 21/2
H OLD VERSION
E/E RACK
E−2 MAIN EQUIPMENT CENTER
FWD
E/E RACK
E−1
For Training Purposes Only
LOCATION OF
AIR SUPPLY CONTROL
TEST UNIT ( M 7957 )
(E2−4)
NEW VERSION
AIR SUPPLY CONTROL TEST UNIT
(ASCTU) MAIN EQUIPMENT CENTER
36−10 DISTRIBUTION The proper function of the PRV Controller and the PRV are
continuously monitored by the CMC. In case of malfunction
the SYSTEM FAULT light comes on
BASIC SCHEMATIC DESCRIPTION
the associated CMC and/or EICAS messages are displayed.
The Engine Bleed Air Switch permit operation of the individual bleed air
systems. In ON, the Air Supply Control Test Unit (ASCTU) commands: FAN AIR MODULATING VALVE (FAMV)
the High Pressure Shutoff Valve Controller (HPSOVC) The fan air modulating valve (FAMV) is opened and closed by the signal
the Pressure Regulator Valve Controller (PRVC) pressure from the fan air temperature sensor (FATS) and by bleed air pres-
the Pressure Regulating and Shutoff Valve (PRSOV) sure from the precooler. When the temperature of the bleed air sensed by the
FATS is below 160C/320F, the FAMV is closed. When the temperature is
to OPEN.
above 193C/380F, the FAMV is fully open.
HIGH PRESSURE SHUT OFF VALVE (HPSOV) If the sensed temperature is between 160C/320F and 193C/380F, the fan
air modulating valve will regulate.
The HPSOV Controller controls the HPSOV.
When open, the valve limits the downstream pressure to 1055 psi when BLEED AIR PRESSURE- AND TEMPERATURE SENSOR
the flight altitude is at or below 27.000 ft.
The bleed air pressure sensor and the bleed air temperature sensor provide
Above 27.000 ft, the switchover pressure changes linearly from 105 psig indication on the ECS SUPPLY Maintenance page.
at 27.000 ft to 77 psig at 42.000 ft.
When the flight altitude is above 42.000 ft, the HPSOV Controller closes the BLEED AIR OVERPRESSURE SWITCH (OPS)
valve at 77 psi. When the bleed air pressure goes above 76 psig, the overpressure switch
The proper function of the HPSOV Controller and the HPSOV are opens and senses an input to the ASCTU logic circuits. A SYS FAULT light will
continuously monitored by the CMC. In case of malfunction come on and a BLEED 1, 2, 3 or 4 EICAS advisory message will come into
the SYSTEM FAULT light comes on view on EICAS along with its associated BLEED OVPRESS 1, 2, 3 or 4 EICAS
the associated CMC and/or EICAS messages are displayed. status message, when the ECS status page is selected.
The intermediate pressure check valve (IP-Check Valve) is an in−line check BLEED AIR OVERHEAT SWITCH (OHS)
valve that prevents high stage reverse flow into the intermediate stage.
The overtemperature switch senses the temperature of the air in the bleed duct
PRESSURE REGULATING VALVE (PRV) downstream of the precooler. When the temperature goes above 243C/470F,
For Training Purposes Only
the ASCTU will close the HPSOV and PRV. When this occurs, the circuit that
The PRV Controller controls the PRV. controls the HPSOV and PRV latches the valves closed. The valves will not
The PRV downstream pressure is regulated to maintain precooler inlet automatically open when the temperature decreases below 243C/470F. To
pressure at 64psi. If there is an overpressure condition in the precooler inlet, release the latched closed condition, operate the ENGINE BLEED switch from
the controller will cause the PRV to close. ON to OFF and then back to ON again. Fault Monitoring is similar to the OPS.
For Nacelle Anti−Ice (NAI) pneumatic pressure is always available, indepen-
dently of the Engine Bleed Air Switch position ON oder OFF. If the pneumatic
system has an overtemperature condition, no bleed air can be delivered to NAI.
R
E
F
E
R
T
O
D
I
N
A
3
For Training Purposes Only
P
A
G
E
PRESSURE REGULATING AND SHUT OFF VALVE (PRSOV) in case of malfunction, the associated CMC and/or EICAS messages
are displayed.
The Pressure Regulating and Shut Off Valve (PRSOV) is the cut between
Engine- and Aircraft Pneumatic System and has the following 5 functions: the VALVE light in the upper portion of the Isolation Valve switch comes on
when the valve is IN TRANSIT.
SHUTOFF VALVE FUNCTION
the valve can be opened and closed by the Engine Bleed Air Switch (EBA) APU ISOLATION VALVE
or closed by the Engine Fire Switch when it is open.
When the APU switch is put in the ON position, the valve will open and permit
CHECK VALVE FUNCTION APU bleed air to pressurize the pneumatic system.
If the downstream pressure (aircraft pneumatic pressure) is higher than The following conditions must occur to cause the valve to open:
the upstream pressure (engine pneumatic manifold pressure) the valve will the APU switch is in the ON position
move to the close position.
the APU override relay is not energized
REVERSE FLOW OVERRIDE FUNCTION
the APU fire switch is in the NORMAL position
An electrically operated reverse flow solenoid is used during engine start.
the APU start relay is energized (ON or START position)
When the engine start switch is pulled, a signal is sent to the solenoid. The
solenoid then lets the valve use downstream air pressure to open the valve. the APU is at 95% capacity.
The EBAS must be in ON.
AIR SUPPLY CONTROL TEST UNIT (ASCTU)
TEMPERATURE CONTROL
The temperature control portion of the valve will begin to close the valve The AIR SUPPLY CONTROL TEST UNIT (ASCTU) gives control and
when the temperature gets to 220C/428F. When the temperature gets to indication data for the pneumatic system components.
232C/450F, the valve will be nearly closed. The indications are displayed on the
PRESSURE CONTROL Main EICAS Display
The pressure control portion of the valve keeps the downstream pressure ECS Synoptic Page
between 30 and 50 psi (nominal 45 psi). ECS Maintenance Page (Air Supply)
The proper function of the PRSOV is continuously monitored by the CMC. The ASCTU is installed in the main equipment center on the E2−4 rack.
in case of malfunction, the associated CMC and/or EICAS messages
are displayed. DUCT PRESSURE SENSORS
the OFF light in the lower portion of the EBAS comes on when the valve is There are two pressure transmitters (L, R) installed in the L and R wing pneu-
For Training Purposes Only
fully closed matic manifold, both transmitters are located upstream of their respective wing
isolation valves. Pressure signals from the transducers are sent to the EICAS
LEFT AND RIGHT WING ISOLATION VALVE and CMCS via the ASCTU. Pressure is displayed on the
There are two wing isolation valves installed in the pneumatic manifold aft Main EICAS Display
of the air−conditioning bay. The valves are normally in the open position. ECS Synoptic Page
The wing isolation switch directly commands the associated Isolation Valve to ECS Maintenance Page (Air Supply)
OPEN or CLOSE. Engine Performance Maintenance Page
The proper function of the Wing lsolation Valves is continuously monitored by
the CMC.
R
E
F
E
R
T
O
D
I
N
A
3
For Training Purposes Only
P
A
G
E
1 1
ECS Control Panel (P5)
ON
1 1
ON ON
OFF OFF
OFF
the CLOSED−Limit Switch installed at the Pressure Regulating and Shutoff
Valve (PRSOV) signals the fully closed position.
the ASCTU commands the following valves to open:
the PRSOV
SYSTEM FAULT−LIGHT (AMBER)
the HPSOV by using the HPSOVC There are four amber SYS FAULT lights located on the
SYS
the PRV by using the PRVC engine bleed air system control module, M7328 on the P5
FAULT
but only if overhead panel that will come on in the event of
the Engine Fire Handle is in NORMAL,
For Training Purposes Only
BLEED
CONTROL
MODULE
P5 PANEL
1 PACKS 2 PACKS 3
P6 PANEL
NORM NORM NORM
OFF A OFF A OFF A
FLIGHT COMPARTMENT B B B
L ISLN R ISLN
VALVE VALVE
WING WING
TAI TAI
APU
SYSTEM FAULT
LIGHT SYS SYS SYS SYS
ON
FAULT FAULT FAULT FAULT
VALVE
1 2 3 4
For Training Purposes Only
ENGINE
BLEED AIR ON ON ON ON
ENGINE
SWITCH BLEED
OFF OFF OFF OFF
APU ISOLATION
VALVE SWITCH
LEFT AND RIGHT WING ISOLATION VALVE SWITCH APU ISOLATION VALVE SWITCH
There are two wing isolation valves installed in the pneumatic manifold aft OPEN :
of the air−conditioning bay. The valves are normally in the open position. APU APU
ON ON
The switch directly commands the associated Isolation Valve to
OPEN or CLOSE. VALVE
OPEN :
L ISLN When the APU switch is put in the ON position, the valve will open and permit
APU bleed air to pressurize the pneumatic system. The following conditions
must occur to cause the valve to open:
the APU switch is in the ON position
the APU override relay is not energized
The valve is commanded to OPEN, the APU fire switch is in the OFF position
the Flow Bar in the lower half of the switchlight is visible. the APU start relay is energized (ON or START position)
the APU is at 95% capacity.
CLOSE : CLOSE :
L ISLN APU
The valve is commanded to CLOSE, When the APU switch is set to the OFF position, the valve will close. The valve
the lower half of the switchlight is blank. will be closed also if one or more of the following conditions is available:
the APU is below 95% capacity
Wing Isolation VALVE Light : the APU Fire Switch is in FIRE
L ISLN L ISLN the APU control circuitries are not powered.
For Training Purposes Only
VALVE VALVE
APU Isolation Valve ”VALVE”−Light
APU
The VALVE light monitors the position of the respective Wing Isolation Valve. The VALVE light monitors the position of the APU Isolation Valve. The light is
The light is on while the valve is in transit or when a disgree occurs. on while the valve is in transit or when a disgree occurs.
BLEED
CONTROL
MODULE
P5 PANEL
1 PACKS 2 PACKS 3
P6 PANEL
NORM NORM NORM
OFF A OFF A OFF A
FLIGHT COMPARTMENT B B B
L ISLN R ISLN
VALVE VALVE
WING WING
TAI TAI
APU
SYSTEM FAULT
LIGHT SYS SYS SYS SYS
ON
FAULT FAULT FAULT FAULT
VALVE
1 2 3 4
For Training Purposes Only
ENGINE
BLEED AIR ON ON ON ON
ENGINE
SWITCH BLEED
OFF OFF OFF OFF
APU ISOLATION
VALVE SWITCH
airflow is available
(white)
NOTE: A FLOW BAR IS VISIBLE, IF A PNEUMATIC POWER SOURCE
AND A PNEUMATIC POWERED SYSTEM IS ON AT THE SAME Bleed Isolation Valve is CLOSED
TIME.
OFF (amber)
For Training Purposes Only
PRSOV closed, Engine Bleed Air Switch in ON but the respective engine is
running (N2 > 50%).
TEMP C
F/D U/D
26 25 26 25 MASTER 26 OUTFLOW VALVES
L R
A B C D E OP
26 25 26 25 26 25 26 25 26 25
CL
FWD AFT MAN AUTO
25 26 25
HI FLOW HI FLOW
1 2 3
NAC NAC
TAI TAI BLEED FLOW
INDICATION
BLEED ISOLATION (FLOW)
VALVE (CLOSED) 1 ENG 2 3 ENG 4
The duct pressure is indicated in PSI NAI System is OFF (Valve CLOSED)
if the manifold duct pressure is above or equal to 11 psia, the indication
appears in white.
if the Ductpressure is below 11 psia, the indication appears in amber.
NAC (green Flow Bar indicated)
TAI
WING THERMAL ANTI-ICE INDICATION (WTAI) EXTERNAL AIR INDICATION (EXT AIR)
EXT AIR
WING (WTAI Symbol Blank)
TAI
EXT AIR indication appears, if
WTAI System is OFF (Valve CLOSED) − the APU Isolation Valve and all PRSOV’s are closed or
− the APU Isolation Valve is closed, one or both PRSOV on one side is
open and the respective Wing Isolation Valve is closed
and one or both pressure sensors senses a duct pressure.
This means, the airplane is on the ground, and a pneumatic ground cart
For Training Purposes Only
WING (green Flow Bar indicated) supplies air for the pneumatically operated systems.
TAI
WTAI System is ON (Valve OPEN) NOTE: IN CASE OF A FAULTY INDICATION (WRONG OR MISSING FLOW
SEGMENTS) REFER TO THE FAULT ISOLATION MANUAL (FIM) :
36−20−00
LOGIC DIAGRAMS/ECS SYNOPTIC FLOW DIAGRAMS
TEMP C
F/D U/D
26 25 26 25 MASTER 26 OUTFLOW VALVES
L R
A B C D E OP
26 25 26 25 26 25 26 25 26 25
CL
FWD AFT MAN AUTO
25 26 25
HI FLOW HI FLOW
1 2 3
EXTERNAL AIR
MESSAGE OFF PACK CONTROL A PACK CONTROL B
DUCT DUCT
PSI EXT AIR PSI DUCT
WING THERMAL 0 28 PRESSURE
ANTI−ICE
(INACTIVE) WING WING WING THERMAL
TAI TAI ANTI−ICE
(ACTIVE)
BLEED FLOW
INDICATION APU
(NO FLOW) ENGINE
OFF OFF OFF OFF BLEED
(OPEN)
For Training Purposes Only
NAC NAC
TAI TAI BLEED FLOW
INDICATION
BLEED ISOLATION (FLOW)
VALVE (CLOSED) 1 ENG 2 3 ENG 4
NACELLE THERMAL
APU ISOLATION NACELLE THERMAL
ANTI−ICE (INACTIVE)
VALVE (CLOSED) ANTI−ICE (ACTIVE)
HIGH
PRESSURE
CONTROLLER
ECS MAINTENANCE PAGE (AIR SUPPLY SYSTEM) PRESS REG S/O VLV
(Pressure Regulating and Shut Off Valve indication)
FAN AIR VLV
The indication is provided by the PRSOV open and close limit switch.
(Fan Air Modulating Valve indication) CLOSED : (is displayed with)
CLOSED : − Engine Bleed Air System unpressurized or
− is displayed if the Engine Bleed Air Temperature is below 160C/320F . − Engine Bleed Air Switch in OFF or
REGLTG (Regulating): − Engine Fire Switch pulled (FIRE) or
− is displayed if the sensed temperature is between 160C/320F and − Engine Bleed Air Overheat Condition (> 243C/>470F)
193C/380F.
REGLTG (Regulating) :
The fan air modulating valve will regulate.
− is displayed if the PRSOV downstream pressure is regulated by the
OPEN :
PRSOV to maintain pneumatic pressure at 45 psi.
− is displayed if the Engine Bleed Air System unpressurized or
OPEN : (is displayed with)
− Engine Bleed Air Temperature is above 193C/380F .
− Engine Bleed Air System pressurized
− Engine Bleed Air Switch in ON
− Engine Fire Switch NORMAL
− Engine Bleed Air Temperature <243C/<470F
or (with pneumatic pressure available) at
− Engine Start (Reverse Flow).
STARTER VLV
(Starter Valve indication) BLEED FLOW (OPTION)
The indication is provided by the Start Air Valve (SAV) close limit switch.
shows the airflow from one or two engines to the pneumatic System.
CLOSED :
displays kg/min.
− is displayed if the Starter Valve is CLOSED
OPEN :
For Training Purposes Only
1 2 3 4
HIGH PRESS CONT OPEN OPEN OPEN OPEN
MANIFOLD L R
DUCT PRESSURE MANIFOLD DUCT PRESSURE 44 45
GEAR
EGT
65 65 OIL P 12 66
F 5 105 105 OIL T 103 107 F
L L 5
A 15 15 OIL Q 19 15 A
P P
S S
86 86 FP 86 86
1.0 1.0 N2 1.0 1.0
350 350 BURN PR 350 350
1.1 1.1 BB 1.1 1.1
100 100 NAC T 100 100
28 28 FAN PH 28 28
33.8 33.8 33.8 33.8
For Training Purposes Only
TRASEL
102 102 LPT PH 102 102
0.0 0.0 T/R 0.0 0.0
12 DUCT PRESS 12
MANIFOLD
Engine Performance Maintenance Page DUCT PRESSURE
The engine start switch energizes the PRSOV reverse flow solenoid to provide
air supply to the engine starter. As soon as the Start Air Valve (SAV) signals
NOT CLOSE, the ASCTU commands the PRV to close.
For Training Purposes Only
ENGINE FIRE
MODULE
THERMAL
ANTI−ICE ENGINE START
MODULE MODULE
P 5 PANEL
OVERHEAD
NACELLE 3 ANTI−ICE
2
1 OFF 4 ENGINE FIRE MODULE
AUTO THERMAL
ANTI−ICE MODULE
ON (WITH ICE
WING ANTI−ICE DETECTION)
AUTO
OFF ON
NACELLE ANTI−ICE
2 3
1 4
For Training Purposes Only
ON ON
ON VALVE VALVE ON
VALVE VALVE
THERMAL ON
ANTI−ICE MODULE
(WITHOUT ICE VALVE
WING ANTI−ICE
DETECTION) ENGINE START MODULE
36 - 10 DISTRIBUTION
PNEUMATIC DISTRIBUTION SYSTEM
General
The primary source of air for the pneumatic system is engine bleed air from the There are two sources of bleed air available from each engine: intermediate
high pressure compressors. The engine bleed control system includes the fol- pressure (8th−stage) and high pressure (15th−stage). During low power engine
lowing components: operation, the three 15th−stage bleed ports supply compressed air. During high
Intermediate Pressure Check Valve (IP-CHECK VALVE) power engine operation, the two 8th−stage bleed ports supply compressed air.
The intermediate pressure check valve will not permit high stage air to be sup-
Pressure Regulating and Shutoff Valve (PRSOV)
plied to the intermediate bleed ports (it is a one−way valve).
High Pressure Shutoff Valve (HPSOV)
High Pressure Controller (HPSOVC)
The high pressure controller controls the position of the HPSOV. When the
Pressure Regulating Valve (PRV) valve is open, 15th−stage air is supplied to the engine pneumatic manifold.
Pressure Regulating Valve Controller (PRVC) When the valve is closed, 8th−stage (IP) air is supplied to the engine pneu-
Air Supply Control and Test Unit (ASCTU) matic manifold. The pressure controller controls the position of the PRV. The
air from the IP/HP bleed ports is regulated to 59−69psig by the PRV before it
Engine Bleed Air Precooler
enters the precooler.
Fan Air Temperature Sensor (FATS)
Fan Air Modulating Valve (FAMV)
The precooler reduces the temperature of the bleed air extracted from the en-
gines. It uses engine fan air to remove heat from the bleed air. The fan air tem-
perature sensor measures the temperature of the bleed air downstream of the
precooler and varies signal pressure to the fan air modulating valve. The fan air
modulating valve controls the amount of fan air that goes through the pre-
cooler.
The bleed air from the precooler, goes up through the strut and the PRSOV
For Training Purposes Only
before it enters the airplane pneumatic ducts. The PRSOV controls the pres-
sure in the pneumatic ducts. This valve also prevents reverse flow back to the
engine. It has an override function to permit reverse flow during engine start.
The valve can be closed during engine operation to isolate the system or if
there is an overheat condition.
PRESSURE REGULATING
AND SHUTOFF VALVE
TO COWL
TO STRUT HYDRAULIC
THERMAL ANTI−ICE
RESERVIOR
AIR SUPPLY
PRECOOLER
FAN AIR TEMPERATURE
FAN AIR
SENSOR
MODULATING
VALVE
INTERMEDIATE
TO STARTER
PRESSURE
CHECK VALVE
PRESSURE REGULATING
VALVE
HIGH PRESSURE
SHUTOFF VALVE
HIGH PRESSURE
BLEED PORTS
For Training Purposes Only
(4 PLACES)
INTERMEDIATE
PRESSURE
BLEED PORTS
(2 PLACES)
36−10 DISTRIBUTION
HIGH PRESSURE SHUTOFF VALVE CONTROLLER (HPSOVC) HPSOV CONTROLLER FAULT INDICATION
The high pressure controller is installed on the engine in the 7:00 o’clock posi- The proper function of the HPSOV Controller is continuously monitored by the
tion on the forward face of the main gearbox CMC. In case of malfunction
The high pressure controller senses high stage pressure the SYSTEM FAULT light comes on
receives command inputs from the ASCTU and the Advisory Message
sends pneumatic signals to the HPSOV. − BLEED (#) and/or
These signals will cause the HPSOV to open or close. − BLEED HP ENG (#)
The high pressure controller has the following components: appears.
a cast aluminum controller body
an altitude biased pneumatic switch The Status Message
an internal sensing diaphragm BLEED HP ENG (#)
a shutoff solenoid will be displayed also on lower EICAS.
four pressure sensing switches
THE CMC provides the associated CMC Present Leg Fault/Existing Fault
a high stage pressure sensing port with a filter element (Supply Pressure)
Message visible on the MCDU:
a signal pressure port that goes to the HPSOV (Actuator Servo Pressure)
BLEED − (#) HIGH PRESSURE CONTROLLER / HPSOV FAIL
The HPSOV Controller controls the HPSOV.
BLEED − (#) HIGH PRESSURE CONTROLLER FAIL
The valve moves when high stage servo pressure acts on the servo pressure
or in case of a BITE switch fault:
sensing diaphragm.
BLEED (#) HIGH PRESSURE CONTROLLER HIGH PRESSURE SWITCH
The downstream pressure is limited as follows:
FAIL
The valve will be commanded to close when high stage engine pressure is
105"5 psi at or below 27.000"1,000 ft.
Above 27.000 ft, the switchover pressure changes linearly from 105 psig
at 27.000 ft to 74 psig at 42.000 ft.
For Training Purposes Only
When the flight altitude is above 42.000 ft, the HPSOV Controller closes the
valve at 74 psi.
The HPSOV and the inlet filter are LRU‘s, the components of the HPSOV are NOTE: THE (#) STANDS FOR THE ENGINE POSITION.
SRU’s.
PC − BITE
HIGH PRESSURE PRESSURE PD ( PH − PC ) − BITE
SHUTOFF VALVE SWITCH PRESSURE
CONTROLLER SWITCH
( HPSOVC ) ACTUATOR
SERVO
PRESSURE
PH − BITE
PRESSURE
SWITCH
ENGINE GEARBOX
ANEROID DOSE FWD
HIGH PRESSURE
SHUTOFF VALVE
CONTROLLER
SENSING ELECTRICAL
LOCATION HIGH PRESSURE DIAPHRAGM CONNECTOR
SHUTOFF VALVE
CONTROLLER
MAGNETIC
SHUTOFF
SOLENOID PL − BITE
PRESSURE
SWITCH
HIGH STAGE
PRESSURE
INLET PORT
O−RING
FILTER
For Training Purposes Only
O−RING
SPRING
PRESSURE
REGULATING VALVE
CONTROLLER O−RING
FILTER PLUG
FWD
ENGINE 1 PREFERRED
GEARBOX 2 FILTER
1 PLUG 2 ALTERNATIVE
3 2 1
TERMINAL
BLOCK
OPEN/CLOSE
POSITION
HIGH PRESSURE
SHUTOFF VALVE SWITCHES
LOCKING
PIN HOLE
ELECTRICAL
CONNECTIONS
VISUAL
POSITION
INDICATOR
MANUAL
OPERATION
HEX NUT
VALVE ACTUATOR
ACTUATOR
SERVO
PRESSURE
For Training Purposes Only
LOCKING PIN
(STOWED POSITION)
FWD
VALVE OUTLET
HPSOVC AND HPSOV FUNCTION DESCRIPTION HIGH PRESSURE SHUTOFF VALVE OPEN
1st opening MODE :
Functional Description
Engine Bleed Air Switch (#) : ON
The power that is required for the high pressure controller is 28 volt dc.
ELECTRICALLY CONTROLLED
1. MODE :
ENGINE BLEED
AIR SWITCH :
ON
⇒
ÉÉÉÉÉ
2. MODE :
ÉÉÉÉÉ
ÉÉÉÉÉ
PNEU. CONT.
ÉÉÉÉÉ
THE HIGH PRESSURE SHUTOFF VALVE WILL AUTOMATICALLY OPEN, CONTROLLED BY THE ANEROID
For Training Purposes Only
BELLOW IF :
ÉÉÉÉÉ
OPEN
THE FLGHT ALTITUDE < 27000FT BY < 105PSI,
THE FLIGHT ALTITUDE < 42000FT BY < 77PSI.
28V DC REGULATED
BUS 1 POWER
AIR SUPPLY SUPPLY
CONTROL 1 PWR
P6 CB PANEL
NORMAL OFF
PULSE
GEN OPEN
FIRE ON
0.5 SEC
ENGINE 1 ENGINE 1
FIRE SW BLEED SW
5 SEC
OVERHEAT SWITCH
28V DC REGULATED
BUS 1 POWER
AIR SUPPLY SUPPLY
CONTROL 1 PWR PULSE OPEN
GEN
P6 CB PANEL
FIRE ON
14 psig
ENGINE 1 ENGINE 1 PC
FIRE SW BLEED SW
FAULT 20 psig
PD
MD&T SYSTEM
FAULT a 62 psig
PL
FIRE CONTROL PANEL (P5) RESET
127 psig
LATCH
PH
5 SEC
5 SEC FULLY OPEN
OVERHEAT SWITCH
5 SEC
FULLY CLOSE
AIR SUPPLY CONTROL TEST UNIT
(E2−4) HPSOV
EIU, EICAS
Figure 18 HPSOV MONITORING AND INDICATION CIRCUIT
FRA US/T ReF 12.12.05 Page 35
Lufthansa Technical Training
PNEUMATIC B 747 - 400
DISTRIBUTION PW 4000
36 − 10
PC (Pressure Control)
The pressure control switch opens when the pressure in the HPSOVC servo
pressure line is more than 14 psig (minimum OPEN−Pressure).
PL (Pressure Low)
The pressure High switch opens if the 15. stage pressure is above 62 psig
PH (Pressure High)
The pressure High switch opens if the 15. stage pressure is above 127 psig
R
E
F
E
R
ÇÇÇÇ
ÇÇÇÇ
T
O ÇÇÇÇ
ÇÇÇÇ
ÇÇÇÇ
D
I
N
A
3 ÇÇÇÇ
ÇÇÇÇ
For Training Purposes Only
ÇÇÇÇ
ÇÇÇÇ
P
A ÇÇÇÇ
ÇÇÇÇ
G
E
LEGEND :
SUPPLY PRESSURE
TO
ACTUATOR SERVO PRESSURE FAN AIR
FAN AIR
MODULATING R
VALVE
E
TO
LP PRESSURE F
REGULATOR
VALVE E
HIGH
R
PRESSURE
OPEN SHUTOFF
VALVE T
(HPSOV)
O
CLOSED
HP D
I
HIGH
PSIG
14
PRESSURE N
SHUTOFF
PC
VALVE
110
105
PD
20
CONTROLLER
(HPSOVC)
A
100 HPSOV
CLOSED PHL
3
For Training Purposes Only
OPEN
90
62
HPSOV
80 OPEN
PHH
P
70
74
127 A
FEET G
0 ABOVE CLOSE
0 20 000
27 000
30 000
42 000
40 000 50 000
SEA LEVEL E
OPERATION
When the pressure upstream of the intermediate pressure check valve
becomes more than the pressure downstream of the valve, the valve poppet
assembly moves to the open position. The tube guide in the inner shell guides B
the poppet assembly. This will occur when the HPSOV is in the closed position.
For Training Purposes Only
SUPPORT STRUT
VALVE
POPPET
VALVE
AND HOUSING
INNER SHELL
VALVE OPEN
VALVE CLOSED
For Training Purposes Only
FLOW
FILTER PLUG
O−RING
SPRING
FILTER
MAGNETIC
SUPPLY SHUTOFF
PRESSURE SOLENOID
ENGINE GEARBOX INLET
PRESSURE REGULATING
VALVE CONTROLLER
LOCATION ACTUATOR
HIGH PRESSURE SERVO
SHUTOFF VALVE PRESSURE
CONTROLLER ( HIDDEN )
PRV ACTUATOR
PRESSURE TUBE
FWD
PRESSURE
REGULATING
VALVE
CONTROLLER
( PRVC )
ELECTRICAL
For Training Purposes Only
DOWNSTREAM CONNECTOR
REGULATED
PRESSURE TUBE
REGULATED
UPSTREAM SUPPLY PRESSURE
PRESSURE TUBE INLET
ENGINE
GEARBOX
PRESSURE FWD
CONTROLLER
ELECTRICAL
CONNECTOR
LOCKING PIN
PRESSURE HOLE
REGULATING
VALVE LOCKING
CRANK
ELECTRICAL
CONNECTORS
VALVE
ACTUATOR
3 2 1
TERMINAL
ACTUATOR
BLOCK SERVO
PRESSURE
OPEN/CLOSE
POSITION
SWITCHES
LOCKING PIN
VALVE
INLET
For Training Purposes Only
VALVE
OUTLET
VISUAL
POSITION
INDICATOR
MANUAL
OPERATION
HEX NUT LOCKING PIN
ENGINE FIRE ENGINE BLEED ENGINE ENGINE ENGINE HIGH PRESS STARTER PRESSURE
SWITCH : BLEED AIR BLEED AIR BLEED SHUTOFF VALVE REGULATING
AIR PRESS
NORM SWITCH : SWITCH : OVERTEMP VALVE : CLOSED VALVE
< 64 PSI
ON OFF < 243C/<470F CLOSED ( > 15 SEC. ) OPEN
COMMAND
1. MODE :
ENGINE BLEED
AIR SWITCH : ⇒
ELECTRICALLY CONTROLLED
ON
2. MODE :
NACELLE
ANTI − ICE
ACTIVE
⇒
3. MODE :
NACELLE
ANTI − ICE ⇒
For Training Purposes Only
ACTIVE
28V DC REGULATED
BUS 1 POWER
AIR SUPPLY SUPPLY
CONTROL 1 PWR PULSE OPEN
GEN
P6 CB PANEL
NORMAL OFF
ON PULSE
FIRE GEN
ENGINE 1 ENGINE 1 CLOSE
FIRE SW BLEED SW
PRV
FIRE CONTROL PANEL (P5) CONTROLLER
NACELLE
ANTI−ICE ON
RESET
470F/243C
LATCH
5 SEC
For Training Purposes Only
OVERHEAT SWITCH
15 SEC
CLOSED
28V DC REGULATED
BUS 1 POWER
AIR SUPPLY SUPPLY
CONTROL 1 PWR PULSE OPEN
P6 CB PANEL GEN
NORMAL OFF
FIRE ON PULSE
GEN
ENGINE 1 ENGINE 1 CLOSE
FIRE SW BLEED SW
PRV CTRL
SYSTEM
MD&T FAULT
a NACELLE
FAULT OPEN
ANTI−ICE ON
FIRE CONTROL PANEL (P5)
RESET BITE
LATCH LOGIC CLOSE
470F/243C
PRV
5 SEC HPSOV
For Training Purposes Only
POS SW EIU
OVERHEAT SWITCH EICAS
CLOSED 15 SEC 5 SEC
OPEN
START VALVE AIR SUPPLY CONTROL TEST UNIT (E2−4)
R
E
F
E
R
ÇÇÇÇ
ÇÇÇÇ
ÇÇÇÇ
T
O
ÇÇÇÇ
ÇÇÇÇ
D
I
N
A
3
ÇÇÇÇ
ÇÇÇÇ
For Training Purposes Only
ÇÇÇÇ
P ÇÇÇÇ
A ÇÇÇÇ
ÇÇÇÇ
G
E
ÎÎÎ
FROM
R
ÎÎÎ
8th STAGE
OR
E
ÎÎÎ
HPSOV TO
(15th STAGE) PRESSURE
F
ÎÎÎ
OPEN
REGULATING
ÎÎÎ
SHUTOFF
VALVE
E
ÎÎÎ ÎÎÎÎÎ R
PRESSURE (ENGINE BLEED AIR)
ÎÎÎ ÎÎÎÎÎ
REGULATOR
VALVE CLOSED
( PRV )
ÎÎÎÎÎ
PRECOOLER
T
O
TO D
PRESSURE
REGULATING I
SHUTOFF
VALVE N
ÎÎÎÎ
( OPEN PRESSURE )
ÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎ
ÎÎÎ
ÎÎÎÎÎ
ÎÎÎ ÎÎÎÎ
ÎÎÎÎÎ
A
ÎÎÎÎ
LEGEND : PRESSURE
3
ÎÎÎ
REGULATOR
SUPPLY PRESSURE
For Training Purposes Only
OPEN
ACTUATOR SERVO PRESSURE
ÎÎÎ
ÎÎÎ
PRESSURE
REGULATOR
ÎÎÎ
REGULATED PRESSURE
CLOSE
VALVE P
CONTROLLER
( PRVC ) A
G
E
Figure 28 PRVC AND PRV SCHEMATIC
FRA US/T ReF 12.12.05 Page 53
Lufthansa Technical Training
PNEUMATIC B 747 − 400
DISTRIBUTION PW 4000
36 - 10
FAN AIR TEMPERATURE SENSOR (FATS) FAN AIR SYSTEM FAULT INDICATION
The proper function of the FATS/FAMV are continuously monitored by the
Description
CMC.
The fan air temperature sensor controls the servo pressure that controls the In case of malfunction
fan air modulating valve.
the Advisory Message
The fan air temperature sensor is installed on the pneumatic duct in the left
− BLEED (#)
side of the strut.
appears.
The temperature probe extends into the pneumatic duct.
The sensor body has a lever and a crank that are operated by a bimetallic
In case of malfunction also the Status Message
temperature probe.
BLEED FAMV ENG (#)
The sensor is adjusted to maintain the Precooler outlet temperature to
nominal 177C/350F (within the specified operational range of will be displayed on lower EICAS.
160C/320F - 193C/380F).
The sensor is cooled with fan air . The CMC provides the associated CMC Present Leg Fault/Existing Fault
Message visible on the MCDU:
The sensor is not monitored by the CMCS.
BLEED − (#) FAN AIR MODULATING VALVE/FAN AIR TEMPERATURE
SENSOR FAIL
FATS OPERATION
In case of disagree (valve is commanded to open but is closed or valve
The bimetallic−temperature probe in the pneumatic duct connects the is commanded to close but remains open), the messages discribed above
compensating springs to the control lever. appears and in addition the following CMC Present Leg Fault/Existing Fault
Message are displayed:
The temperature changes in the duct cause the temperature probe to change BLEED (#) TEMPERATURE CONTROL SYSTEM FAIL OPEN or
the force on the control lever. The movement of the control lever causes the BLEED (#) TEMPERATURE CONTROL SYSTEM FAIL CLOSED
poppet to open or close. This will change the pressure signal that is sent to
the fan air modulating valve.
For Training Purposes Only
OUTBOARD
INBORD FAN AIR TEMPERATURE
FAN AIR TEMPERATURE SENSOR
SENSOR
FAN AIR
TEMPERATURE
SENSOR
SIGNAL
PRESSURE INLET
TUBE FILTER
MOUNTING BOLT
For Training Purposes Only
COOLING FWD
AIR TUBE
FAN AIR MODULATING VALVE (FAMV) FAN AIR SYSTEM FAULT INDICATION
The proper function of the FATS/FAMV are continuously monitored by the
Description
CMC.
The fan air modulating valve is installed on the right side of the precooler. In case of malfunction
The valve is a nine inch diameter pneumatically−operated butterfly valve. the Advisory Message
It is spring loaded in the open position. − BLEED (#)
The precooler outlet servo pressure is used to operate the fan air appears.
modulating valve. When the valve receives the pneumatic signal from the
fan air temperature sensor, it will move toward the closed position.
In case of malfunction also the Status Message
There is a locking crank on the actuator to permit the valve to be operated
BLEED FAMV ENG (#)
manually. There are 2 different methods to deactivate the valve:
will be displayed on lower EICAS.
1. deactivation method:
The valve can be deactivated in the 48 (intermediate) position with a
THE CMC provides the associated CMC Present Leg Fault/Existing Fault
positioning screw.
Message visible on the MCDU:
If the valve must be locked, the lockpin is removed from the actuator case.
This lets valve control pressure go to ambient. The pin is installed through BLEED − (#) FAN AIR MODULATING VALVE/FAN AIR TEMPERATURE
the valves manual control linkage into a threaded hole to lock the valve in SENSDOR FAIL
the closed position.
2. deactivation method:
The valve can be deactivated also in the full open position by disconnecting NOTE: A FAULT OF FATS AND FAMV CAN BE DETECTED ONLY, IF
the servo pressure line at the Fan Air Temperature Sensor (FATS). The BLEED AIR PRESSURE OF MORE THAN 14 PSI IS AVAILABLE
valve then remains springloaded open. AND THE AIRPLANE IS IN AIR.
FAN AIR
MODULATING
VALVE
ÎÎÎÎ
LOCATION
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎÎÎ
ÎÎÎÎ
SPACER
ASSEMBLY ÎÎÎÎ
ÎÎÎÎ
BONDING
JUMPER
ÎÎÎ
ÎÎÎÎ
ÎÎÎ
FLANGE
PLATE
ÎÎÎ
ÎÎÎ
ÎÎÎÎ ÎÎÎ
ÎÎÎÎ ÎÎÎ
SWITCH SUPPLY
ÎÎÎ ÎÎÎÎÎÎ
CLOSE PORT
PIN
( FROM FATS )
ÎÎÎ ÎÎÎÎ
INLET
FILTER
ÎÎÎ ÎÎÎÎ
For Training Purposes Only
OPEN TERMINAL
BLOCK
ÎÎÎÎ
LOCKING
CRANK ÎÎÎÎ
ÎÎÎÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎ
AFT VIEW COOLING AIR
OUTLET
ÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎ
COOLING AIR PORT
FAN AIR TEMPERATURE SENSOR AND VALVE SCHEMATIC FAN AIR MODULATING VALVE LOCKOUT
There is a locking crank on the actuator to permit the valve to be operated
Functional Description
manually. There are 2 different methods to deactivate the valve:
All of the engine bleed air goes through the precooler before it goes into the
1. deactivation method:
airplane pneumatic ducts. The quantity of cool fan air that goes through the
precooler is controlled by the position of the fan air modulating valve. The valve can be deactivated in the 48 (intermediate) position with a
positioning screw.
The fan air temperature sensor measures the temperature in the pneumatic
If the valve must be locked, the lockpin is removed from the actuator case.
duct and controls the position of the fan air modulating valve.
This lets valve control pressure go to ambient. The pin is installed through
The fan air modulating valve (FAMV) is opened and closed by bleed air the valves’ manual control linkage into a threaded hole to lock the valve in
pressure from the precooler.The signal pressure from the fan air temper- the closed position.
ature sensor (FATS) modulates the closed pressure.
2. deactivation method:
The valve can be deactivated also in the full open position by disconnecting
Operation the servo pressure line at the Fan Air Temperature Sensor (FATS). The
valve then remains springloaded open.
When the temperature of the engine bleed air sensed by the FATS is
below 160C/320F, the FAMV is closed.
is between 160C/320F and 193C/380F, the FAMV is modulating FAMV FAULT DETECTION AND INDICATION
above 193C/380F, the FAMV is fully open.
The proper function of the fan air modulating valve is monitored by an
OPEN− and CLOSED−Limit Switch.
The indicated temperature on the EICAS ECS maintenance page may vary The switches send their signals to the ASCTU.
between 121C/250F and 193C/380F while the fan air modulating valve
The position of the fan air modulating valve
regulates between open and closed.
– OPEN – REGLTG – CLOSED
The pressure signal will change in proportion to the temperature. is shown on the ECS SUPPLY Maintenance Page.
The pressure signal is sent through the signal pressure tube. The cooling air
tube supplies the sensor with pressurized air. The air in this tube is cool and NOTE: A FAULT OF FATS AND FAMV CAN BE DETECTED ONLY, IF
decreases the temperature of the sensor. BLEED AIR PRESSURE OF MORE THAN 14PSI IS AVAILABLE
For Training Purposes Only
After the fan air modulating valve receives the pressure signal, it uses AND THE AIRPLANE IS IN AIR.
precooler pressure to change the position of the butterfly valve. As the
valve moves to the open position, more fan air is permitted to go through the
precooler. The fan air then flows overboard through a duct in the core cowl.
LEGEND :
COOLING AIR
PRESSURE OVERPRESSURE
PRESSURE SENSOR SWITCH SUPPLY PRESSURE
PRESSURE
REGULATOR REGULATOR
CONTROL CONTROL ACTUATOR
SERVO
ADJUSTMENT PRESSURE
OPEN
FAN AIR
MODULATING POPPET
VALVE CONTROL
( FAMV ) LEVER
FAN AIR
TEMPERATURE
CLOSE SENSOR
( FATS )
FAN
AIR
INLET
FATS
SERVO FAMV FROM
PRESS ANGLE PRESSURE
(PSI) () REGULATOR
VALVE
TO
10 90 PRESSURE
OPEN REGULAOR
9 SHUTOFF
8 160C/320F VALVE
For Training Purposes Only
7
BLEED AIR
6 OVERTEMPERATURE
177C/350F
5 45 SWITCH
4 PRECOOLER
3 193C/380F BLEED AIR
2 TEMPERATURE
1 FATS SENSOR
EBA SERVO
0 TEMP. PRESS
(C) 0 FAN AIR
0 160 170 180 190 200 0 1 2 3 4 5 6 7 8 9 10 (PSI)
CLOSE OUTLET
BLEED AIR
OUTLET
FAN AIR
OUTLET
For Training Purposes Only
PRECOOLER
EXHAUST FLANGE
HIGH/INTERMEDIATE
PRESSURE INLET
FAN AIR
INLET
(ROTATED FOR CLARITY)
servo pressure is sent to ambient. With no servo pressure, the valve will
move to the spring loaded closed position. The shutoff solenoid is energized by
The temperature control portion of the valve will begin to close the valve
Engine Bleed Air Switch (#) : OFF or when the temperature gets to 220C/428F. When the temperature gets to
Engine Fire Handle (#) FIRE or 232C/450F the valve will be nearly closed.
Overheat Switch (#) OVERHEAT The temperature is measured by a probe which extends into the valve duct.
The temperature probe is protected by a thin metal tube which is easily
When the magnetic shutoff solenoid is in the ENABLED position, the valve can damaged and will not support heavy loads.
be opened by pneumatic air. The valve opens when the air pressure is more The temperature regulation function is deactivated during engine start.
than the spring force. This causes the pneumatic actuator to open the valve.
LOCKING PIN
(STOWED POSITION)
PRESSURE REGULATING
AND SHUTOFF VALVE (PRSOV)
SHUTOFF
(MAGNETIC)
SOLENOID
TEMPERATURE
SENSOR
ASSEMBLY
MAIN FILTER
OPEN AND
CLOSED-
LIMIT
SWITCH
For Training Purposes Only
TEMPERATURE
SENSOR
PROBE HEX FOR MANUAL
OPERATION (VALVE
VALVE
SHAFT EXTENSION)
DISK
LOCKING PIN
(STOWED POSITION)
PRESSURE REGULATING
AND SHUTOFF VALVE (PRSOV)
SHUTOFF
(MAGNETIC)
SOLENOID
TEMPERATURE
SENSOR
ASSEMBLY
MAIN FILTER
OPEN AND
CLOSED-
LIMIT
SWITCH
For Training Purposes Only
TEMPERATURE
SENSOR
PROBE HEX FOR MANUAL
OPERATION (VALVE
VALVE
SHAFT EXTENSION)
DISK
The proper function of the PRSOV are continuously monitored by the CMC.
In case of malfunction
the Advisory Message
− BLEED (#)
appears on Main EICAS.
The CMC provides the associated CMC Present Leg Fault/Existing Fault
Message visible on the MCDU:
BLEED (#) PRESSURE REGULATOR & SHUTOFF VALVE FAIL
PRECOOLER
PRESSURE
SENSE PORT
RIGHT SIDE
DOWNSTREAM DOWNSTREAM
PRESSURE FWD PRESSURE PRECOOLER
SENSE TUBE SENSE PORT PRESSURE
SENSE TUBE
BONDING
PRSOV STRUT ACCESS
JUMPER DOOR OPENING
PRSOV
PORT G1
PORT G2
For Training Purposes Only
LEFT SIDE
AIR FILTER
36 - 10
MANUALLY OPERATE THE PRSOV Push the manual override drive in approximately 1/4 inch with the drive ex-
tension.
Turn the manual override drive 90 degrees or more in the clockwise direc-
Special Tools and Equipment tion.
G71021−6 Drive Extension − Starter Valve and PRSOV (Recommended) NOTE: THE VALVE WILL BE RELEASED AND IN THE SPRING LOADED
15MIT65B00717 − Wrench, Pylon Valve Manual Drive (Optional) CLOSED POSITION.
36 - 10
ÎÎÎÎ
ÎÎÎ
ÎÎÎ
ÎÎÎÎ
ÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
OPEN
POSITION ACCESS
ÎÎÎ
TO THE
ÎÎÎ
ÎÎÎÎ
MANUAL OVERRIDE
ÎÎÎ
ÎÎÎÎ
ÎÎÎÎ ÎÎÎ
ÎÎÎÎ
MANUAL
ÎÎÎÎ ÎÎÎÎ
OVERRIDE
ÎÎÎÎ
ÎÎÎÎ
CLOSED
POSITION
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎ ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎ ÎÎÎÎÎÎ
For Training Purposes Only
ÎÎÎÎÎÎ
ÎÎÎÎ ÎÎÎÎÎÎ
LOCKED CLOSED
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ RATCHET
LEFT SIDE OF THE ENGINE STRUT
28V DC REGULATED
BUS 1 POWER
AIR SUPPLY SUPPLY
CONTROL 1 PWR PULSE OPEN
GEN
P6 CB PANEL
NORMAL OFF
PULSE
ON GEN
FIRE CLOSE
ENGINE 1
FIRE SW 20
PRL
57
PRH
MD&T BITE
OFF LOGIC
a FULL OPEN
ENGINE 1
BLEED SW
PRSOV
EIU
Figure 37 PRSOV MONITORING AND INDICATION CIRCUT
FRA US/T ReF 12.12.05
Lufthansa Technical Training
PNEUMATIC B 747 - 400
DISTRIBUTION PW 4000
36 - 10
28V DC
BUS 1
AIR SUPPLY
CONTROL 1 PWR
28V DC
APU BAT
BUS
ENG START/
IGN CONTROL 1
REGULATED
POWER
P6 CB PANEL SUPPLY
PULSE OPEN
GEN
NORMAL OFF
PULSE
GEN
FIRE ON CLOSE
ENGINE 1 ENGINE 1
FIRE SW BLEED SW REVERSE
FLOW
For Training Purposes Only
SOLENOID
OFF
START
AIR SUPPLY CONTROL TEST UNIT (E2−4) PRESSURE
ENGINE 1 START SW R7538 REGULATING
START 1 AND SHUTOFF
FIRE CONTROL PANEL (P5) (P414) VALVE
ENG SPEED CARD GND = LOGIC 0
PRSOV CLOSE
To close the PRSOV the engine bleed switch is put in the OFF position.
The ASCTU will then send a 28v dc pulse to set the valve to the OFF mode.
LEGEND :
PNEUMATIC SYSTEM NO.1 SHOWN,
OTHER SYSTEMS SIMILAR.
GROUND = 0
GROUND = 1
28V DC
BUS 1
POWER
SUPPLY
AIR SUPPLY
CONT 1 PWR
28V DC
P6−4 REVERSE
FLOW
SOLENOID
OFF
OPEN
START 28V DC
R 7538 MAGNETIC
START RELEAY SOLENOID
ENGINE START (P6)
SWITCH 0,5
SEC
CLOSE
ÎÎ
PULS
FIRE
ÎÎ
OFF
28V DC
ÎÎ
> 20 PSI
NORMAL PL
ON
ÎÎ
1 0,5
ENGINE FIRE > 55 PSI
SEC
ÎÎ
PH
SWITCH ON PULS
OFF B I T E−
For Training Purposes Only
LOGIC
OPEN
BLEED AIR
CONTROL SWITCH
(P 5)
SIGNAL
CONDITIONER
CLOSED
TO EFIS/EICAS
EICAS INTERFACE
DISPLAYS PRESSURE REGULATING
UNITS
SHUTOFF VALVE
AIR SUPPLY CONTROL TEST UNIT
two control diaphragms pressure through the diaphragm. If downstream pressure exceeds upstream
pressure by 0.13 psi, the poppet moves down and the servo pressure is sent to
two feedback diaphragms
ambient. This will cause the valve to close.
a poppet control lever.
NOTE: THE REVERSE FLOW CHECK FUNCTION IS DEACTIVATED
The control diaphragms control the movement of the poppet. The poppet lets
DURING ENGINE START.
servo pressure bleed to ambient or push against the piston. When downstream
pressure pushes on the control diaphragm, the poppet opens, servo pressure
bleeds to ambient, and the valve closes. The downstream pressure pushes An electrically operated reverse flow solenoid is used during engine start.
against preset spring tension to close the poppet. This lets servo pressure When the engine starter valve is NOT CLOSED, a signal is sent to the sole-
push on the actuating piston which will move the valve to the open position. noid. The solenoid then lets the valve use downstream air pressure to open the
valve.
VALVE PRESSURE
REFER TO DIN A3 PAGE
ANGLE CONTROLLER
220C/428F TEMPERATURE
90 CONTROLLER
OP
DOWNSTREAM
PRESSURE
45
232C/450F
P P
RH RL
0 TEMP
PRESSURE
CL ( C ) SWITCHES
215 220 225 230 235 240 FEEDBACK
TEST PORT
REVERSE FLOW
VALVE LIMITER
ANGLE S/O SOLENOID PRECOOLER
INLET
32 PRESSURE
90
OP
START
SOLENOID
Pa
45 CL SW
OP SW
47 CLOSE
0 PRESS TEMPERATURE
( PSI ) SENSOR
For Training Purposes Only
CL
30 32 34 36 38 40 42 44 46 48 50
INC T PA
ACTUATOR ACCESS
ACCESS
PORT PNEUMATIC PORT
TEST PORT
ACTUATOR
FLOW
RIGHT
WING ISOLATION
VALVE
ÎÎÎÎÎÎ
LEFT
WING ISOLATION
ÎÎÎÎÎÎ
VALVE
ÎÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎÎ
MANUAL DRIVE
ÎÎÎÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎÎÎÎ
ELECTRICAL
ÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎÎÎÎ
CONNECTOR
ÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
ACTUATOR
For Training Purposes Only
ÎÎÎÎÎ
HOUSING
ÎÎÎÎÎ
POSITION
INDICATOR
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
COUPLING
APU
ISOLATION
ÎÎÎÎÎ
VALVE
ÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
APU BLEED
ÎÎÎÎÎ
AIR VALVE
ÎÎÎÎÎÎ
ÎÎÎ
ÎÎÎ ÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎ ÎÎÎÎÎ ÎÎÎ
ÎÎÎÎÎÎ
MANUALOVERRIDE
For Training Purposes Only
ÎÎÎÎÎÎÎ ÎÎÎÎÎ
DRIVE
FWD
ÎÎÎÎ ÎÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ BONDING
ÎÎÎÎÎ
ELECTRICAL
ÎÎÎÎÎ
CONNECTOR
ÎÎÎÎ
JUMPER
FROM
APU ISOLATION
VALVE
APU
CHECK
VALVE
ÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎ
APU CHECK VALVE
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎÎ
COUPLING SEAL
For Training Purposes Only
TO
CROSSOVER
DUCT
NOTE: CHECK THAT THE THE CHECK VALVE FLAPPERS ARE CLOSED
BEFORE YOU CLOSE THE ACCESS DOOR.
For Training Purposes Only
ÎÎÎ
ÎÎÎ
ÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎ ÎÎÎ APU
ÎÎÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎ
ÎÎÎÎÎ
ÎÎÎ
ÎÎÎÎÎÎ
AIR CONDITIONING
ÎÎÎÎÎ
ÎÎÎ
PACKS
(3 LOCATIONS)
PNEUMATIC GROUND
ÎÎÎ
AIR CONNECTORS
(REF)
SEE A
ÎÎÎÎÎ ÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎ ÎÎÎÎÎ
ÎÎÎÎÎÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎ
CHECK VALVE ÎÎÎÎÎ
ÎÎÎ
ÎÎÎÎÎ
ÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎÎÎ GASKET
ÎÎÎÎ
ÎÎÎ AND NUT
ÎÎÎÎÎÎ ÎÎÎÎ
ÎÎÎÎÎÎ
FLANGE
FWD BOLT, WASHER,
For Training Purposes Only
ÎÎÎ ÎÎ ÎÎÎÎ ÎÎ
AND NUT
ÎÎÎ INBD
ÎÎ ÎÎ
ÎÎ
ÎÎ 2 ÎÎÎÎÎÎÎ
ÎÎ
ÎÎÎÎÎÎÎ
ÎÎ 1
ÎÎÎÎÎÎÎ
A
GROUND
CONNECTOR GROUND CONNECTOR
1 CHECK VALVE WITHOUT FLANGE
SEE B
2 CHECK VALVE WITH FLANGE B
The CMC provides the associated CMC Present Leg Fault/Existing Fault
Message visible on the MCDU:
WING ISOLATION VALVES INDICATION ISOLATION VALVE L FAIL
Fault monitoring and indication is provided by the internal actuator ISOLATION VALVE R FAIL
OPEN and CLOSE limit switches.The switches send their signals to the
ASCTU.
The VALVE light will come on when any of the following conditions occur:
the Valve is IN TRANSIT
the valve has a disagree with the respective Wing Isolation Valve switch.
(valve is commanded to open but is closed or valve is commanded to close
For Training Purposes Only
NOTE :
POWER SUPPLY FOR THE RIGHT WING ISOLATION VALVE OPEN
VIA THE CIRCUIT BREAKER :
R ISO VLV AIR
SUPPLY PWR
115V AC BUS 3
(P 6−3 H 24) 115V AC
BUS 1
L ISO VLV AIR CLOSE
SUPPLY PWR
LEFT ISLN VALVE
P 6−3 H 20
VALVE
MD&T a
PANEL w
LIGHTS
CIRCUIT LEFT ISLN
VALVE SW
BLEED AIR
CONTROL (P5)
CMCS MESSAGE
CENTRAL − ISOLATION VALVE−L FAIL
MAINT. ( 36 057 )
COMPUTER − ISOLATION VALVE−R FAIL
( 36 058 )
For Training Purposes Only
10 SEC
ADVISORY MESSAGE
SIGNAL EFIS/EICAS − BLEED ISLN L
CONDITIONER INTERFACE − BLEED ISLN R
UNITS STATUS MESSAGE
− BLEED ISLN L
NOTE :
− BLEED ISLN R
LEFT ISOLATION VALVE SYSTEM SHOWN, AIR SUPPLY CONTROL
RIGHT ISOLATION VALVE SYSTEM SIMILAR. TEST UNIT (ASCTU)
Figure 45 Wing Isolation Valve Circuit
FRA US/T ReF 12.12.05 Page 85
Lufthansa Technical Training
PNEUMATIC B 747 - 400
DISTRIBUTION PW 4000
36 - 10
OPEN
115V AC
BUS 2
APU ISO VLV AIR
SUPPLY PWR
P 6−3 H 22
28V DC
BUS 2
APU VALVE
AIR SUPPLY CONT CLOSE
R 7745 V 121
P 6−4 H 36 AIR SUPPLY APU VALVE APU BLEED AIR
CONTROL RELAY ISOLATION VALVE
R 7730
APU START LATCH RELAY
(P6) APU N1
RPM > 95%
NORMAL
R 7715
N1 SPEED RELAY
OFF
For Training Purposes Only
ON
PANEL 10 SEC
LIGHTS ON
CIRCUIT w
ADVISORY MESSAGE
SIGNAL EFIS/EICAS − BLEED ISLN APU
VALVE CONDITIONER INTERFACE − > BLEED ISLN APU
MD&T a UNITS STATUS MESSAGE
APU ISLN − BLEED ISLN APU
VALVE SWITCH
AIR SUPPLY CONTROL
BLEED AIR TEST UNIT
CONTROL (P5)
Figure 46 Apu Isolation Valve Circuit
FRA US/T ReF 12.12.05 Page 87
Lufthansa Technical Training
PNEUMATIC B 747 - 400
DISTRIBUTION PW 4000
36 - 00
It makes an analysis of this information and sends the appropriate command
AIR SUPPLY CONTROL TEST UNIT (ASCTU) signals to the
The ASCTU is installed in the main equipment center aft of the nose gear High Pressure Shutoff Valve Controller (HPSOVC)
wheel well on the E2−4 rack. The ASCTU gives control and indication data for Pressure Regulator Valve Controller (PRVC)
the pneumatic system components except for: Pressure Regulator and Shutoff Valve (PRSOV).
the Fan Air System (Sensor and Valve) The ASCTU monitors the position of
the Isolation Valves (3) High Pressure Shutoff Valve (HPSOV) (4)
The ASCTU has the following components: Pressure Regulator Valve (PRV) (4)
four control logic cards (bleed control modules) Pressure Regulator and Shutoff Valve (PRSOV) (4)
one isolation card Fan Air Modulating Valve (4)
two monitor cards Wing Isolation Valves (2)
one power supply card. APU Isolation Valve (1)
The ASCTU has a Built In Test (BITE) function that gives status information to This information is processed and sent to EICAS.
EICAS and the central maintenance computer (CMC). The build in test equip-
ment consists of
The ASCTU determines the proper function of the
BITE−Module A
HPSOV Controller (using 4 BITE pressure switches to check the EBA)
BITE−Module B
PRSOV (using 2 BITE pressure switches to check the EBA).
BITE−Input/Output Module
The redundant BITE logic will continuously monitor the air supply components, If the ASCTU determines that there is a system failure, the BITE part of the
but does not supply inputs for the operation or control of the pneumatic system. ASCTU will send the component fault to the CMC. The indication part of the
ASCTU will send a signal to the SYS FAULT light on the bleed control
ASCTU OPERATION
module and to EICAS if any of this conditions occur:
The ASCTU consists of two independend channel (CH-A and CH-B) and is Pneumatic System Overheat (>243C/>470F)
power supplied by the DC Bus 1 - 4. The channel are connected together with
Pneumatic System Overpressure ( >76 psi )
an internal data link. Each channel has 4 printed circuit boards, which are
attached to the respective engine. (Bleed Control Module No.1 attached to HPSOV and PRV malfunction.
For Training Purposes Only
36 - 20 INDICATION
MANIFOLD PRESSURE INDICATION MANIFOLD PRESSURE INDICATION FAULT INDICATION
MANIFOLD DUCT PRESSURE TRANSMITTER (2) The proper function of the duct pressure transmitters are continuously
monitored by the CMC. In case of malfunction
The pressure in the pneumatic manifold is sensed by duct pressure
transmitters. the Advisory Message
There are two pressure transmitters (L, R) installed in the left and right pneu- − ENG (#) START VLV
matic wing manifold, both transmitters are located upstream of their respective appears.
wing isolation valves. In case of malfunction also
The transmitters can be accessed through the air conditioning bay, near packs the Status Message
1 and 3. − ENG (#) START VLV
The transmitters are strain gage based pressure transducers. Pressure signals will be displayed on lower EICAS.
from the transducers are sent to the EICAS and CMCS via the ASCTU.
The CMC provides the associated CMC Present Leg Fault/Existing Fault
The pneumatic manifold duct pressure is shown on the Message visible on the MCDU:
Main EICAS Display
ECS Synoptic Page MANIFOLD PRESSURE SENSOR − L FAIL
ECS Maintenance Page MANIFOLD PRESSURE SENSOR − R FAIL
APU Maintenance Page
Engine Performance Maintenance Page.
MANIFOLD
DUCT PRESSURE
TRANSMITTER
DUCT PRESSURE
TRANSMITTER
For Training Purposes Only
FWD
PRESSURE SENSING
TUBE
PRECOOLER
PRESSURE
SENSOR
BLEED AIR TEMPERATURE SENSOR FAULT INDICATION BLEED AIR OVERTEMP SWITCH FAULT INDICATION
The proper function of the bleed air temperature sensors are continuously The proper function of the bleed air overtemperature switches are continuously
monitored by the BITE logic. In case of malfunction monitored by the BITE logic. In case of malfunction
the Advisory Message the Advisory Message
− BLEED (#) OVHT − BLEED (#) OVHT
comes in view along with comes in view along with
the Status Message the Status Message
− BLEED (#) OVHT − BLEED (#) OVHT
on lower EICAS. on lower EICAS.
For Training Purposes Only
The CMC provides the associated CMC Present Leg Fault/Existing Fault The CMC provides the associated CMC Present Leg Fault/Existing Fault
Message visible on the MCDU: Message visible on the MCDU:
BLEED − (#) TEMPERATURE SENSOR FAIL BLEED − (#) OVERTEMP SWITCH FAIL
BLEED AIR
TEMPERATURE
OVERTEMPERATURE SENSOR
SWITCH
JAMNUT PACKING
RETAINER
MOUNTING BOSS
For Training Purposes Only
PACKING
36 - 20 INDICATION
PNEUMATIC INDICATION CIRCUIT
TEMPERATURE SENSOR OVERHEAT SWITCH
The temperature sensor measures the temperature of the air in the bleed duct The overtemperature switch senses the temperature of the air in the bleed duct
downstream of the precooler. downstream of the precooler. The switch gives an electrical ground to the
ASCTU when the temperature is below 243C/470F. When the temperature
goes above 243C/470F for more than 5 seconds, the switch gives an open
The temperature indication system gets power from the 28V DC bus.
circuit to the ACSTU.
The sensor sends a DC signal to the Air Supply Control and Test Unit (ASCTU)
When the bleed air overtemperature switch opens,
BITE−Logic which changes in proportion to the bleed air temperature.
the control logic in the ASCTU will close the
− HPSOV and the
The bleed air temperature is displayed on the ECS AIR SUPPLY maintenance
page only. − PRV
by using their respective controllers.
the circuit that controls the HPSOV and PRV latches the valves closed.
PRECOOLER OUT TEMP 178 180 183 171
NOTE: THE VALVES WILL NOT AUTOMATICALLY OPEN WHEN THE
TEMPERATURE DECREASES BELOW 243C/470F. TO RE-
The temperature is displayed in centigrade (C ). LEASE THE LATCHED CLOSED CONDITION, IT IS NECESSARY
TO OPERATE THE ENGINE BLEED SWITCH FROM ON TO OFF
AND THEN BACK TO ON AGAIN. THE HPSOV AND PRV WILL
THEN OPEN IF THE BLEED AIR TEMPERATURE IS BELOW
243C/470F.
NOTE: The PRSOV also closes after the PRV is closed because there is no
open pressure available. The PRSOV OFF light goes ON when the
PRSOV is fully closed.
28V DC
BUS 1
POWER MAGNETIC
SUPPLY SOLENOID
AIR SUPPLY 0,5
SEC
CONT 1 PWR PULS
CLOSE
P6−4
HIGH PRESSURE
SOV CONTROLLER
MD&T SYS
FAULT
OPEN
OFF 0,5
SEC
PULS
ON MAGNETIC
1
SOLENOID
ON
OFF CLOSE
PRESSURE REGULATOR
VALVE CONTROLLER
BLEED AIR
CONTROL SWITCH
(P 5)
>243C
>470F RESET B I T E−
LOGIC
5 SEC LATCH BLEED AIR
<243C
TEMPERATURE
<470F SENSOR
OVERHEAT
SWITCH 5 SEC SIGNAL BLEED
CONDITIONER AIR
PRESSURE
For Training Purposes Only
SENSOR
AIR SUPPLY CONTROL TEST UNIT PWR SUPPLY
60 SEC
T
D 28V DC
>76PSI TO EFIS/EICAS BUS 1
OVERPRESSURE EICAS INTERFACE
DELAY TIMER DISPLAYS UNITS AIR SUPPLY
<76PSI RELAY CONT 1 PWR
OVERPRESSURE (E2−4)
P6−4
SWITCH
OPEN
28V DC
BUS 1
POWER MAGNETIC
SUPPLY SOLENOID
AIR SUPPLY 0,5
SEC
CONT 1 PWR PULS
P6−4 CLOSE
HIGH PRESSURE
SOV CONTROLLER
MD&T SYS
FAULT
OPEN
OFF 0,5
SEC
PULS
ON MAGNETIC
1
SOLENOID
ON
OFF CLOSE
PRESSURE REGULATOR
VALVE CONTROLLER
BLEED AIR
CONTROL SWITCH
(P 5)
>243C
>470F RESET BITE
LOGIC
5 SEC LATCH BLEED AIR
<243C
TEMPERATURE
<470F SENSOR
OVERHEAT
SWITCH 5 SEC SIGNAL BLEED
CONDITIONER AIR
PRESSURE
For Training Purposes Only
SENSOR
AIR SUPPLY CONTROL TEST UNIT PWR SUPPLY
60 SEC
T
D 28V DC
>76PSI TO EFIS/EICAS BUS 1
OVERPRESSURE EICAS INTERFACE
DELAY TIMER DISPLAYS UNITS AIR SUPPLY
<76PSI RELAY CONT 1 PWR
OVERPRESSURE (E2−4)
P6−4
SWITCH
ME N U
GR O U N D TESTS 4/ 6
1L < F MC 1R
1L < 34 NAVIGATION RADIOS 1R
2L 2R
2L < 34 FLIGHT MANAGEMENT 2R
3L 3R
3L < 36 PNEUMATICS 3R
4L 4R
4L < 45 CENTRAL MAINTENANCE 4R
5L 5R
5L < 49 APU 5R
6L < C MC < A CT > 6R −−−−−−−−−−−−−−−−−−−−−−−−
6L < RE T URN HE L P > 6R
C MC ME N U 1/ 2 G R OU N D TESTS 1/ 1
4L < GR OU N D TESTS 4R 4L 4R
5L 5R 5L 5R
−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−
6L HE L P > 6R 6L < RE T URN HE L P > 6R
initial value. The message advises the crew to switch the systems ON.
If the heater cannot melt the ice after 25 seconds, or if the internal temperature
of the ice detector exceeds 149C/300F, the heater and the detector outputs The Message
are automatically deactivated.
> ANTI-ICE NAC (#) (Level C Advisory) and/or
Each ice detector provides an output to activate the corresponding left or right
side engine anti−ice systems, and a separate output to activate the wing > ANTI-ICE WING L (R) (Level C Advisory) appears if
anti−ice system at a different level of ice buildup than the engine systems. the NAI−System has been switched ON and
Computations for identifying icing conditions and for activating anti−ice systems the TAT is above 12C/53F
are performed in the ice detector. The message advises the crew to switch the respective system OFF.
L ICE DETECTOR
LEFT ICE DETECTOR PROBE PROBE, M6704
(R ICE DETECTOR PROBE,
NOTE:
____ LEFT ICE DETECTOR PROBE SHOWN, M6703 OPPOSITE)
RIGHT PROBE SIMILAR
ICE DETECTOR
PROBE
AIRPLANE
SKIN
For Training Purposes Only
MAGNETOSTRICTIVE
PROBE TIP
30 - 80 ICE DETECTION
ICE DETECTION SYSTEM FUNCTION DESCRIPTION
General Control
As ice builds up on the ice detector sensor element during flight, the resonant To activate the ice detection system, place the WING ANTI−ICE and NACELLE
frequency of the sensing element decreases. When a approximately 0.5 mm ANTI−ICE switches on the anti−ice−rain removal module in the AUTO position.
ice layer accumulates, the heater turns on to melt the ice. When the airplane is in the air, the wing and nacelle TAI systems will be auto-
matically activated when icing conditions are detected.
When the resonant frequency returns to its initial value, the heater turns off,
normally 7−8 seconds after it turns on. This process is repeated as long as Flight deck indication of icing conditions is performed automatically by the ice
icing conditions exist. detection system.
The ice detector keeps count of the number of icing/de−icing cycles of the
sensor element.
When two (2) consecutive probe icing/de−icing cycles are counted, the
detector outputs a signal to activate the engine anti−ice system for
180 10 seconds. If an additional icing/de−icing cycle occurs during this
time interval, the 180−second engine anti−ice activation period is begun
again.
− If it takes more than 15 seconds to melt the ice on the first icing/de−icing
cycle, the ice detector will activate the engine anti−ice system for
180 10 seconds without waiting for a second cycle.
When ten (10) consecutive probe icing/de−icing cycles are counted, the
detector outputs a signal to activate the wing anti−ice system for
180 10 seconds. If an additional icing/de−icing cycle occurs during this
time interval, the 180−second wing anti−ice activation period is begun
again.
For Training Purposes Only
115V AC
BUS 1 CONTROL
POWER DISPLAY
SUPPLY UNIT
LEFT ICE
DETECTOR
P 414 L 10
HEATER
FEEDBACK DRIVE COIL
COIL COIL
MAGNETOSTRICTIVE
PROBE
CENTRAL
GROUND TEST MAINTENANCE
COMPUTER
PROBE HEATER
OSCILATOR CONTROL
ÄÄÄÄÄÄÄÄÄ
ÄÄÄÄÄÄÄÄÄ
ÄÄÄÄ ÄÄÄÄÄ
NOTE :
ÄÄÄÄÄÄÄÄÄ
LEFT ICE DETECTOR SHOWN,
HEATER TIMER FAULT
RIGHT ICE DETECTOR SIMILAR. BUILT − IN
AND HEATER LOGIC OUTPUT
ÄÄÄÄÄÄÄÄÄ
CB : P 415 L 33 TEST
(CA. 7 SEC. ) LOGIC
ICE
DETECTION
FAIL OUTPUT EFIS/EICAS
INTERFACE
1& UNITS
>15sec.
For Training Purposes Only
TEST
General
This ground test does a check of the ice detector operation.
This ground test does not do a check of the wing thermal anti−ice
system or the engine inlet thermal anti−ice system.
For Training Purposes Only
ME N U
GROU N D T EST S 4/8
1L < F MC 1R
1L < 30 ICE AND RAIN 1R
2L 2R
2L < 31 INDICATING/WARNING 2R
3L 3R
3L < 31 RECORDING 3R
4L 4R
4L < 32 BRAKE CONTROL 4R
5L 5R
5L < 32 PSEU SYSTEM 5R
6L < C MC < A CT > 6R −−−−−−−−−−−−−−−−−−−−−−−−
6L < RE T URN HE L P > 6R
C MC ME N U 1/ 2 GR OU N D TESTS 1/ 1
LEFT RIGHT
WING THERMAL WING THERMAL
ANTI−ICE ANTI−ICE
VALVE VALVE
TO
AIR COND
PACK NO.1
LEFT
WING ISOLATION TO
VALVE AIR COND
PACK NO.3
TO
AIR COND
PACK NO.2
FROM RIGHT
GROUND WING ISOLATION
FROM VALVE
CONNECTORS
APU
MAIN
EICAS
WAI DISPLAY
ICE DETECTORS 0 28
WING
TAI WING
TAI ECS
WING ANTI−ICE SYNOPTIC
PAGE
SWITCH
CMCS MESSAGE (P5)
− WING ANTI−ICE LEFT VALVE FAIL EFIS/EICAS
− WING ANTI−ICE RIGHT VALVE FAIL INTERFACE ADVISORY MESSAGE :
UNITS − WAI VALVE LEFT
− WAI VALVE RIGHT
STATUS MESSAGE :
− ANTI−ICE WING L
− ANTI−ICE WING R
ON − Position AUTO
− causes both valves to move to OPEN if the airplane is in AIR.
AUTO − Position
AIR WTAI
− causes both valves to move to OPEN if VALVES
the airplane is in AIR ON OPEN
the 3 Flap Control Units (FCU’s) senses LE−Flap UP or FAIL.
any icing conditions is detected from the left and/or the right
ICE DETECTOR.
THERMAL
ANTI−ICE MODULE
P5
NACELLE ANTI−ICE
2 3
FLIGHT COMPARTMENT OFF
1 4
AUTO
ON
WING ANTI−ICE
AUTO
For Training Purposes Only
OFF ON
CLOSE
OPEN
V153 RIGHT WING
R7427 R7428 RIGHT TAI VALVE
RIGHT VALVE VALVE OPEN CLOSE
DISAGREE
115V AC
BUS 2
WING RIGHT
ANTI−ICE ICING
VLV
OPEN
V152 LEFT WING
TAI VALVE M6704 RIGHT
R7534
LEFT VALVE ICE DETECTOR
28V DC DISAGREE
BUS 2 M3414 DIODE LEFT
WING ICING
ANTI−ICE AIR
CONT
P6 MAIN POWER R7536 WING
DISTRIBUTION GND ANTI−ICE M3904 DIODE M3411 DIODE
PANEL M6703 LEFT
R227 AIR/ ICE DETECTOR
GROUND
R8327 FLAP
LOCKOUT 3 R8326 FLAP M7880 CENTER
LOCKOUT 2 R8325 FLAP M7888 LEFT FCU
LOCKOUT 1 FCU
T
LE GROUP
D E1−2 ELECTRONICS
A NOT RET
AUTO SHELF
R7776 WING
For Training Purposes Only
The pneumatic bleed air supply is routed to the leading edge of each wing Flight deck indication is performed automatically by the ice prevention system.
through control valves in the leading edge flap cavity near the outboard
engines. The valve is joined to a Y−type coupling which connects to two A ground test may be performed by selecting the wing anti−ice BITE test with
elbows. The elbows direct air to the main anti−ice ducts which run inboard the CMCS. When the test is initiated, the indication will come on while the
and outboard behind the leading edge. valve is opening and closing.
For Training Purposes Only
Each duct is rigidly mounted to the leading edge structure at the elbow and is
supported within the leading edge structure by heat resistant clamps. Cushions
on the clamps allow the duct to expand as it heats up. Spray holes along the
front of the duct direct the heated air throughout the leading edge surface. The
air then flows along the leading edge skin and is exhausted overboard through
drain slots in the bottom of the leading edge.
LEFT RIGHT
WING THERMAL WING THERMAL
ANTI−ICE ANTI−ICE
VALVE VALVE
TO
AIR COND
PACK NO.1
LEFT
WING ISOLATION TO
VALVE AIR COND
PACK NO.3
TO
AIR COND
PACK NO.2
FROM RIGHT
GROUND WING ISOLATION
FROM VALVE
CONNECTORS
APU
MAIN
EICAS
WAI DISPLAY
− GROUND TEST
− CMCS MESSAGES
− INPUT MONITORING CENTRAL ON DUCT DUCT
MAINT
COMPUTER OFF ON PSI PSI
For Training Purposes Only
VALVE 0 28
WING
WING ANTI−ICE TAI WING
TAI ECS
WING ANTI−ICE SYNOPTIC
PAGE
SWITCH
CMCS MESSAGE (P5)
− WING ANTI−ICE LEFT VALVE FAIL EFIS/EICAS
− WING ANTI−ICE RIGHT VALVE FAIL INTERFACE ADVISORY MESSAGE :
UNITS − WAI VALVE LEFT
− WAI VALVE RIGHT
STATUS MESSAGE :
− ANTI−ICE WING L
− ANTI−ICE WING R
The control switch is used to turn the wing anti ices ystem and/or the
ice detection system on and off.
AIR
ON − Position ON
OFF − Position
− causes both valves to move to CLOSE independently of the airplane
WTAI
is in AIR or on GND. VALVES
OPEN
GROUND
OFF 7 SEC
THERMAL
ANTI−ICE MODULE
P5
FLIGHT COMPARTMENT
NACELLE ANTI−ICE
2 3
1 4
ON ON
VALVE VALVE
ON ON
VALVE VALVE
For Training Purposes Only
ON
VALVE
WING ANTI−ICE
GROUND TEST :
for detailed information refer to ground test - Wing Thermal Anti-Ice.
WAI- (R 7536) and AUTO/TEST−Relay (R 7788) energized
WAI−Valves opens
after 7sec. the
− WAI-Time Delay Relay will be energized
− WAI − Relay (R 7536) will be deenergized
WAI-Valves closes.
For Training Purposes Only
OFF
ON
CLOSE
VALVE
MD&T
LIGHT
R7427
YMES5 WING RIGHT VALVE OPEN
ANTI−ICE DISAGREE
SWITCH
M7321 ANTI−ICE R7428 RIGHT V153 RIGHT WING
RAIN REMOVAL VALVE OPEN THERMAL ANTI−ICE
MODULE (P5) VALVE
R7534
LEFT VALVE
DISAGREE
115V AC
BUS 2
WING
ANTI−ICE AIR
VLV CLOSE
28V DC
BUS 2
WING GND R7536 WING
ANTI−ICE ANTI−ICE OPEN
R227 AIR/
CONT GROUND
P6 MAIN POWER V152 LEFT WING
DISTRIBUTION THERMAL ANTI−ICE
PANEL VALVE
T
D
M7373,M7374
CENTRAL
MAINTENANCE M7353 L EIU M7352 CTR EIU M7351 R EIU
COMPUTERS
E2−6 ELECTRONICS SHELF
E1−4 ELECTRONICS
SHELF
HI FLOW HI FLOW
1 2 3
DUCT DUCT
WING PSI
EXT AIR
PSI
THERMAL 0 28 WING
ANTI−ICE THERMAL
(INACTIVE) WING
TAI
WING ANTI−ICE
TAI
(ACTIVE)
APU
OFF
NAC NAC
TAI TAI
1 ENG 2 3 ENG 4
For Training Purposes Only
WING THERMAL ANTI-ICE VALVE WING THERMAL ANTI-ICE VALVE FAULT INDICATION
The flow of air into the wing anti−ice ducts from the engine pneumatic system If the valve position does not agree with the commanded switch position, the
is controlled by a 3−1/2−inch shutoff valve in each wing. EICAS advisory messages :
The butterfly type valve is driven open and closed by an internal electric mo- WAI VALVE LEFT
tor. WAI VALVE RIGHT
The valve has limit switches to prevent overtravel and valve position are displayed along with the status messages
switches for fault indication.
ANTI−ICE WING L
The valve has an external position indicator which shows the position of the
ANTI−ICE WING R
valve, and a handle which allows the valve to be operated manually.
The wing anti−ice valve opens and closes in less than 3 seconds.
The CMC provides the associated CMC Present Leg Fault/Existing Fault
Message visible on the MCDU:
WING ANTI − ICE RIGHT VALVE FAIL
WING ANTI − ICE LEFT VALVE FAIL
For Training Purposes Only
NOTE :
LEFT WING SIDE SHOWN,
RIGHT WING SIDE SIMILAR.
WING THERMAL
ANTI−ICE
CONTROL VALVE
WING PNEUMATIC
THERMAL MANIFOLD
ANTI−ICE
VALVE
LOCATION
MANUAL
VALVE
POSITION
BONDING INDICATOR
JUMPER
ELECTRICAL LEADING
CONNECTOR EDGE FLAP
ME N U
GR OU N D T ESTS 4/8
1L < F MC 1R
1L < 30 ICE AND RAIN 1R
2L 2R
2L < 31 INDICATING/WARNING 2R
3L 3R
3L < 31 RECORDING 3R
4L 4R
4L < 32 BRAKE CONTROL 4R
5L 5R
5L < 32 PSEU SYSTEM 5R
6L < C MC < A CT > 6R −−−−−−−−−−−−−−−−−−−−−−−−
6L < RE T URN HE L P > 6R
C MC ME N U 1/ 2 GR O U N D TESTS 1/ 1
TABLE OF CONTENTS
ATA 36 PNEUMATIC . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRESS REG VLV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
ENG DUCT PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
36-00 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 PRECOOLER OUT TEMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
AIR SUPPLY CONTROL TEST UNIT (ASCTU) . . . . . . . . . . . . . . . . . . . 4 ECS MAINTENANCE PAGE (AIR SUPPLY SYSTEM) . . . . . . . . . . . . . 20
FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FAN AIR VLV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
INPUT MONITORING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 STARTER VLV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
36−10 DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 PRESS REG S/O VLV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
BASIC SCHEMATIC DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 BLEED FLOW (OPTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
HIGH PRESSURE SHUT OFF VALVE (HPSOV) . . . . . . . . . . . . . . . . . 6 MANIFOLD DUCT PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
PRESSURE REGULATING VALVE (PRV) . . . . . . . . . . . . . . . . . . . . . . . 6 MAIN EICAS DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
FAN AIR MODULATING VALVE (FAMV) . . . . . . . . . . . . . . . . . . . . . . . . . 6 DUCT PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
BLEED AIR PRESSURE- AND TEMPERATURE SENSOR . . . . . . . . 6 ENGINE PERFORMANCE MAINTENANCE PAGE . . . . . . . . . . . . . . . 22
BLEED AIR OVERPRESSURE SWITCH (OPS) . . . . . . . . . . . . . . . . . . 6 DUCT PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
BLEED AIR OVERHEAT SWITCH (OHS) . . . . . . . . . . . . . . . . . . . . . . . . 6 ENGINE FIRE HANDLE SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
PRESSURE REGULATING AND SHUT OFF VALVE (PRSOV) . . . . . 8 ENGINE START SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
LEFT AND RIGHT WING ISOLATION VALVE . . . . . . . . . . . . . . . . . . . . 8 NACELLE ANTI-ICE SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
APU ISOLATION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 36 - 10 DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
AIR SUPPLY CONTROL TEST UNIT (ASCTU) . . . . . . . . . . . . . . . . . . . 8 PNEUMATIC DISTRIBUTION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . 26
DUCT PRESSURE SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 36−10 DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
PANEL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 HIGH PRESSURE SHUTOFF VALVE CONTROLLER (HPSOVC) . . 28
ENGINE BLEED AIR SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 HPSOV CONTROLLER FAULT INDICATION . . . . . . . . . . . . . . . . . . . . 28
SYSTEM FAULT−LIGHT (AMBER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 HIGH PRESSURE SHUTOFF VALVE (HPSOV) . . . . . . . . . . . . . . . . . . 30
LEFT AND RIGHT WING ISOLATION VALVE SWITCH . . . . . . . . . . . 12 HPSOV FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
APU ISOLATION VALVE SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 HPSOVC AND HPSOV FUNCTION DESCRIPTION . . . . . . . . . . . . . . 32
ECS SYNOPTIC PAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 HIGH PRESSURE SHUTOFF VALVE OPEN . . . . . . . . . . . . . . . . . . . . . 32
BLEED FLOW INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 HPSOV FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
ENGINE BLEED INDICATION (PRSOV STATUS SYMBOL) . . . . . . . 14 HPSOVC FAULT DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
BLEED ISOLATION VALVE STATUS SYMBOL . . . . . . . . . . . . . . . . . . . 14
MANIFOLD DUCT PRESSURE INDICATION . . . . . . . . . . . . . . . . . . . . 16 HPSOVC/HPSOV FUNCTION SUMMARY . . . . . . . . . . . . . . . . . . . . . . . 36
WING THERMAL ANTI-ICE INDICATION (WTAI) . . . . . . . . . . . . . . . . . 16 HPSOVC AND HPSOV SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
NACELLE ANTI−ICE INDICATION (NAI) . . . . . . . . . . . . . . . . . . . . . . . . 16 HPSOVC FAULT DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
EXTERNAL AIR INDICATION (EXT AIR) . . . . . . . . . . . . . . . . . . . . . . . . 16
ECS MAINTENANCE PAGE (AIR SUPPLY) . . . . . . . . . . . . . . . . . . . . . 18 HPSOV FAULT DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
HIGH PRESS CONT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 INTERMEDIATE PRESSURE CHECK VALVE
(IP-CHECK VALVE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
HIGH PRESS VLV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TABLE OF CONTENTS
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 BITE PRESSURE SWITCHES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
PRESSURE REGULATING VALVE CONTROLLER (PRVC) . . . . . . . . 42 PRESSURE REGULATING SHUTOFF VALVE (PRSOV) SCHEMATIC . . . .
PRV FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 74
PRESSURE REGULATING VALVE (PRV) . . . . . . . . . . . . . . . . . . . . . . . 44 WING ISOLATION VALVES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
PRV FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 WING ISOLATION VALVES INDICATION . . . . . . . . . . . . . . . . . . . . . . . . 76
PRESSURE REGULATING VALVE CONTROLLER (PRVC) AND PRES- WING ISOLATION VALVES FAULT INDICATION . . . . . . . . . . . . . . . . . 76
SURE REGULATING VALVE (PRV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 APU ISOLATION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
PRESSURE REGULATOR VALVE OPEN . . . . . . . . . . . . . . . . . . . . . . . 46
PRV FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 APU ISOLATION VALVES INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . 78
PRVC/PRV FUNCTION SUMMARY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 APU ISOLATION VALVES FAULT INDICATION . . . . . . . . . . . . . . . . . . 78
PRESSURE REGULATOR VALVE CONTROLLER (PRVC) AND PRES- APU CHECK VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
SURE REGULATOR VALVE (PRV) OPERATION . . . . . . . . . . . . . . . . . 52 PNEUMATIC GROUND AIR CONNECTORS (2) . . . . . . . . . . . . . . . . . . 82
PRV FAULT DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 WING ISOLATION VALVE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 84
FAN AIR TEMPERATURE SENSOR (FATS) . . . . . . . . . . . . . . . . . . . . . 54
FATS OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 WING ISOLATION VALVES INDICATION . . . . . . . . . . . . . . . . . . . . . . . . 84
FAN AIR SYSTEM FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . 54 WING ISOLATION VALVES FAULT INDICATION . . . . . . . . . . . . . . . . . 84
FAN AIR MODULATING VALVE (FAMV) . . . . . . . . . . . . . . . . . . . . . . . . . 56 APU ISOLATION VALVE OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . 86
FAMV FAULT DETECTION AND INDICATION . . . . . . . . . . . . . . . . . . . 56 APU ISOLATION VALVE INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . 86
FAN AIR SYSTEM FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . 56 APU ISOLATION VALVE FAULT INDICATION . . . . . . . . . . . . . . . . . . . . 86
FAN AIR TEMPERATURE SENSOR AND VALVE SCHEMATIC . . . . 58 AIR SUPPLY CONTROL TEST UNIT (ASCTU) . . . . . . . . . . . . . . . . . . . 88
FAN AIR MODULATING VALVE LOCKOUT . . . . . . . . . . . . . . . . . . . . . . 58 ASCTU OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
FAMV FAULT DETECTION AND INDICATION . . . . . . . . . . . . . . . . . . . 58 ASCTU FAULT INDICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
BLEED AIR PRECOOLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 INDICATION ON EICAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
PRESSURE REGULATING SHUTOFF VALVE (PRSOV) . . . . . . . . . . 62 CMCS INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
PRSOV OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 36 - 20 INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
PRSOV FAULT DETECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 MANIFOLD PRESSURE INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . 92
MANUAL OVERRIDE MANIFOLD PRESSURE INDICATION FAULT INDICATION . . . . . . . . 92
............................................................. 64 ENGINE BLEED AIR PRESSURE INDICATION . . . . . . . . . . . . . . . . . . 94
INDICATION AND WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 BLEED AIR PRESSURE SENSOR FAULT INDICATION . . . . . . . . . . . 94
PRSOV FAULT INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 BLEED AIR OVERPRESSURE SWITCH FAULT INDICATION . . . . . 94
MANUALLY OPERATE THE PRSOV . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 ENGINE BLEED AIR TEMPERATURE INDICATION . . . . . . . . . . . . . . 96
PRESSURE REGULATING SHUTOFF VALVE (PRSOV) . . . . . . . . . . 72 BLEED AIR TEMPERATURE SENSOR FAULT INDICATION . . . . . . . 96
PRSOV OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 BLEED AIR OVERTEMP SWITCH FAULT INDICATION . . . . . . . . . . . 96
PRSOV CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
36 - 20 INDICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
PRSOV REVERSE FLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
PNEUMATIC INDICATION CIRCUIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
TABLE OF CONTENTS
GROUND TEST − PNEUMATIC SYSTEM . . . . . . . . . . . . . . . . . . . . . . . 102
TABLE OF CONTENTS
TABLE OF FIGURES
Figure 12 Pneumatic Manifold System . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 42 Fan Air Temperature Sensor & Valve Schematic . . . . . 59
Figure 13 Air Supply Control Test Unit (ASCTU) . . . . . . . . . . . . . . . 5 Figure 43 BLEED AIR PRECOOLER . . . . . . . . . . . . . . . . . . . . . . . . 61
Figure 14 BASIC SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 44 PRESSURE REGULATING AND SHUTOFF VALVE ( PRSOV ) .
Figure 15 BASIC SCHEMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 63
Figure 16 Bleed Control Module (1) . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 45 PRESSURE REGULATING AND SHUTOFF VALVE ( PRSOV ) .
65
Figure 17 Bleed Control Module (1) . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 46 PRSOV Location & Details . . . . . . . . . . . . . . . . . . . . . . . . 67
Figure 18 ECS Synoptic Page (1) . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 47 PRSOV MANUAL OPERATION . . . . . . . . . . . . . . . . . . . . 69
Figure 19 ECS Synoptic Page (2) . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 48 PRSOV MONITORING AND INDICATION CIRCUT . . 70
Figure 20 ECS AIR SUPPLY Maintenance Page (1) . . . . . . . . . . . 19
Figure 49 PRESSURE REGULATOR AND SHUTOFF VALVE CONTROL
Figure 21 ECS AIR SUPPLY Maintenance Page (2) . . . . . . . . . . . 21 CIRCUIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Figure 22 EICAS Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Figure 50 PRESSURE REGULATING AND SHUTOFF VALVE SCHEMATIC
Figure 23 Panel Description (1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 73
Figure 24 ENGINE BLEED AIR SYSTEM COMPONENT OVERVIEW . . . . Figure 51 Pressure Regulating and Shut Off Valve Schematic . . . 75
27 Figure 52 WING ISOLATION VALVE . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 25 HIGH PRESSURE SHUTOFF VALVE CONTROLLER 29 Figure 53 APU ISOLATION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Figure 26 HIGH PRESSURE SHUTOFF VALVE . . . . . . . . . . . . . . . 31 Figure 54 APU CHECK VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Figure 27 HPSOV CONTROLLER AND −VALVE . . . . . . . . . . . . . . 33 Figure 55 3−Inch GROUND CONNECTION . . . . . . . . . . . . . . . . . . 83
Figure 28 HIGH PRESSURE SHUTOFF VALVE CONTROL CIRCUIT . . . . . Figure 56 Wing Isolation Valve Circuit . . . . . . . . . . . . . . . . . . . . . . . . 85
34
Figure 57 Apu Isolation Valve Circuit . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 29 HPSOV MONITORING AND INDICATION CIRCUIT . . 35
Figure 58 AIR SUPPLY CONTROL TEST UNIT (ASCTU) . . . . . . 89
Figure 30 HPSOV CONTROLLER AND −VALVE FUNKTIONS−SCHEMATIC
37 Figure 59 AIR SUPPLY CONTROL TEST UNIT (ASCTU) . . . . . . 91
Figure 31 HPSOVC & HPSOV Schematic . . . . . . . . . . . . . . . . . . . . 39 Figure 60 Manifold Duct Pressure Transmitter . . . . . . . . . . . . . . . . . 93
Figure 32 INTERMEDIATE PRESSURE CHECK VALVE . . . . . . . 41 Figure 61 EBA Pressure Sensor & Overpressure Switch . . . . . . . 95
Figure 33 PRESSURE REGULATING VALVE CONTROLLER ( PRVC ) . . . Figure 62 EBA Temperature Sensor & Overtemperature Switch . 97
43 Figure 63 Pneumatic Temperature Indication Circuit . . . . . . . . . . . 99
Figure 34 PRESSURE REGULATING VALVE ( PRV ) . . . . . . . . . . 45 Figure 64 Pneumatic Pressure Indication Circuit . . . . . . . . . . . . . . . 101
Figure 35 PRV CONTROLLER AND −VALVE SCHEMATIC . . . . . 47 Figure 65 Ground Test - Pneumatic System . . . . . . . . . . . . . . . . . . 103
Figure 36 PRESSURE REGULATOR CONTOL CIRCUIT . . . . . . 48 Figure 66 ICE DETECTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Figure 37 PRESSURE REGULATOR VALVE MONITORING AND INDICA- Figure 67 Ice Dection System Operation . . . . . . . . . . . . . . . . . . . . . 107
TION CIRCUIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Figure 68 GROUND TEST − ICE DETECTION SYSTEM . . . . . . . 109
Figure 38 HPSOV CONTROLLER AND −VALVE FUNKTIONS−SCHEMATIC Figure 69 Wing Thermal Anti−ice System . . . . . . . . . . . . . . . . . . . . . 111
51
Figure 70 Thermal Anti−ice Control Module . . . . . . . . . . . . . . . . . . . 113
Figure 39 PRVC AND PRV SCHEMATIC . . . . . . . . . . . . . . . . . . . . . 53
Figure 71 Wing Thermal Ant-ice Simplified Schematic . . . . . . . . . . 115
Figure 40 FAN AIR TEMPERATURE SENSOR ( FATS ) . . . . . . . 55
Figure 72 Wing Thermal Anti−ice System . . . . . . . . . . . . . . . . . . . . . 117
Figure 41 FAN AIR MODULATING VALVE ( FAMV ) . . . . . . . . . . . 57
Figure 73 THERMAL ANTI−ICE CONTROL MODULE . . . . . . . . . 119
TABLE OF FIGURES
Figure 74 WING THERMAL ANTI−ICE FUNCTION . . . . . . . . . . . . 121
Figure 75 Wing Thermal Anti−ice Indication . . . . . . . . . . . . . . . . . . . 123
Figure 76 Wing Thermal Anti−ice Valve . . . . . . . . . . . . . . . . . . . . . . 125
Figure 77 WTAIS Ground Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
TABLE OF FIGURES
TABLE OF FIGURES