You are on page 1of 4

COOLING TOWER

Dewi Permata Sari Binti Saiful Bahari (2019660264), Farah Aida Binti Md Azman (2019452304)

Abstract— Cooling tower are one type of heat exchanger. cooling are used. We can see that the cold water entered and
Thus, the purpose is to lower the temperature of hot water that distribute by using spray nozzles and the water vapors
are circulate throughout the cooling tower. From the process evaporates and flow upwards as a result from decreased
occurred, small volumes of water vapors will then evaporate
temperature of hot water. Besides, as nozzles are used to
which it will lowering the temperature of the hot water that
was being circulated throughout the cooling tower. For this
spray the water, it helps to slows water flow down and
equipment, two experiments were being held which are exposes the maximum amount of water surface area
experiment 1 and experiment 2. In experiment 1, the changes is possible which is packing for contact between air and water.
heater power at 0.5kW, 1.0kW and 1.5kW while water flow
rate 1LPM remains constant. From experiment, we determine However, common cooling towers cannot be used for all
the correspondence between cooling load and cooling range. In applications. As we all know, two types of cooling system
experiment 2, the changes is blower opening whether it full are available which are cross flow and counter flow cooling
open, partially opened or full closed while flow of water at tower. Differ interaction contact between of air and water
1LPM and heat power 1kW remains constant. Through the
are their key differences.
experiment, we investigate the effect of blower opening state on
wet bulb approach and pressure drop within the packing.

Keywords— Cooling Tower; open circuit; packing;


evaporative cooling; hot water; cooling load; cooling range;
blower; pressure drop; wet bulb

I. INTRODUCTION
Cooling towers is an example of heat exchangers that
available where water and air are interact with each other to
decrease temperature of hot water. As we mentioned earlier,
through this process, a small volumes of water vapors will
evaporate thus lowering the temperature of hot water
circulated in the cooling tower. In a simple words, cooling
tower cools down water that heat up from equipment and
other processes occurred. Figure 1 shows cooling tower
theoretical principles, it works based on evaporative
cooling’s principle.
Figure 2. Open Circuit cooling tower

Apart from that, packing or fill pack are important to


improve effectiveness of cooling tower. It provides enough
surface area towards evaporative cooling process. Types of
packing are also depending on purpose whether for
industrial or in lab scale. Some requirements are needed to
choose the suitable type of packing:

a) Process involved
b) Cooling Tower designs

In this laboratory experiment, we are experienced the open


circuit cooling tower as shown in Figure 2. Through open
circuit, there is no separation occurred in the loop cooling
Figure 1. Cooling Tower working principle system throughout process flow. This is because cooled
water only flows through process then returns back into
There are different types of cooling tower available. From cooling tower. This actions will repeated again where the
the illustration provided, the principles of evaporative
system increased temperature and flows of cold water again dependent on the factors to be able to verify water flow
for evaporative cooling. rates, water temperatures, airflow rate and inlet air relative
humidity.
II. OBJECTIVES
The working principle and performance of cooling tower is
1. To determine the correspondence between cooling load based on the thermodynamic property, inclusive of First
and cooling range. Law of Thermodynamic which is conversion of energy.
Conversion energy is defined as transferring energy into and
2. To investigate effect of blowing opening state on wet out of the unit operation. The first law of thermodynamics
bulb approach and pressure drop within the packing. also states that the differences in the internal energy of a
system, ΔU equals the heat transfer into the system Q, plus
3. To study the performance of cooling tower at the net work done on the system W (Openstax, 2012). This
manipulated variables such as cooling load and air velocity. forms an equation of the first law of thermodynamics,

ΔU=Q+W (equation 1)
III. THEORY
Cooling towers are an uncommon type of heat exchanger The specific enthalpy of compressed liquid is given by,
that permits water and air which allows a contact with each
other to achieve a lower temperature of water. At the same h = hf +v f (p − psat) (equation 2)
time, when small amount of water evaporates, it brings down
the temperature of the water within the cooling tower. The For the following relationship, it is for the cooling tower
impact of evaporation is important where cooling takes place unit:
and acts as water particles. The water particles are
continuously replaced by others within the fluid. The hot Δh = CpΔT (equation 4)
water is usually caused by air conditioning condensers or and
other mechanical forms (Cooling Tower Products, 2018). h = CpT (equation 5)
The water is cooled by means of two processes: conduction Where Cp = 4.18 kJ.kg-1
and evaporation.
Evaporation essentially happens from a wet surface into the IV. PROCEDURES
surrounding air. The equilibrium temperature is the "wet
bulb temperature" under adiabatic conditions. With an General start-up procedures
adequate air flow, the water that leaves the system will be the
wet bulb temperature. Therefore, this shows effectiveness of 1. V1 and V6 valves was inspected to make sure that
the cooling of the tower. Moreover, an important parameter these valves were closed and v7 valve was slightly
of cooling towers which is the approaching to wet bulb open.
shows the difference between the temperature outlet and the 2. Deionised water or distilled water are used to fill
temperature inlet of air. The psychometric chart can give out the load tank in the cooling tower instrument. It is
information such as the specific enthalpy, specific volume, done by pouring the water in the load tank after
humidity ratio and relative humidity. taking out the make-up tank first. Then the make-
up tank was filled up until it reach the zero mark at
the water scale after replacing it bank onto the load
tank and the bulb has been tighten.
3. The wet bulb sensor reservoir were filled with
distilled water or deionised water until it full.
4. Each deferential pressure sensor was attach to the
proper tubing.
5. In this experiment. Suitable cooling tower packing
were used.
6. The set point in temperature for this experiment
temperature was 50°C. The water heater with the
power of 1kW was on and the water were heated
up until the temperature was estimate reaching
40°C.
7. After switching on the pump, control valve (V1)
Figure 3. shows the sample of psychometric chart was slowly open until it reach 2.0 LPM. The water
flow uniformly through and steady operation was
The effect of these factors is essential in the operation of achieved.
cooling tower. The performance of a cooling tower shall be
8. The fan damper was completely open and the
blower was turn on. The orifice differential
pressure was measure by checking the differential V. RESULTS AND DISCUSSIONS
pressure sensor reading when the valve manifold.
9. The level of water in the load tank was adjust by
the float valve after letting the unit run for 20
minutes. The makeup tank was filled if needed.
10. The cooling tower is ready to use.
Experiment 1 : To determine the correspondence between
cooling load and cooling range. CONCLUSION
1. The cooling tower has been started up according to
the start-up procedure that has been prepared. Write a concise statement summarizing the results.
2. The water flow rate has been set to 1.0 LPM. The Accurately answers objective.
power was set to 0.5 kW using column A and the
blower’s opening is fully opened. The system was
allowed to stabilize for 10 minutes.
3. The data needed for the experiment have been RECOMMENDATIONS
recorded after the 10 minutes passed. The data that
Concise recommendations and closely relevant to the
were required in this experiment were T1 (°C),
experimental procedures must be included.
T2(°C), T3(°C), T4(°C), T5(°C), T6(°C),
differential pressure orifice (Pa), differential
References
pressure column (Pa) and heater power (kW)
[1] Kurnik, C. W., Boyd, B., Stoughton, K. M., & Lewis, T.
4. The power for the system is set to 1.0 kW after
(2017). Cooling Tower (Evaporative Cooling
obtaining the data without changing the systems
System) Measurement and Verification Protocol.
settings.
doi: 10.2172/1412805
5. The experiment was repeated for 1.5 kW.
[2] COOLING TOWER PACKING – ALL YOU NEED TO
Experiment 2 : To investigate the effect of blower opening KNOW. (2020, January 13). Retrieved from
state on wet bulb approach and pressure drop within the https://www.vistechcooling.co.uk/vistech-industrial-
packing. services/cooling-tower-packing-all-you-need-to-
1. The cooling tower condition has been retained know/
from experiment. [3] How Cooling Towers Work (W/ Diagram, Pictures &
2. The only condition that being change was heater Principles) 2018. (n.d.). Retrieved from
power to 1.0 kW. https://www.coolingtowerproducts.com/blog/how-
3. After 10 minutes for the system to stabilize with cooling-towers-work-diagram-pictures-
blower’s opening fully opened, the required data 2015.htm#14
has been recorded. The data that were required in [4] Cooling Tower Products. (2018). HOW COOLING
this experiment were T1 (°C), T2(°C), T3(°C), TOWERS WORK (W/ DIAGRAM, PICTURES &
T4(°C), T5(°C), T6(°C), differential pressure PRINCIPLES) 2018. Retrieved from
orifice (Pa) and differential pressure column (Pa) coolingtowerproducts.com:
4. The experiment were repeated with different https://www.coolingtowerproducts.com/blog/how-cooling
blower’s opening, partially opened and fully towers-work-diagram-pictures-2015.htm#1
closed. [5] OpenStax, The First Law of Thermodynamics.
OpenStax CNX. Aug 19, 2014
General shut-down procedures. http://cnx.org/contents/fb11b483-b85f-4cda-bec7-
1. After switching off the heater, the remaining water 4dfd136dba60@7.
in the cooling tower were left to circulate through
the system for about three to five minutes until the
temperature decrease.
2. The blower was off and the fan damper was
completely closed.
3. The pump and power supply were turn off.
4. Water in the tank were reserve for the next
experiment.
5. If it was not used, the water were drain off from the
tank.
APPENDIX

Additional information in appendices extracted from


resources cited in references, concise and closely related to
the experiment. Raw data recorded can be included here.

You might also like