PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 16F - 1 (3-Phase)


FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER
1 R1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATHROOM 2 4 4 6 7 3 2 26 13 50 18 3 7 50 554

2 Y1 6 1.5 1.5 KITCHEN + MAID'S + PASSAGE+ LIVING/DINING 4 2 2 5 1 1 18 /72 /100 /7 /36 /3 490
3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500
7 R3 30 6.0 6.0 COOKER 1 3000 3000

8 Y3 10 SPARE 0

9 B3 10 SPARE

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 30 6.0 6.0 LIVING DINING 7 200 1400 RING CIRCUIT

63A 3P 12 B4 20 4.0 4.0 BEDROOM 5 200 1000


ISOLATOR 13 R5 20 4.0 4.0 ACP 1 200 200
14 Y5 30 6.0 6.0 MASTER BEDROOM 8 200 1600 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE + MAID'S 5 200 1000


16 R6 20 SPARE
40A 4P
30 mA 17 Y6 20 4.0 4.0 KITCHEN 1 1500 1500
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500

19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1500

21 B7 20 4.0 4.0 MAID'S BATH 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1500


23 Y8 20 SPARE

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8254 6990 7500 22.7


CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet
W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-1


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 16F - 2 (3-Phase)


FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER
1 R1 6 1.5 1.5 KITCHEN + MAID'S + PASSAGE+ LIVING/DINING + FOYER 2 1 5 3 2 1 2 36 36 8 13 3 18 100 411

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM 4 3 2 6 6 1 2 2 13 52 13 18 3 28 18 50 524


3 B1 10 2.5 2.5 0

4 R2 10 2.5 2.5 FCU-1 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-2 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-3 1 500 500
7 R3 10 2.5 2.5 FCU-4 1 500 500

8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE

10 R4 20 4.0 4.0 KITCHEN 7 200 1400

11 Y4 30 6.0 6.0 LIVING DINING 7 200 1400

63A 3P 12 B4 20 4.0 4.0 BEDROOM 5 200 1000


ISOLATOR 13 R5 20 4.0 4.0 ACP 1 200 200
14 Y5 30 6.0 6.0 MASTER BEDROOM 8 200 1600

15 B5 20 4.0 4.0 PASSAGE + MAID'S 5 200 1000


16 R6 20 4.0 4.0 LAUNDRY 1 1500 1500
40A 4P
30 mA 17 Y6 20 4.0 4.0 KITCHEN 1 1500 1500
RCD
18 B6 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1500

19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1500

20 Y7 20 SPARE

21 B7 20 4.0 4.0 MAID'S BATH 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1500


23 Y8 20 SPARE

24 B8 20 4.0 4.0 G. TOILET 1 1500 1500

TOTAL 7511 8524 7000


CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet
W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-2


REMARKS

RING CIRCUIT

RING CIRCUIT

23.0

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-2


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 16F- 3 (3-Phase)

FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5 KITCHEN + MAID'S + PASSAGE+ LIVING/DINING 8 4 1 2 2 2 1 3 8 13 36 36 18 3 18 100 584

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM 4 3 3 5 4 2 1 2 13 52 13 18 3 28 13 50 518


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 SPARE -

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 4.0 4.0 ACP 2 200 400

63A 3P 12 B4 30 6.0 6.0 BEDROOM 7 200 1400 RING CIRCUIT


ISOLATOR 13 R5 30 6.0 6.0 LIVING DINING 8 200 1600 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 7 200 1400 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE + MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 SPARE 1500 -
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 4.0 4.0 LAUNDRY 1 1500 -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8584 7318 7400 23.302

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-3


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 16F - 4 (3-Phase)

FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5 KITCHEN + MAID'S + PASSAGE+ LIVING/DINING 2 6 6 2 3 1 2 36 8 13 18 3 18 100 461

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM 4 4 4 3 4 2 52 18 3 28 13 50 528


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 4.0 4.0 ACP 2 200 400

63A 3P 12 B4 20 4.0 4.0 BEDROOM 5 200 1000


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 6 200 1200 RING CIRCUIT

14 Y5 20 4.0 4.0 PASSAGE 4 200 800

15 B5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT

16 R6 20 4.0 4.0 BEDROOM BATH 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 MAID'S TOILET 1 1500 1500
RCD
18 B6 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1500
19 R7 20 4.0 4.0 G. TOILET 1 1500 1,500

20 Y7 20 4.0 4.0 KITCHEN 1 1500 1,500


21 B7 20 4.0 4.0 LAUNDRY 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 SPARE -

TOTAL 7661 8228 6200 22.089

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-4


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 16F -5 (3-Phase)

FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING4 6 3 2 3 2 36 8 13 18 3 100 476

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ PASSAGE 3 2 1 3 4 3 2 6 2 8 28 18 13 13 52 18 3 50 499


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 SPARE 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 20 4.0 4.0 MASTER BEDROOM 4 200 800

15 B5 30 6.0 6.0 PASSAGE& MAID'S 7 200 1400 RING CIRCUIT

16 R6 20 4.0 4.0 ACP 2 200 400


40A 4P
30 mA 17 Y6 20 4.0 4.0 KITCHEN 1 1500 1500
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE 1500 -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 7176 7799 7700 22.675

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-5


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 16F - 6 (3-Phase)

FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5 KITCHEN + MAID'S + PASSAGE+ LIVING/DINING 2 3 2 5 2 36 18 3 8 100 372

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ PASSAGE 4 3 2 3 2 2 2 13 18 3 28 52 13 50 426


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 SPARE 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 8 200 1600 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 SPARE -
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE 1500 -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 7772 7026 7300 22.098

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-6


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 16F - 7 (3-Phase)

FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING 2 2 3 5 2 100 52 18 8 3 404

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ PASSAGE 2 4 11 5 3 5 2 52 11 18 50 7 3 50 732


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 4.0 4.0 ACP 2 200 400

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 7 200 1400 RING CIRCUIT

15 B5 30 6.0 6.0 PASSAGE& MAID'S 6 200 1200 RING CIRCUIT

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 SPARE -
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 SPARE MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 SPARE MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 7804 7532 7500 22.836

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-16F-7


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 26F - 1 (3-Phase)

FED FROM: SMDB-26F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5MASTER BEDROOM + BEDROOM+ BATHROOM3 6 5 7 9 3 52 11 28 18 3 50 665

2 Y1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 2 5 1 6 52 100 18 30 7 466


3 B1 10 SPARE -

4 R2 10 2.5 2.5 FCU-1 1 500 500

5 Y2 10 2.5 2.5 FCU-2 1 500 500


40A 4P 6 B2 10 2.5 2.5 FCU-3 1 500 500
100 mA
RCD 7 R3 10 2.5 2.5 FCU-4 1 500 500
8 Y3 10 SPARE . -

9 B3 10 2.5 2.5 FCU-5 1 500 500


10 R4 10 SPARE

11 Y4 30 6.0 6.0 COOKER 1 3000 3000


12 B4 10 SPARE -

13 R5 20 4.0 4.0 KITCHEN 4 200 800


63A 3P
14 Y5 20 4.0 4.0 BEDROOM 2 5 200 1000
ISOLATOR
15 B5 20 4.0 4.0 BEDROOM 1 5 200 1000

16 R6 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

17 Y6 30 6.0 6.0 MASTER BEDROOM 5 200 1000 RING CIRCUIT

18 B6 30 6.0 6.0 PASSAGE& MAID'S 5 200 1000 RING CIRCUIT


19 R7 20 4.0 4.0 KITCHEN 1 1500 1500
40A 4P
30 mA 20 Y7 20 4.0 4.0 BEDROOM 2 BATH 1 1500 1500
RCD
21 B7 20 4.0 4.0 G. TOILET 1 1500 1500

22 R8 20 4.0 4.0 BEDROOM 1 BATH 1 1500 1,500


23 Y8 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500

24 B8 20 4.0 4.0 MAID'S TOILET 1 1500 1500

25 R9 20 4.0 4.0 KITCHEN 1 1500 1,500

26 Y9 20 SPARE -

27 B9 20 4.0 4.0 LAUNDRY 1 1500 1500


TOTAL 8365 8966 7500 24.831

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet
W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-26F-1


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 26F - 2 (3-Phase)

FED FROM: SMDB-26F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING1 6 2 4 52 8 100 18 372

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 2 4 4 2 3 2 52 13 30 8 18 50 446


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 2.5 2.5 FCU-5 1 500 500


8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 5 200 1000


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 6 200 1200 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 4 200 800 RING CIRCUIT

15 B5 30 6.0 6.0 PASSAGE& MAID'S 4 200 800 RING CIRCUIT

16 R6 20 4.0 4.0 ACP 2 200 400


40A 4P
30 mA 17 Y6 20 SPARE KITCHEN 1 1500 1500
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 SPARE MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 SPARE MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 6972 7746 7300 22.018

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-26F-2


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 26F - 3 (3-Phase)

FED FROM: SMDB-26F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 8 4 1 3 52 8 18 30 100 570

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 3 4 4 8 1 2 100 52 11 18 30 50 826


3 B1 10 1.5 1.5 500 -

4 R2 10 2.5 2.5 FCU-1 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-2 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-3 1 500 500

7 R3 10 SPARE 500 -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 30 6.0 6.0 BEDROOM 7 200 1400 RING CIRCUIT


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 7 200 1400 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8370 7626 7400 23.396

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-26F-3


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 26F - 4 (3-Phase)

FED FROM: SMDB-26F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 6 2 2 1 52 18 100 3 18 436

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 4 4 3 4 2 4 2 52 11 50 18 8 3 50 602


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 ### 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 SPARE -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 4 200 800

16 R6 20 4.0 4.0 KITCHEN 1 ### 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 ### 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 ### 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 ### 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 ### 1500

22 R8 20 4.0 4.0 KITCHEN 1 ### 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 ### 1500

TOTAL 8236 7202 7100 22.538

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-26F-4


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 26F - 5 (3-Phase)

FED FROM: SMDB-26F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 2 4 5 4 52 100 18 8 3 428

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 3 4 5 3 5 2 2 52 11 18 8 3 50 50 529


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 8 200 1600 RING CIRCUIT

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 30 6.0 6.0 BEDROOM 7 200 1400 RING CIRCUIT


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 7 200 1400 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8428 7329 7900 23.657

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-26F-5


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 26F - 6 (3-Phase)

FED FROM: SMDB-26F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 5 5 2 3 52 18 8 100 3 443

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 2 4 6 3 2 52 11 18 50 50 506


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 SPARE 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 7843 7106 7300 22.249

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-26F-6


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 27F - 1 (3-Phase)

FED FROM: SMDB-27F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5MASTER BEDROOM + BEDROOM+ BATHROOM3 6 5 7 9 3 52 11 28 18 3 50 665

2 Y1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 2 5 1 6 52 100 18 30 7 466


3 B1 10 1.5 1.5 -

4 R2 10 2.5 2.5 FCU-1 1 500 500

5 Y2 10 2.5 2.5 FCU-2 1 500 500


40A 4P 6 B2 10 2.5 2.5 FCU-3 1 500 500
100 mA
RCD 7 R3 10 2.5 2.5 FCU-4 1 500 500
8 Y3 10 SPARE -

9 B3 10 2.5 2.5 FCU-5 1 500 500


10 R4 10 2.5 2.5

11 Y4 30 6.0 6.0 COOKER 1 3000 3000


12 B4 10 SPARE -

13 R5 20 4.0 4.0 KITCHEN 5 200 1000


63A 3P
14 Y5 20 4.0 4.0 BEDROOM 2 5 200 1000
ISOLATOR
15 B5 20 4.0 4.0 BEDROOM 1 5 200 1000

16 R6 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

17 Y6 30 6.0 6.0 MASTER BEDROOM 8 200 1600 RING CIRCUIT

18 B6 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000


19 R7 20 4.0 4.0 KITCHEN 1 1500 1500
40A 4P
30 mA 20 Y7 20 4.0 4.0 BEDROOM 2 BATH 1 1500 1500
RCD
21 B7 20 4.0 4.0 G. TOILET 1 1500 1500

22 R8 20 4.0 4.0 BEDROOM 1 BATH 1 1500 1,500


23 Y8 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500

24 B8 20 4.0 4.0 MAID'S TOILET 1 1500 1500

25 R9 20 4.0 4.0 KITCHEN 1 1500 1,500

26 Y9 20 SPARE -

27 B9 20 4.0 4.0 LAUNDRY 1 1500 1500


TOTAL 8565 9566 7500 25.631

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet
W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-27F-1


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 27F - 2 (3-Phase)

FED FROM: SMDB-27F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING1 6 2 4 52 8 100 18 372

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 2 4 4 2 3 2 52 13 30 8 18 /50 446


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 2.5 2.5 FCU-5 1 500 500


8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 5 200 1000


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 6 200 1200 RING CIRCUIT

14 Y5 20 4.0 4.0 MASTER BEDROOM 4 200 800

15 B5 20 4.0 4.0 PASSAGE& MAID'S 4 200 800

16 R6 20 4.0 4.0 ACP 2 200 400


40A 4P
30 mA 17 Y6 20 SPARE KITCHEN 1 1500 1500
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 SPARE MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 SPARE MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 6972 7746 7300 22.018

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-27F-2


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 27F - 3 (3-Phase)

FED FROM: SMDB-27F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 8 4 1 3 52 8 18 30 100 570

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 3 4 4 8 1 2 100 52 11 18 30 50 826


3 B1 10 2.5 2.5 500 -

4 R2 10 2.5 2.5 FCU-1 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-2 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-3 1 500 500

7 R3 10 SPARE 500 -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 30 6.0 6.0 BEDROOM 7 200 1400 RING CIRCUIT


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 7 200 1400 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8370 7626 7400 23.396

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-27F-3


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 27F - 4 (3-Phase)

FED FROM: SMDB-27F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 6 2 2 1 52 18 100 3 18 436

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 4 4 3 4 2 4 2 52 11 50 18 8 3 50 602


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 SPARE -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 4 200 800

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8236 7202 7100 22.538

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-27F-4


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 27F - 5 (3-Phase)

FED FROM: SMDB-27F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 2 4 5 4 52 100 18 8 3 428

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 3 4 5 3 5 2 2 52 11 18 8 3 50 50 529


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 9 200 1800 RING CIRCUIT

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 8 200 1600 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8628 7529 7300 23.457

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-27F-5


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 26F - 6 (3-Phase)

FED FROM: SMDB-26F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 5 5 2 3 52 18 8 100 3 443

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 2 4 6 3 2 52 11 18 50 50 506


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 -
40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-2 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-3 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 SPARE 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 7343 7106 7300 21.749

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-27F-6


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 28F - 1 (3-Phase)

FED FROM: SMDB-28F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5MASTER BEDROOM + BEDROOM+ BATHROOM3 6 5 7 9 3 52 11 28 18 3 50 665

2 Y1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 2 5 1 6 52 100 18 30 7 466


3 B1 10 1.5 1.5 -

4 R2 10 2.5 2.5 FCU-1 1 500 500

5 Y2 10 2.5 2.5 FCU-2 1 500 500


40A 4P 6 B2 10 2.5 2.5 FCU-3 1 500 500
100 mA
RCD 7 R3 10 2.5 2.5 FCU-4 1 500 500
8 Y3 10 SPARE -

9 B3 10 2.5 2.5 FCU-5 1 500 500


10 R4 10 2.5 2.5

11 Y4 30 6.0 6.0 COOKER 1 3000 3000


12 B4 10 SPARE -

13 R5 20 4.0 4.0 KITCHEN 5 200 1000


63A 3P
14 Y5 20 4.0 4.0 BEDROOM 2 5 200 1000
ISOLATOR
15 B5 20 4.0 4.0 BEDROOM 1 5 200 1000

16 R6 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

17 Y6 30 6.0 6.0 MASTER BEDROOM 8 200 1600 RING CIRCUIT

18 B6 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000


19 R7 20 4.0 4.0 KITCHEN 1 1500 1500
40A 4P
30 mA 20 Y7 20 4.0 4.0 BEDROOM 2 BATH 1 1500 1500
RCD
21 B7 20 4.0 4.0 G. TOILET 1 1500 1500

22 R8 20 4.0 4.0 BEDROOM 1 BATH 1 1500 1,500


23 Y8 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500

24 B8 20 4.0 4.0 MAID'S TOILET 1 1500 1500

25 R9 20 4.0 4.0 KITCHEN 1 1500 1,500

26 Y9 20 SPARE -

27 B9 20 4.0 4.0 LAUNDRY 1 1500 1500


TOTAL 8565 9566 7500 25.631

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet
W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-28F-1


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 28F - 2 (3-Phase)

FED FROM: SMDB-28F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING1 6 2 4 52 8 100 18 372

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 2 4 4 2 3 2 52 13 30 8 18 50 446


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 2.5 2.5 FCU-5 1 500 500


8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 5 200 1000


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 6 200 1200 RING CIRCUIT

14 Y5 20 4.0 4.0 MASTER BEDROOM 4 200 800

15 B5 20 4.0 4.0 PASSAGE& MAID'S 4 200 800

16 R6 20 4.0 4.0 ACP 2 200 400


40A 4P
30 mA 17 Y6 20 SPARE KITCHEN 1 1500 1500
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 SPARE MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 SPARE MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 6972 7746 7300 22.018

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-28F-2


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 28F - 3 (3-Phase)

FED FROM: SMDB-28F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 8 4 1 3 52 8 18 30 100 570

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 3 4 4 8 1 2 100 52 11 18 30 50 826


3 B1 10 1.5 1.5 500 -

4 R2 10 2.5 2.5 FCU-1 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-2 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-3 1 500 500

7 R3 10 SPARE 500 -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 7 200 1400 RING CIRCUIT


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 7 200 1400 RING CIRCUIT

15 B5 30 6.0 6.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8370 7626 7400 23.396

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-28F-3


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 28F - 4 (3-Phase)

FED FROM: SMDB-28F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 6 2 2 1 52 18 100 3 18 436

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 4 4 3 4 2 4 2 52 11 50 18 8 3 /50 602


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 20 SPARE -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 4 200 800

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8236 7202 7100 22.538

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-28F-4


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 28F - 5 (3-Phase)

FED FROM: SMDB-28F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 2 4 5 4 52 100 18 8 3 428

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 3 4 5 3 5 2 2 52 11 18 8 3 50 50 529


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 30 6.0 6.0 KITCHEN 9 200 1800 RING CIRCUIT

11 Y4 20 4.0 4.0 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 7 200 1400 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 8628 7329 7300 23.257

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-28F-5


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 28F - 6 (3-Phase)

FED FROM: SMDB-28F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5KITCHEN + MAID'S + PASSAGE+ LIVING/DINING2 5 5 2 3 52 18 8 100 3 443

2 Y1 6 1.5 1.5 MASTER BEDROOM + BEDROOM+ BATH 2 4 6 3 2 52 11 18 50 50 506


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 SPARE -
40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-2 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-3 1 500 500

7 R3 10 SPARE -
8 Y3 30 6.0 6.0 COOKER 1 3000 3000

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 5 200 1000

11 Y4 20 SPARE 200 -

63A 3P 12 B4 20 4.0 4.0 BEDROOM 4 200 800


ISOLATOR 13 R5 30 6.0 6.0 LIVING/DINING 7 200 1400 RING CIRCUIT

14 Y5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT

15 B5 20 4.0 4.0 PASSAGE& MAID'S 5 200 1000

16 R6 20 4.0 4.0 KITCHEN 1 1500 1500


40A 4P
30 mA 17 Y6 20 4.0 4.0 ACP 2 200 400
RCD
18 B6 20 4.0 4.0 G. TOILET 1 1500 1500
19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1,500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 4.0 4.0 MAID'S TOILET 1 1500 1500

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 SPARE -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 7343 7106 7300 21.749

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-28F-6


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 2B - 7 (3-Phase)

FED FROM: SMDB-30

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5 52 8 11 36

2 Y1 6 1.5 1.5 11 /52 /11


3 B1 10 2.5 2.5 500 -

4 R2 10 2.5 2.5 FCU-1 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-2 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-3 1 500 500

7 R3 10 2.5 2.5 FCU-4 1 500 500

8 Y3 10 2.5 2.5 FCU-5 1 500 500


9 B3 10 2.5 2.5 FCU-6 1 500 500

10 R4 20 SPARE

11 Y4 30 6.0 6.0 COOKER 1 3000 3000

12 B4 20 SPARE

13 R5 6.0 6.0 LIVING DINING 200 - RING CIRCUIT


14 Y5 30 6.0 6.0 KITCHEN 200 - RING CIRCUIT

15 B5 30 6.0 6.0 BEDROOM 1 200 - RING CIRCUIT


63A 3P
ISOLATOR 16 R6 20 4.0 4.0 BEDROOM 2 200 -

17 Y6 20 SPARE MASTER BEDROOM 200 1500


18 B6 20 4.0 4.0 FAMILY SITTING 200 1500

19 R7 20 4.0 4.0 PASSAGE & MAID 200 1,500


40A 4P
30 mA 20 Y7 20 4.0 4.0 KITCHEN 1 1500 1,500
RCD
21 B7 20 4.0 4.0 BEDROOM 2 BATH 1 1500 1500

22 R8 20 4.0 4.0 G. TOILET 1 1500 1,500


23 Y8 20 4.0 4.0 BEDROOM 1 BATH 1 1500 -

24 B8 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1500


25 R9 20 4.0 4.0 MAID'S TOILET 1 1500 1,500

26 Y9 20 4.0 4.0 ACP 2 200 400


27 B9 20 4.0 4.0 KITCHEN 1 1500 1500
25 R10 20 4.0 4.0 LAUNDRY 1 1500 1500
26 Y10 20 4.0 4.0

27 B10 20 4.0 4.0

1500 7000 7400 7000 21.4


TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

7.00 7.40 7.00

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-28-7 (29-)


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 2B-1 (3-Phase)

FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5 8 11 52 36 0
2 Y1 6 1.5 1.5 11 /52 /11 /28 /8 0

3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500
7 R3 30 6.0 6.0 COOKER 1 3000 3000

8 Y3 10 SPARE
9 B3 10 SPARE

10 R4 20 4.0 4.0 KITCHEN 5 200 1000


11 Y4 30 6.0 6.0 LIVING DINING 7 200 1400 RING CIRCUIT

12 B4 20 4.0 4.0 BEDROOM 5 200 1000


13 R5 20 4.0 4.0 ACP 2 200 400
63A 3P
14 Y5 30 6.0 6.0 MASTER BEDROOM 8 200 1600 RING CIRCUIT
ISOLATOR
15 B5 20 4.0 4.0 PASSAGE + MAID'S 5 200 1000

16 R6 20 SPARE
40A 4P
30 mA 17 Y6 20 4.0 4.0 KITCHEN 1 1500 1500
RCD
18 B6 20 4.0 4.0 G-TOILET 1 1500 1500

19 R7 20 4.0 4.0 BEDROOM BATH 1 1500 1500

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1500

21 B7 20 4.0 4.0 MAID'S BATH 1 1500 1500


22 R8 20 4.0 4.0 KITCHEN 1 1500 1500

23 Y8 20 4.0 4.0 ALL BATHROOMS 5 /4 2 3 /18 /50 187

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 7900 6687 7500 22.1


CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-2B-1


PROJECT: Apartment Tower, Burj Khalifa LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB - 2B-2 (3-Phase)

FED FROM: SMDB-16F

CCT ECC CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. SPUR 13 A 15 A ELEC. W / UNIT REMARKS
INCOMER No. No. SIZE SIZE LTG W/H FCU BELL W/M D/W R Y B
RCCB IN A
mm² mm² SO FAN S/O S/O S/O COOKER

1 R1 6 1.5 1.5 52 8 11 36 -

2 Y1 6 1.5 1.5 11 /52 /11 -


3 B1 10 2.5 2.5 FCU-1 1 500 500

4 R2 10 2.5 2.5 FCU-2 1 500 500


40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU-3 1 500 500
RCD
6 B2 10 2.5 2.5 FCU-4 1 500 500

7 R3 30 6.0 6.0 COOKER 1 3000 3000


8 Y3 10 SPARE -

9 B3 10 SPARE -

10 R4 20 4.0 4.0 KITCHEN 7 200 1400 RING CIRCUIT

11 Y4 30 6.0 6.0 LIVING DINING 6 200 1200 RING CIRCUIT

63A 3P 12 B4 20 4.0 4.0 BEDROOM 6 200 1200 RING CIRCUIT


ISOLATOR 13 R5 20 SPARE -
40A 4P
30 mA 14 Y5 30 6.0 6.0 MASTER BEDROOM 6 200 1200 RING CIRCUIT
RCD
15 B5 20 4.0 4.0 PASSAGE + MAID'S 5 200 1000

16 R6 20 SPARE
17 Y6 20 4.0 4.0 KITCHEN 1 1500 1500

18 B6 20 4.0 4.0 G-TOILET 1 1500 1500


19 R7 20 SPARE -

20 Y7 20 4.0 4.0 MASTER BEDROOM BATH 1 1500 1,500


21 B7 20 SPARE -

22 R8 20 4.0 4.0 KITCHEN 1 1500 1,500


23 Y8 20 4.0 4.0 ALL BATHROOMS 3 /18 /50 -

24 B8 20 4.0 4.0 LAUNDRY 1 1500 1500

TOTAL 6400 5900 6200 18.5

TOTAL CONNECTED LOAD:

CABLE SIZE: 4Core 16 mm2 CU. XLPE/PVC + 1 x 1C 16mm2 CU.G/Y PVC, ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.

X:\6_Design Docs\6_Schedules\2_Elec\DB-Rev-Apr-02\483390290.xlsx07/11/2020 - DB-2B-2


MAIN DISTRIBUTION BOARD DETAILS OF CONNECTED LOAD / MAX. DEMAND

4B + G + 15 TYP. + ROOF Commercial and CONSULTANT:


PROJECT :
Residential Building
CLIENT : M/S BU HALEEBA MEP CONTRACTOR
NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB : MDB-03 AREA : Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM : TX-03 PLOT : 1341040 P.O.Box 233237 Dubai – UAE
LOCATION : G.F - LV ROOM
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE ECC CONNECTED LOAD - KW PROPOSED TYPE & No. OF KWH
FEEDER SP/ DUTY 2/4x1C 2/3/4C SIZE MAX METERS
WAY NO. R Phase Y Phase B Phase TOTAL LOAD ACTUAL LOAD STAND BY DEMAND
DEMAND
DB NO. TP ACB MCCB MCB IN kA SWA / PVC in mm2 in mm2 in mm2 IN kW IN kW LOAD kW LOAD IN kW FACTOR (1) (2) (2) (3) REMARKS
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER-01 4P 2500A. ACB SET @ 0.85 50 BY DEWA 405.02 404.23 406.72 1215.97 1179.92 36.06 1061.93 0.90 1 2400/5A. CT METER

INCOMER-02 4P 2500A. ACB SET @ 0.85 50 BY GENERATOR SUPPLIER PROVISION FOR MOBILE GENERATOR WITH ELECTRICAL AND MECHANICAL INTERLOCK

OUT GOINGS

DB-SS RYB1 SP 40 50 XLPE/SWA/LSZH 2C-10 1x1C-10 0.4 0.6 0.0 1.0 1.0 0.0 0.9 0.90

SMDB-GF-LL RYB2 TP 125 50 XLPE/SWA/LSZH 4C-50 1x1C-25 12.9 14.7 17.5 45.1 45.1 0.0 40.6 0.90

SMDB-RF RYB3 TP 630 50 XLPE/SWA/LSZH 2x4C-185 2x1C-95 96.5 96.5 95.9 288.9 288.9 0.0 260.0 0.90

SMDB-EXT RYB4 TP 160A 50 XLPE/SWA/LSZH 4C-70 1x1C-35 26.80 26.80 26.40 80.00 80.0 0.0 72.0 0.90

SMDB-RETAIL-1 RYB5 TP 250A 50 XLPE/SWA/LSZH 4C-150 1x1C-95 36.67 36.67 36.67 110.00 110.0 0.0 99.0 0.90

SMDB-RETAIL-2 RYB6 TP 100A 50 XLPE/SWA/LSZH 4C-35 1x1C-25 16.67 16.67 16.67 50.00 50.0 0.0 45.0 0.90

SMDB-RETAIL-3 RYB7 TP 250A 50 XLPE/SWA/LSZH 4C-150 1x1C-95 36.67 36.67 36.67 110.00 110.0 0.0 99.0 0.90

SMDB-B1-LL RYB8 TP 100A 50 XLPE/SWA/LSZH 4C-35 1x1C-25 13.42 12.85 13.28 39.56 32.02 7.5 28.8 0.90

ISOLATOR FOR FIRE PUMP RYB9 TP 500 50 FIRE RATED 2x4C 150 2x1C-70 62.5 62.5 62.5 187.5 187.5 0.0 168.8 0.90 ELS+ALARM

ISOLATOR FOR JOCKEY


RYB10 TP 40 50 FIRE RATED 4C-10 1x1C-10 5.0 5.0 5.0 15.0 15.0 0.0 13.5 0.90 ELS+ALARM
PUMP

EMDB RYB11 TP 630 50 FIRE RATED 2x4C-185 2x1C-95 97.5 95.3 96.1 289.0 260.5 28.5 234.4 0.90

CAPACITOR BANK RYB12 TP 1000 50 XLPE/SWA/LSZH 3x4C-240 3x1C-120 400 kVAR CAPACITOR BANK

MDB Connected to : DEWA


TX-03 TOTAL CONNECTED LOAD / PHASE : 405.02 404.23 406.72 1215.97 1179.92 36.06 0.86 0.90
SMDB Connected to : MDB-03

MAX. DEMAND ( 3 PH) : 1061.93 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ): 1215.97 kW

TOTAL STAND BY LOAD: 36.06 KW TOTAL CONNECTED LOAD WITH OUT STAND BY: 1179.90 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
( 1 Phase ) ( 3 Phase ) ( 3 Phase )

LV-P4-3S-01 Page 30 of 63
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al MEP CONTRACTOR CONSULTANT
Mamzar, Dubai,UAE

D B. NO. : DB-SS LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. NATIONAL ENGINEERING BUREAU LLC

FED FROM : MDB-03 P.O.Box 233237 Dubai – UAE

LOCATION :
LV ROOM
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO

1 R1 10 2.5 2.5 LIGHTING IN TRANSFORMER ROOM 6 60 360


40A SPN ISOLATOR

40 A 4P
100mA 1 2 Y1 SPACE 0
ELCB

3 B1 SPACE 0

4 R2 SPACE 0

40 A 4P
30mA 2 5 Y2 20 4.0 4.0 Power Sockets -Transformer Room 3 200 600
ELCB

6 B2 SPACE 0

TOTAL CONNECTED LOAD: 360 600 0 0.96

Cable size : 1 x 2C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 0.96 kW
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB : SMDB-GF-LL AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : GROUND FLOOR ELECTRICAL ROOM Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 125A 25 XLPE/SWA/LSZH 4C, 50 1C, 25 12.91 14.67 17.52 45.10 40.59 0.00

OUT GOINGS
DB-GF-LL TP 40A 25 XLPE/SWA/LSZH 4C-10 1x1C-10 2.5 2.9 4.2 9.6 8.68
DB-3F-LL TP 40A 25 XLPE/SWA/LSZH 4C-10 1x1C-10 2.9 3.1 3.5 9.6 8.67
DB-7F-LL TP 32A 25 XLPE/SWA/LSZH 4C-10 1x1C-10 1.9 2.3 1.8 6.0 5.41
DB-11F-LL TP 32A 25 XLPE/SWA/LSZH 4C-10 1x1C-10 2.0 2.5 2.1 6.6 5.97
DB-15F-LL TP 40A 25 XLPE/SWA/LSZH 4C-10 1x1C-10 3.6 3.8 5.8 13.2 11.86
DB-GYM TP 40A 25 XLPE/SWA/LSZH 4C-10 1x1C-10 No confirmation

TOTAL CONNECTED LOAD / PHASE 12.91 14.67 17.52 45.10 40.59

MAX. DEMAND ( 3 PH) : 40.59 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 45.10 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 32 of 63
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: GROUND FLOOR

DB No: DB -GF-LL

FED FROM: SMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR & FIRE ESCAPE 10 18 180 LCP

2 Y1 10 2.5 2.5 MAIN ENTRANCE 16 18 288 LCP

40A 4P 3 B1 10 2.5 2.5 RAMP 5 60 300 LCP


100 mA
ELCB 4 R2 10 2.5 2.5 L.V ROOM & GARBAE 7 60 420

ELECTRICAL, MTR, GSM GENRERATOR &


5 Y2 10 2.5 2.5 5 60 300
WATCHMAN ROOM

6 B2 SPACE 0

7 R3 SPACE

8 Y3 10 2.5 2.5 CORRIDOR 1F 9 18 162 LCP

40A 4P 9 B3 10 2.5 2.5 CORRIDOR 2F 9 18 162 LCP


100 mA
ELCB 10 R4 SPACE 0

11 Y4 10 2.5 2.5 LIFT SHAFT 1 (B4 TO 2F) 7 18 126

12 B4 10 2.5 2.5 LIFT SHAFT 2 (B4 TO 2F) 7 18 126

13 R5 10 2.5 2.5 LIFT SHAFT 3 (B4 TO 2F) 7 18 126


40A 4P
100 mA 14 Y5 10 2.5 2.5 LIFT SHAFT 4 (B4 TO 2F) 7 18 126
ELCB
15 B5 10 2.5 2.5 LIFT SHAFT 5 (B4 TO 2F) 7 18 126

16 R6 20 4.0 4.0 LV ROOM 2 95 190


40A 4P
100 mA 17 Y6 20 4.0 4.0 GARBAGE ROOM GF 2 30 60
ELCB
18 B6 20 4.0 4.0 ENTRANCE LOBBY GF 3 95 41 95 231

19 R7 SPACE 0
40A TPN
ISOLATOR 20 Y7 20 4.0 4.0 MTR & ELECTRICAL ROOM GF 2 243 41 284

40A 4P 21 B7 20 4.0 4.0 CORRIDOR 1F 2 95 95 190


100 mA
ELCB 22 R8 20 4.0 4.0 WATCHMAN ROOM & GSM ROOM GF 2 41 214 255

23 Y8 20 4.0 4.0 CORRIDOR 2F 2 95 95 190

24 B8 SPACE 0

25 R9 20 4.0 4.0 IF LV & TRANSFORMER ROOM GF 2 50 100

26 Y9 20 4.0 4.0 IF SECURITY & FIRE ESCAPE GF 2 50 100

40A 4P 27 B9 20 4.0 4.0 IF MTR & GENERATOR GF 2 50 100


30 mA
ELCB 28 R10 20 4.0 4.0 IF GSM & ELECTRIC ROOM GF 2 50 100

29 Y10 20 4.0 4.0 PANTRY 3 200 600

30 B10 20 4.0 4.0 MAIN INTERCOM PANEL 1 500 500

31 R11 20 4.0 4.0 CORRIDOR &STORE 1F 5 200 1000

32 Y11 20 4.0 4.0 IF CORRIDOR 1F 2 50 100

40A 4P 33 B11 20 4.0 4.0 CORRIDOR & STORE 2F 5 200 1000


30 mA
ELCB 34 R12 20 4.0 4.0 IF CORRIDOR 2F 2 50 100

35 Y12 20 4.0 4.0 WATCHMAN ROOM & ELECT. ROOM GF 3 200 600

36 B12 SPACE 0

37 R13 SPACE 0
40A 4P
30 mA 38 Y13 SPACE 0
ELCB
39 B13 20 4.0 4.0 WATER HEATER (WATCHMAN ROOM) 1 1500 1500

TOTAL CONNECTED LOAD: 2471 2936 4235 9.6

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: THIRD FLOOR

DB No: DB -3F-LL

FED FROM: SMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. IN ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR 3F 9 18 162 LCP

2 Y1 10 2.5 2.5 CORRIDOR 4F 9 18 162 LCP

40A 4P 3 B1 10 2.5 2.5 CORRIDOR 5F 9 18 162 LCP


100 mA
ELCB 4 R2 10 2.5 2.5 CORRIDOR 6F 9 18 162 LCP

5 Y2 10 2.5 2.5 LIFT SHAFT 1 (3F TO 10F) 8 18 144

6 B2 10 2.5 2.5 LIFT SHAFT 2 ( (3F TO 10F) 8 18 144

7 R3 10 2.5 2.5 LIFT SHAFT 3 (3F TO 10F) 8 18 144

8 Y3 10 2.5 2.5 LIFT SHAFT 4 (3F TO 10F) 8 18 144

40A 4P 9 B3 10 2.5 2.5 LIFT SHAFT 5 ( (3F TO 10F) 8 18 144


100 mA
ELCB 10 R4 SPACE 0

11 Y4 SPACE 0

12 B4 SPACE 0

13 R5 20 4.0 4.0 CORRIDOR 3F 2 95 95 190

14 Y5 20 4.0 4.0 CORRIDOR 4F 2 95 95 190

40A 4P 15 B5 20 4.0 4.0 CORRIDOR 5F 2 95 95 190


100 mA
ELCB 16 R6 20 4.0 4.0 CORRIDOR 6F 2 95 95 190

40A TPN
17 Y6 SPACE 0
ISOLATOR

18 B6 SPACE 0

19 R7 20 4.0 4.0 IF CORRIDOR 3F 2 50 100

20 Y7 20 4.0 4.0 CORRIDOR &STORE 3F 5 200 1000

40A 4P 21 B7 20 4.0 4.0 CORRIDOR & STORE 4F 5 200 1000


30 mA
ELCB 22 R8 20 4.0 4.0 IF CORRIDOR 4F 2 50 100

23 Y8 20 4.0 4.0 IF CORRIDOR 5F 2 50 100

24 B8 20 4.0 4.0 CORRIDOR &STORE 5F 5 200 1000

25 R9 20 4.0 4.0 CORRIDOR & STORE 6F 5 200 1000

26 Y9 20 4.0 4.0 IF CORRIDOR 6F 2 50 100

40A 4P 27 B9 SPACE 0
30 mA
ELCB 28 R10 SPACE 0

29 Y10 20 4.0 4.0 LCP-3F 1 200 200

30 B10 SPACE 0

31 R11 SPACE 900


40A 4P
30 mA 32 Y11 SPACE 1100
ELCB
33 B11 SPACE 900

TOTAL CONNECTED LOAD: 2948 3140 3540 9.6

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: SEVENTH FLOOR

DB No: DB -7F-LL

FED FROM: SMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. IN ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR 7F 9 18 162 LCP

2 Y1 10 2.5 2.5 CORRIDOR 8F 9 18 162 LCP

40A 4P 3 B1 10 2.5 2.5 CORRIDOR 9F 9 18 162 LCP


100 mA
ELCB 4 R2 10 2.5 2.5 CORRIDOR 10F 9 18 162 LCP

5 Y2 SPACE 0

6 B2 SPACE 0

7 R3 20 4.0 4.0 CORRIDOR 7F 2 95 95 190

8 Y3 SPACE 0

40A 4P 9 B3 20 4.0 4.0 CORRIDOR 8F 2 95 95 190


100 mA
ELCB 10 R4 20 4.0 4.0 CORRIDOR 9F 2 95 95 190

11 Y4 SPACE 0

12 B4 20 4.0 4.0 CORRIDOR 10F 2 95 95 190


40A TPN
ISOLATOR
13 R5 20 4.0 4.0 CORRIDOR & STORE 7F 5 200 1000

14 Y5 20 4.0 4.0 IF CORRIDOR 7F 2 50 100

40A 4P 15 B5 20 4.0 4.0 CORRIDOR & STORE 8F 5 200 1000


30 mA
ELCB 16 R6 20 4.0 4.0 IF CORRIDOR 8F 2 50 100

17 Y6 20 4.0 4.0 CORRIDOR &STORE 9F 5 200 1000

18 B6 20 4.0 4.0 IF CORRIDOR 9F 2 50 100

19 R7 20 4.0 4.0 IF CORRIDOR 10F 2 50 100

20 Y7 20 4.0 4.0 CORRIDOR & STORE 10F 5 200 1000

40A 4P 21 B7 20 4.0 4.0 LCP-7F 1 200 200


30 mA
ELCB 22 R8 SPACE 0

23 Y8 SPACE 0

24 B8 SPACE 0

TOTAL CONNECTED LOAD: 1904 2262 1842 6.0

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: ELEVENTH FLOOR

DB No: DB -11F-LL

FED FROM: SMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR 11F 9 18 162 LCP

2 Y1 10 2.5 2.5 CORRIDOR 12F 9 18 162 LCP

40A 4P 3 B1 10 2.5 2.5 CORRIDOR 13F 9 18 162 LCP


100 mA
ELCB 4 R2 10 2.5 2.5 CORRIDOR 14F 9 18 162 LCP

5 Y2 10 2.5 2.5 LIFT SHAFT 1 (11F TO ROOF) 7 18 126

6 B2 10 2.5 2.5 LIFT SHAFT 2 (11F TO ROOF) 7 18 126

7 R3 10 2.5 2.5 LIFT SHAFT 3 (11F TO ROOF) 7 18 126

8 Y3 10 2.5 2.5 LIFT SHAFT 4 (11F TO ROOF) 7 18 126

40A 4P 9 B3 10 2.5 2.5 LIFT SHAFT 5 (11F TO ROOF) 7 18 126


100 mA
ELCB 10 R4 SPACE 0

11 Y4 SPACE 0

12 B4 SPACE 0

13 R5 20 4.0 4.0 CORRIDOR 11F 2 95 95 190

14 Y5 SPACE 0

40A 4P 15 B5 20 4.0 4.0 CORRIDOR 12F 2 95 95 190


40A TPN
100 mA
ISOLATOR
ELCB 16 R6 20 4.0 4.0 CORRIDOR 13F 2 95 95 190

17 Y6 SPACE 0

18 B6 20 4.0 4.0 CORRIDOR 14F 2 95 95 190

19 R7 20 4.0 4.0 CORRIDOR &STORE 11F 5 200 1000

20 Y7 20 4.0 4.0 IF CORRIDOR 11F 2 50 100

40A 4P 21 B7 20 4.0 4.0 CORRIDOR & STORE 12F 5 200 1000


30 mA
ELCB 22 R8 20 4.0 4.0 IF CORRIDOR 12F 2 50 100

23 Y8 20 4.0 4.0 CORRIDOR &STORE 13F 5 200 1000

24 B8 20 4.0 4.0 IF CORRIDOR 13F 2 50 100

25 R9 20 4.0 4.0 IF CORRIDOR 14F 2 50 100

26 Y9 20 4.0 4.0 CORRIDOR & STORE 14F 5 200 1000

40A 4P 27 B9 20 4.0 4.0 LCP-11F 1 200 200


30 mA
ELCB 28 R10 SPACE 0

29 Y10 SPACE 0

30 B10 SPACE 0

TOTAL CONNECTED LOAD: 2030 2514 2094 6.6

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: FIFTEENTH FLOOR

DB No: DB -15F-LL

FED FROM: SMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR 15F 9 18 162 LCP

2 Y1 10 SPARE 162 162

40A 4P 3 B1 2.5 2.5 STORE & POOL MECHANICAL ROOM 4 60 240


100 mA
ELCB 4 R2 10 SPACE 13 0

5 Y2 10 SPACE 18 14 0

6 B2 10 2.5 2.5 ROOF 6 13 78

7 R3 10 2.5 2.5 ROOF 12 13 156


40A 4P
100 mA 8 Y3 10 2.5 2.5 ROOF 10 13 130
ELCB
9 B3 SPACE 0

10 R4 20 4.0 4.0 CORRIDOR 15F 2 95 95 190


40A 4P
100 mA 11 Y4 20 4.0 4.0 POOL MECHANICAL ROOM 2 237 237 474
ELCB
12 B4 4.0 4.0 STORE 1 237 237

13 R5 20 4.0 4.0 CORRIDOR &STORE 15F 5 200 1000

14 Y5 20 4.0 4.0 LCP-15F 1 200 200

40A 4P 15 B5 20 SPARE 1000 1000


63A TPN
30 mA
ISOLATOR
ELCB 16 R6 SPACE

17 Y6 20 4.0 4.0 IF CORRIDOR 15F 2 50 100

18 B6 20 SPARE 1 1500 1500

19 R7 20 SPARE 50

20 Y7 20 4.0 4.0 EF-01 1 750 750

40A 4P 21 B7 20 4.0 4.0 EF-02 1 750 750


30 mA
ELCB 22 R8 20 SPARE 1 2000 2000

23 Y8 20 SPARE 1 2000 2000

24 B8 20 SPARE 1 2000 2000

25 R9 SPACE

26 Y9 SPACE

40A 4P 27 B9 SPACE
30 mA
ELCB 28 R10 SPACE

29 Y10 SPACE

30 B10 SPACE

TOTAL CONNECTED LOAD: 3558 3816 5805 13.2

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: GYM (ROOF)

DB No: DB-GYM

FED FROM: SMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A
mm² mm² LTG BELL FCU CU W/M D/W R Y B
SO FAN S/O S/O

1 R1 10 2.5 2.5 GYM 9 60 540

40A 4P
100 mA 2 Y1 SPACE 0
ELCB

3 B1 SPACE 0

4 R2 10 2.5 2.5 GYM 2 158 158 316

40A 4P
100 mA 5 Y2 10 2.5 2.5 GYM 2 158 158 316
ELCB

6 B2 10 2.5 2.5 GYM 2 158 158 316

7 R3 20 4.0 4.0 GYM 2 200 400

8 Y3 20 4.0 4.0 GYM 3 200 600

9 B3 20 4.0 4.0 WIFI GYM 1 50 50


40A 4P
40A TPN
30 mA
ISOLATOR
ELCB
10 R4 20 4.0 4.0 LOAD PROVISION 1000

11 Y4 20 4.0 4.0 LOAD PROVISION 1000

12 B4 20 4.0 4.0 LOAD PROVISION 1000

13 R5 20 4.0 4.0 LOAD PROVISION 600

14 Y5 20 4.0 4.0 LOAD PROVISION 500

15 B5 20 4.0 4.0 LOAD PROVISION 1000


40A 4P
30 mA
ELCB
16 R6 SPACE 0

17 Y6 20 4.0 4.0 LOAD PROVISION 600

18 B6 20 4.0 4.0 LOAD PROVISION 500

TOTAL CONNECTED LOAD: 2856 3016 2866 8.7

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
SMDB-RF AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : ROOF Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 630 N/A 25 XLPE/SWA/LSZH 2x4C-150 1x1C-150 96.50 96.50 95.90 288.89 260.00 0.00

OUT GOINGS

SF-FAHU-1A & FAHU-1B TP 40 25 XLPE/SWA/LSZH 4C - 16 1C x 16 6.17 6.17 6.17 18.50 16.65 ELS1

EF-FAHU-1A & FAHU-1B TP 40 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.67 3.67 3.67 11.00 9.90 ELS1

TRW-FAHU-1A & FAHU-1B SP 20 25 XLPE/SWA/LSZH 4C - 4 1C x 4 0.60 0.00 0.00 0.60 0.54

ELS4 + UVR + TIMER +


CP-CU-FAHU-1A & FAHU-1B TP 160 25 XLPE/SWA/LSZH 4C - 70 1C x 35 23.04 23.04 23.04 69.12 62.21
CONTACTOR

SF-FAHU-2A & FAHU-2B TP 40 25 XLPE/SWA/LSZH 4C - 16 1C x 16 6.17 6.17 6.17 18.50 16.65 ELS1

EF-FAHU-2A & FAHU-2B TP 40 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.67 3.67 3.67 11.00 9.90 ELS1

TRW-FAHU-2A & FAHU-2B SP 20 25 XLPE/SWA/LSZH 4C - 4 1C x 4 0.00 0.60 0.00 0.60 0.54

ELS4 + UVR + TIMER +


CP-CU-FAHU-2A & FAHU-2B TP 160 25 XLPE/SWA/LSZH 4C - 70 1C x 35 23.04 23.04 23.04 69.12 62.21
CONTACTOR
ELS1 + UVR + TIMER +
CU-01(ROOF) TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.39 3.39 3.39 10.17 9.15
CONTACTOR
ELS1 + UVR + TIMER +
CU-01(BASEMENT) TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 2.76 2.76 2.76 8.29 7.46
CONTACTOR
ELS1 + UVR + TIMER +
CU-01(GF) TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 2.88 2.88 2.88 8.64 7.78
CONTACTOR
ELS1 + UVR + TIMER +
CU-02(GF) TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.39 3.39 3.39 10.17 9.15
CONTACTOR
ELS1 + UVR + TIMER +
CU-01-CORRIDOR 1F -8F TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.88 3.88 3.88 11.63 10.47
CONTACTOR
ELS1 + UVR + TIMER +
CU-02-CORRIDOR 1F -8F TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.88 3.88 3.88 11.63 10.47
CONTACTOR
ELS1 + UVR + TIMER +
CU-01-CORRIDOR 9F -15F TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.55 3.55 3.55 10.64 9.58
CONTACTOR
ELS1 + UVR + TIMER +
CU-02-CORRIDOR 9F -15F TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 3.55 3.55 3.55 10.64 9.58
CONTACTOR
ELS1 + UVR + TIMER +
CU-STORE & PUMP ROOM TP 32 25 XLPE/SWA/LSZH 4C - 10 1C x 10 2.88 2.88 2.88 8.64 7.78
CONTACTOR

TOTAL CONNECTED LOAD / PHASE 96.50 96.50 95.90 288.89 260.00

MAX. DEMAND ( 3 PH) : 260.00 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 288.89 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 39 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
SMDB-EXT AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : GND Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW
(1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 160A (N/A) 35 XLPE/SWA/LSZH 4C, 70 1C, 35 26.80 26.80 26.40 80.00 72.00 0.00

OUT GOINGS
DB-EXT-01 TP 63A XLPE/SWA/LSZH 4C, 25 1C, 16 13.40 13.40 13.20 40.00 36.00
DB-EXT-02 TP 63A XLPE/SWA/LSZH 4C, 25 1C, 16 13.40 13.40 13.20 40.00 36.00

TOTAL CONNECTED LOAD / PHASE 26.80 26.80 26.40

MAX. DEMAND ( 3 PH) : 72.00 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 80.00 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) 125 - 160A '(4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 40 of 63
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al
Mamzar, Dubai,UAE

D B. NO. : DB-EXT-01 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau

FED FROM : SMDB-EXT

LOCATION :
GND

CONNECTED LOAD LOAD PER CIRCUIT - WATT


CKT CPC
MCB
Rating of Rating of Sec Srl. Ckt. Wire Wire SH EX 13A 13A 15 A
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO

1 R1 10 SPARE 1000 1000

2 Y1 10 SPARE 1000 1000

3 B1 10 SPARE 1000 1000


40 A 4P
100mA 1
ELCB 4 R2 10 SPARE 1000 1000

5 Y2 10 SPARE 1000 1000

6 B2 10 SPARE 1000 1000

7 R3 10 SPARE 1000 1000

8 Y3 10 SPARE 1000 1000

9 B3 10 SPARE 1000 1000


40 A 4P
100mA 2
ELCB 10 R4 10 SPARE 1000 1000

11 Y4 10 SPARE 1000 1000

12 B4 10 SPARE 1000 1000

13 R5 10 SPARE 1000 1000

14 Y5 10 SPARE 1000 1000

40 A 4P 15 B5 10 SPARE 1000 1000


100mA 3
ELCB 16 R6 10 SPARE 1000 1000
80A TPN ISOLATOR

17 Y6 10 SPARE 1000 1000

18 B6 10 SPARE 1000 1000


80A TPN ISOLATOR

19 R7 10 SPARE 1000 1000

20 Y7 10 SPARE 1000 1000

40 A 4P 21 B7 10 SPARE 1000 1000


100mA 4
ELCB 22 R8 10 SPARE 1000 1000

23 Y8 10 SPARE 1000 1000

24 B8 10 SPARE 1000 1000

25 R9 20 SPARE 1500 1500

26 Y9 20 SPARE 1500 1500

40 A 4P 27 B9 20 SPARE 1500 1500


30mA 5
ELCB 28 R10 20 SPARE 1500 1500

29 Y10 20 SPARE 1500 1500

30 B10 20 SPARE 1200 1200

31 R11 20 SPARE 1200 1200

32 Y11 20 SPARE 1200 1200

40 A 4P 33 B11 20 SPARE 1200 1200


30mA 6
ELCB 34 R12 20 SPARE 1200 1200

35 Y12 20 SPARE 1200 1200

36 B12 20 SPARE 1300 1300

TOTAL CONNECTED LOAD: 13400 13400 13200 40.00

Cable size : 1 x 4C 25mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 16mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 40.00 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al
Mamzar, Dubai,UAE

D B. NO. : DB-EXT-02 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau

FED FROM : SMDB-EXT

LOCATION :
GND

CONNECTED LOAD LOAD PER CIRCUIT - WATT


CKT CPC
MCB
Rating of Rating of Sec Srl. Ckt. Wire Wire SH EX 13A 13A 15 A
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO

1 R1 10 SPARE 1000 1000

2 Y1 10 SPARE 1000 1000

3 B1 10 SPARE 1000 1000


40 A 4P
100mA 1
ELCB 4 R2 10 SPARE 1000 1000

5 Y2 10 SPARE 1000 1000

6 B2 10 SPARE 1000 1000

7 R3 10 SPARE 1000 1000

8 Y3 10 SPARE 1000 1000

9 B3 10 SPARE 1000 1000


40 A 4P
100mA 2
ELCB 10 R4 10 SPARE 1000 1000

11 Y4 10 SPARE 1000 1000

12 B4 10 SPARE 1000 1000

13 R5 10 SPARE 1000 1000

14 Y5 10 SPARE 1000 1000

40 A 4P 15 B5 10 SPARE 1000 1000


100mA 3
ELCB 16 R6 10 SPARE 1000 1000
80A TPN ISOLATOR

17 Y6 10 SPARE 1000 1000

18 B6 10 SPARE 1000 1000


80A TPN ISOLATOR

19 R7 10 SPARE 1000 1000

20 Y7 10 SPARE 1000 1000

40 A 4P 21 B7 10 SPARE 1000 1000


100mA 4
ELCB 22 R8 10 SPARE 1000 1000

23 Y8 10 SPARE 1000 1000

24 B8 10 SPARE 1000 1000

25 R9 20 SPARE 1500 1500

26 Y9 20 SPARE 1500 1500

40 A 4P 27 B9 20 SPARE 1500 1500


30mA 5
ELCB 28 R10 20 SPARE 1500 1500

29 Y10 20 SPARE 1500 1500

30 B10 20 SPARE 1200 1200

31 R11 20 SPARE 1200 1200

32 Y11 20 SPARE 1200 1200

40 A 4P 33 B11 20 SPARE 1200 1200


30mA 6
ELCB 34 R12 20 SPARE 1200 1200

35 Y12 20 SPARE 1200 1200

36 B12 20 SPARE 1300 1300

TOTAL CONNECTED LOAD: 13400 13400 13200 40.00

Cable size : 1 x 4C 25mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 16mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 40.00 kW
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
SMDB-RETAIL-1 AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : GND Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW
(1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 250A 25 XLPE/SWA/LSZH 4C, 150 1C, 95 36.67 36.67 36.67 110.00 99.00 0.00

OUT GOINGS

SPARE TP 63A 25 XLPE/SWA/LSZH 8.33 8.33 8.33 25.00 22.50

SPARE TP 63A 25 XLPE/SWA/LSZH 8.33 8.33 8.33 25.00 22.50

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

TOTAL CONNECTED LOAD / PHASE 36.67 36.67 36.67 110.00 99.00

MAX. DEMAND ( 3 PH) : 99.00 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 110.00 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 45 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
SMDB-RETAIL-2 AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : GND Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 100A 25 XLPE/SWA/LSZH 4C, 35 1C, 25 16.67 16.67 16.67 50.00 45.00 0.00

OUT GOINGS

SPARE TP 40A 25 XLPE/SWA/LSZH 3.33 3.33 3.33 10.00 9.00

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

TOTAL CONNECTED LOAD / PHASE 16.67 16.67 16.67 50.00 45.00

MAX. DEMAND ( 3 PH) : 45.00 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 50.00 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 46 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
SMDB-RETAIL-3 AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : GND Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW
(1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 250A 25 XLPE/SWA/LSZH 4C, 150 1C, 95 36.67 36.67 36.67 110.00 99.00 0.00

OUT GOINGS

SPARE TP 63A 25 XLPE/SWA/LSZH 8.33 8.33 8.33 25.00 22.50

SPARE TP 63A 25 XLPE/SWA/LSZH 8.33 8.33 8.33 25.00 22.50

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

SPARE TP 63A 25 XLPE/SWA/LSZH 6.67 6.67 6.67 20.00 18.00

TOTAL CONNECTED LOAD / PHASE 36.67 36.67 36.67 110.00 99.00

MAX. DEMAND ( 3 PH) : 99.00 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 110.00 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 47 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
SMDB-B1-LL AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : BASEMENT -01 Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW
(1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 100A (N/A) 25 XLPE/SWA/LSZH 4C, 35 1C, 25 13.42 12.85 13.28 39.56 29.60 7.50

OUT GOINGS
DB-B1-LL TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 4.99 4.61 5.02 14.62 13.16
DB-B3-LL TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 3.43 3.24 3.27 9.94 8.94
IRRIGATION PUMPS IR-01 & IR-02
TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.00 5.00 5.00 15.00 7.50 7.50 ELS1
(1 DUTY + 1 STANDBY)

SMDB-B1-LL CONNECTED TO:


MDB-02
TOTAL CONNECTED LOAD / PHASE 13.42 12.85 13.28 39.56 29.60

MAX. DEMAND ( 3 PH) : 29.60 kW @ DIVERSITY FACTOR : 0.92 TOTAL CONNECTED LOAD ( 3 PHASE ) 39.56 kW

TOTAL STAND BY LOAD: 7.50 KW TOTAL CONNECTED LOAD WITH OUT STAND BY: 32.06 KW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 48 of 63
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al
Mamzar, Dubai,UAE

D B. NO. : DB-B1-LL LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau

FED FROM : SMDB-B1-LL

LOCATION :
BASEMENT -01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO

1 R1 10 2.5 2.5 DRIVE WAY BASEMENT 1 7 60 420 LCP

2 Y1 10 2.5 2.5 DRIVE WAY BASEMENT 1 5 60 300 LCP

40A 4P 3 B1 10 2.5 2.5 DRIVE WAY BASEMENT 1 7 1 60 18 438 LCP


100 mA 1
ELCB
4 R2 10 2.5 2.5 DRIVE WAY BASEMENT 1 6 60 360 LCP

5 Y2 10 2.5 2.5 DRIVE WAY BASEMENT 2 5 60 300 LCP

6 B2 10 2.5 2.5 DRIVE WAY BASEMENT 2 7 1 60 18 438 LCP

7 R3 10 2.5 2.5 DRIVE WAY BASEMENT 2 6 60 360 LCP

8 Y3 10 2.5 2.5 DRIVE WAY BASEMENT 2 7 60 420 LCP

40A 4P 9 B3 10 SPARE 600 600


100 mA 2
ELCB
10 R4 10 SPARE 600 600

11 Y4 10 SPARE 600 600

12 B4 10 SPARE 500 500


40A TPN ISOLATOR

13 R5 20 4.0 4.0 DRIVE WAY BASEMENT 1 4 200 800

14 Y5 20 4.0 4.0 DRIVE WAY BASEMENT 1 3 200 600

15 B5 20 4.0 4.0 LIFT LOBBY & ELECT. ROOM BASEMENT 1 2 200 400
40A 4P 30
3
mA ELCB
16 R6 20 4.0 4.0 DRIVE WAY BASEMENT 2 4 200 800

17 Y6 20 4.0 4.0 SOCKET FOR B4-FCU-06 - CORRIDOR-B2 1 41 41 CU obsulated

18 B6 20 4.0 4.0 LIFT LOBBY & ELECT. ROOM BASEMENT 2 2 200 400

19 R7 20 4.0 4.0 IF LIFT LOBBY BASEMENT 1 1 50 50

20 Y7 20 4.0 4.0 IF LIFT LOBBY BASEMENT 2 1 50 50

21 B7 20 4.0 4.0 SOCKET FOR B4-FCU-07 - CORRIDOR-B1 1 41 41 CU obsulated


40A 4P 30
4
mA ELCB
22 R8 20 4.0 4.0 DRIVE WAY BASEMENT 2 3 200 600

23 Y8 20 SPARE 1000 1000

24 B8 20 SPARE 1000 1000

25 R9 20 SPARE 1200 1000

40A 4P 30
mA ELCB
5 26 Y9 20 SPARE 1300 1300
40A TPN ISOLATOR

40A 4P 30
5
mA ELCB

27 B9 20 SPARE 1000 1200

TOTAL CONNECTED LOAD: 4990 4611 5017 14.62

Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 14.62 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al
Mamzar, Dubai,UAE

D B. NO. : DB-B1-LL LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau

FED FROM : SMDB-B1-LL

LOCATION :
BASEMENT -03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO

1 R1 10 2.5 2.5 DRIVE WAY BASEMENT 3 7 60 420 LCP

2 Y1 10 2.5 2.5 DRIVE WAY BASEMENT 3 5 60 300 LCP

40A 4P 3 B1 10 2.5 2.5 DRIVE WAY BASEMENT 3 7 1 60 18 438 LCP


100 mA 1
ELCB 4 R2 10 2.5 2.5 DRIVE WAY BASEMENT 3 6 60 360 LCP

5 Y2 10 2.5 2.5 DRIVE WAY BASEMENT 4 10 60 600 LCP

6 B2 10 2.5 2.5 DRIVE WAY BASEMENT 4 6 1 60 18 378 LCP

7 R3 10 2.5 2.5 PUMP ROOM BASEMENT 4 6 60 360


40A 4P
100 mA 2 8 Y3 10 SPARE 500 500
ELCB
9 B3 10 SPARE 500 500

10 R4 10 4.0 4.0 DRIVE WAY BASEMENT 3 4 200 800

11 Y4 10 4.0 4.0 DRIVE WAY BASEMENT 3 3 200 600

40A 4P 30
12 B4 10 4.0 4.0 LIFT LOBBY & ELECT. ROOM BASEMENT 3 2 200 400
3
mA ELCB
13 R5 20 200
40A TPN ISOLATOR

4.0 4.0 DRIVE WAY BASEMENT 4 3 600

14 Y5 20 4.0 4.0 SOCKET FOR B4-FCU-04 - CORRIDOR-B4 1 41 41 CU obsulated

15 B5 20 4.0 4.0 LIFT LOBBY & ELECT. ROOM BASEMENT 4 2 200 400

16 R6 20 4.0 4.0 IF LIFT LOBBY BASEMENT 4 2 50 100

17 Y6 20 4.0 4.0 IF LIFT LOBBY BASEMENT 3 1 50 50

40A 4P 30
18 B6 20 4.0 4.0 SOCKET FOR B4-FCU-01 - Pump Room 1 50 50 CU obsulated
4
mA ELCB
19 R7 20 4.0 4.0 SOCKET FOR B4-FCU-02 - Pump Room 1 50 50 CU obsulated

20 Y7 20 4.0 4.0 SOCKET FOR B4-FCU-03 - Pump Room 1 50 50 CU obsulated

21 B7 SPACE 0

22 R8 20 4.0 4.0 SOCKET FOR B4-FCU-05 - CORRIDOR-B3 1 41 41 CU obsulated

23 Y8 SPACE 0

40A 4P 30
24 B8 20 4.0 4.0 DRIVE WAY BASEMENT 4 3 200 600
5
mA ELCB
25 R9 20 SPARE 500 500

26 Y9 20 SPARE 500 500

27 B9 20 SPARE 500 200

28 R10 20 SPARE 600 200


40A 4P 30
mA ELCB
6 29 Y10 20 SPARE 300 600

30 B10 20 SPARE 200 300

TOTAL CONNECTED LOAD: 3431 3241 3266 9.94

Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 9.94 kW
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
EMDB AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : MDB-03 PLOT 1341040

LOCATION : GROUND FLOOR ELECTRICAL ROOM Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 630A N/A 25 FIRE RATED 2x4C-185 2x1C-95 97.53 95.31 96.12 288.96 260.07 24.75

OUT GOINGS

ESMDB-GF-LL TP 200 25 FIRE RATED 4C-95 1x1C-50 25.8 23.6 24.4 73.8 66.39 3.77

ESMDB-MTR TP 160 25 XLPE/SWA/LSZH 4C-70 1x1C-35 22.0 22.0 22.0 66.0 59.40

ESMDB-B1 TP 200 25 FIRE RATED 4C-95 1x1C-50 27.4 27.4 27.4 82.1 73.89

ESMDB-B4 TP 160 25 FIRE RATED 4C-70 1x1C-35 22.4 22.4 22.4 67.1 60.39 24.75

TOTAL CONNECTED LOAD / PHASE 97.53 95.31 96.12 288.96 260.07 28.52

MAX. DEMAND ( 3 PH) : 260.07 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 288.96 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 52 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
ESMDB-B1 AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : EMDB PLOT 1341040

LOCATION : BASEMENT -01 Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW
(1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 200 N/A 25 FIRE RATED 4C-95 1x1C-50 27.37 27.37 27.37 82.10 73.89 0.00

OUT GOINGS

BEF-01(BASEMENT-1) TP 40 25 FIRE RATED 4C-10 1x1C-10 5.0 5.0 5.0 15.1 13.59 ELS

BEF-02(BASEMENT-2) TP 40 25 FIRE RATED 4C-10 1x1C-10 5.6 5.6 5.6 16.8 15.12 ELS

BSF-01(BASEMENT-2) TP 40 25 FIRE RATED 4C-10 1x1C-10 3.3 3.3 3.3 9.9 8.91 ELS

BSF-02(BASEMENT-2) TP 32 25 FIRE RATED 4C-10 1x1C-10 2.3 2.3 2.3 6.8 6.12 ELS

BEF-03(BASEMENT-3) TP 40 25 FIRE RATED 4C-10 1x1C-10 5.6 5.6 5.6 16.8 15.12 ELS

BSF-03(BASEMENT-3) TP 40 25 FIRE RATED 4C-10 1x1C-10 3.3 3.3 3.3 9.9 8.91 ELS

BSF-04(BASEMENT-3) TP 32 25 FIRE RATED 4C-10 1x1C-10 2.3 2.3 2.3 6.8 6.12 ELS

TOTAL CONNECTED LOAD / PHASE 27.37 27.37 27.37 82.10 73.89

MAX. DEMAND ( 3 PH) : 73.89 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 82.10 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 53 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB : ESMDB-B4 AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : EMDB PLOT 1341040

LOCATION : BASEMENT -04 Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
160
INCOMER TP 25 FIRE RATED 4C-70 1x1C-35 22.37 22.37 22.37 67.10 60.39 24.75
N/A
OUT GOINGS

BEF-04 TP 40 25 FIRE RATED 4C-10 1x1C-10 2.9 2.9 2.9 8.8 7.92 ELS

BSF-05 TP 40 25 FIRE RATED 4C-10 1x1C-10 2.9 2.9 2.9 8.8 7.92 ELS

TRANSFER PUMP(TP-01 & TP-02


DUTY+ STANDBY)
TP 80 25 XLPE/SWA/LSZH 4C-25 1x1C-16 12.5 12.5 12.5 37.5 33.75 18.75 ELS4

SUMP PUMP(SP-01 & SP-02


DUTY+ STANDBY)
TP 20 25 FIRE RATED 4C-4 1x1C-4 1.5 1.5 1.5 4.5 4.05 2.25 ELS

SUMP PUMP(SP-03 & SP-04


DUTY+ STANDBY)
TP 32 25 FIRE RATED 4C-10 1x1C-10 2.5 2.5 2.5 7.5 6.75 3.75 ELS

TOTAL CONNECTED LOAD / PHASE 22.37 22.37 22.37 67.10 60.39 24.75

MAX. DEMAND ( 3 PH) : 60.39 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 67.10 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 54 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
ESMDB-GF-LL AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : EMDB PLOT 1341040

LOCATION : BASEMENT -01 Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 200 N/A 35 FIRE RATED 4C-95 1x1C-50 25.80 23.58 24.39 73.76 66.39 3.77

OUT GOINGS

ISOLATOR FOR GSF-01 TP 32 25 FIRE RATED 4C-10 1x1C-10 2.3 2.3 2.3 6.9 6.21 ELS1

EDB-B3-LL TP 32 25 FIRE RATED 4C-10 1x1C-10 1.2 1.1 0.9 3.2 2.85

EDB-B1-LL TP 32 25 FIRE RATED 4C-10 1x1C-10 1.3 1.2 1.1 3.6 3.27

EDB-GF-LL TP 40 25 FIRE RATED 4C-10 1x1C-10 3.6 4.1 3.7 11.4 10.27

EDB-4F-LL TP 32 25 FIRE RATED 4C-10 1x1C-10 2.8 0.8 1.0 4.6 4.13

EDB-8F-LL TP 32 25 FIRE RATED 4C-10 1x1C-10 0.90 0.76 0.75 2.4 2.17

EDB-12F-LL TP 32 25 FIRE RATED 4C-10 1x1C-10 1.9 1.4 2.8 6.1 5.45

ISOLATOR FOR LIFT-5 TP 63 50 FIRE RATED 4C-16 1x1C-16 4.1 4.1 4.1 12.4 11.16 ELS2

EMCC-R TP 63 50 FIRE RATED 4C-16 1x1C-16 7.7 7.7 7.7 23.2 20.88 3.77

TOTAL CONNECTED LOAD / PHASE 25.80 23.58 24.39 73.76 66.39 3.77

MAX. DEMAND ( 3 PH) : 66.39 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 73.76 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 55 of 63
PROJECT: 4B+G+15 TYP.+ ROOF (COMMERCIAL & RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: ELECTRICAL ROOM AT BASEMENT - 3

DB No: EDB -B3-LL

FED FROM: ESMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 DRIVE WAY BASEMENT 3 9 60 540 LCP

2 Y1 10 2.5 2.5 DRIVE WAY BASEMENT 3 10 3 60 18 654 LCP

40A 4P 3 B1 10 2.5 2.5 DRIVE WAY BASEMENT 4 7 60 420 LCP


100 mA
ELCB 4 R2 10 2.5 2.5 DRIVE WAY BASEMENT 4 7 3 60 18 474 LCP

5 Y2 10 2.5 2.5 PUMP ROOM BASEMENT 4 3 60 180

6 B2 SPACE 0
32A TPN
ISOLATOR
7 R3 20 4.0 4.0 DRIVE WAY BASEMENT 3 CCTV 3 50 150

8 Y3 20 4.0 4.0 DRIVE WAY BASEMENT 3 CCTV 3 50 150

9 B3 20 4.0 4.0 DRIVE WAY BASEMENT 4 CCTV 2 50 100


40A 4P 30
mA ELCB
10 R4 SPACE 0

11 Y4 20 4.0 4.0 DRIVE WAY BASEMENT 4 CCTV 2 50 100

12 B4 20 4.0 4.0 LCP-B3 & ELCP-B3 2 200 400

TOTAL CONNECTED LOAD: 1164 1084 920 3.2

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish wahser

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15 TYP.+ ROOF (COMMERCIAL & RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: ELECTRICAL ROOM AT BASEMENT - 1

DB No: EDB -B1-LL

FED FROM: ESMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 DRIVE WAY BASEMENT 1 9 60 540 LCP

2 Y1 10 2.5 2.5 DRIVE WAY BASEMENT 1 10 3 60 18 654 LCP

40A 4P 3 B1 10 2.5 2.5 DRIVE WAY BASEMENT 2 9 60 540 LCP


100 mA
ELCB 4 R2 10 2.5 2.5 DRIVE WAY BASEMENT 2 10 3 60 18 654 LCP

5 Y2 10 2.5 2.5 ELECTRICAL ROOM (B1 TO B4) 4 60 240

6 B2 SPACE 0
32A TPN
ISOLATOR
7 R3 20 4.0 4.0 DRIVE WAY BASEMENT 1 CCTV 3 50 150

8 Y3 20 4.0 4.0 DRIVE WAY BASEMENT 1 CCTV 3 50 150

9 B3 20 4.0 4.0 DRIVE WAY BASEMENT 2 CCTV 3 50 150


40A 4P 30
mA ELCB
10 R4 SPACE 0

11 Y4 20 4.0 4.0 DRIVE WAY BASEMENT 2 CCTV 3 50 150

12 B4 20 4.0 4.0 LCP-B1 & ELCP-B1 2 200 400

TOTAL CONNECTED LOAD: 1344 1194 1090 3.6

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish wahser

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15 TYP.+ ROOF (COMMERCIAL & RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: ELECTRICAL ROOM AT GROUND FLOOR

DB No: EDB-GF-LL

FED FROM: ESMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 L.V ROOM & GARBAGE 9 60 540

2 Y1 10 2.5 2.5 RAMP 5 60 300 ELCP

40A 4P 3 B1 10 2.5 2.5 MAIN ENTRACE & CORRIDOR 13 18 234 ELCP


100 mA ELECTRICAL, FCC, GSM
ELCB 4 R2 10 2.5 2.5 GENRERATOR & WATCHMAN 7 60 420
ROOM
5 Y2 10 2.5 2.5 STAIR - 1 (B1 TO 3F) 17 18 306

6 B2 10 2.5 2.5 STAIR - 2 (B1 TO 3F) 17 18 306

7 R3 SPACE 0

8 Y3 10 2.5 2.5 CORRIDOR 1F 8 18 144 ELCP

40A 4P 9 B3 10 2.5 2.5 CORRIDOR 2F 8 18 144 ELCP


100 mA
ELCB 10 R4 10 2.5 2.5 CORRIDOR 3F 8 18 144 ELCP

ELECTRICAL,TELECOM, STO, WM,


11 Y4 10 2.5 2.5 3 2 13 60 159
G. CHUTE AT 1F
ELECTRICAL,TELECOM, STO, WM,
12 B4 10 2.5 2.5 3 2 13 60 159
G. CHUTE AT 2F
ELECTRICAL,TELECOM, STO, WM,
13 R5 10 2.5 2.5 3 2 13 60 159
G. CHUTE AT 3F
40A 4P
100 mA 14 Y5 SPACE 0
ELCB
15 B5 SPACE 0

16 R6 20 4.0 4.0 WATCHMAN FARP 500 500

17 Y6 20 4.0 4.0 ISOLATOR FOR CBSP-1 2000 2000

40A 4P 18 B6 20 4.0 4.0 FACP 2000 0


30 mA
ELCB 19 R7 20 4.0 4.0 SECURITY ROOM 4 200 800

40A TPN
20 Y7 20 4.0 4.0 GCC SECURITY 400 400
ISOLATOR

21 B7 20 4.0 4.0 CCTV RACK 1000 1000

22 R8 20 4.0 4.0 DROP ARM BARRIER SYSTEM 500 500

23 Y8 4.0 4.0 Leak Detection Control Panel 500 500

40A 4P 24 B8 20 4.0 4.0 PRINTER 750 750


30 mA
ELCB 25 R9 20 4.0 4.0 CCTV GF 3 50 150

26 Y9 20 4.0 4.0 CCTV GF 2 50 100

27 B9 20 4.0 4.0 ACS PANEL 500 500

28 R10 20 4.0 4.0 CCTV CORRIDOR 1F 2 50 100

29 Y10 20 4.0 4.0 CCTV CORRIDOR 1F 1 50 50

40A 4P 30 B10 20 4.0 4.0 CCTV CORRIDOR 2F 2 50 100


30 mA
ELCB 31 R11 20 4.0 4.0 CCTV CORRIDOR 2F 1 50 50

32 Y11 SPACE 0

33 B11 20 4.0 4.0 LCP-GF & ELCP-GF 2 200 400

34 R12 20 4.0 4.0 CCTV GF 3 50 150

35 Y12 20 4.0 4.0 CCTV GF 2 50 100

40A 4P 36 B12 20 4.0 4.0 CCTV GF 2 50 100


30 mA
ELCB 37 R13 20 4.0 4.0 CCTV CORRIDOR 3F 2 50 100

38 Y13 20 4.0 4.0 CCTV CORRIDOR 3F 1 50 50

39 B13 SPACE 0

TOTAL CONNECTED LOAD: 3613 4109 3693 11.4

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15 TYP.+ ROOF (COMMERCIAL & RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: ELECTRICAL ROOM AT 4TH FLOOR

DB No: EDB-4F-LL

FED FROM: ESMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR 4F 8 18 144 ELCP

2 Y1 10 2.5 2.5 CORRIDOR 5F 8 18 144 ELCP

40A 4P 3 B1 10 2.5 2.5 CORRIDOR 6F 8 18 144 ELCP


100 mA
ELCB 4 R2 10 2.5 2.5 CORRIDOR 7F 8 18 144 ELCP

5 Y2 10 2.5 2.5 STAIR - 1 (4F TO 11F) 16 18 288

6 B2 10 2.5 2.5 STAIR - 2 (4TO 11F) 16 18 288

ELECTRICAL,TELECOM, STO, WM, G.


7 R3 10 2.5 2.5 3 2 13 60 159
CHUTE AT 4F
ELECTRICAL,TELECOM, STO, WM, G.
8 Y3 10 2.5 2.5 3 2 13 60 159
CHUTE AT 5F
ELECTRICAL,TELECOM, STO, WM, G.
40A 4P 9 B3 10 2.5 2.5 3 2 13 60 159
CHUTE AT 6F
100 mA
ELCB ELECTRICAL,TELECOM, STO, WM, G.
10 R4 10 2.5 2.5 3 2 13 60 159
CHUTE AT 7F

11 Y4 SPACE 0

12 B4 SPACE 0
32A TPN
ISOLATOR
13 R5 20 4.0 4.0 CCTV CORRIDOR 4F 1 50 50

14 Y5 20 4.0 4.0 CCTV CORRIDOR 4F 2 50 100

40A 4P 15 B5 20 4.0 4.0 CCTV CORRIDOR 5F 2 50 100


30 mA
ELCB 16 R6 20 4.0 4.0 CCTV CORRIDOR 5F 1 50 50

17 Y6 20 4.0 4.0 CCTV CORRIDOR 6F 1 50 50

18 B6 20 4.0 4.0 CCTV CORRIDOR 6F 2 50 100

19 R7 20 4.0 4.0 CCTV CORRIDOR 7F 1 50 50

20 Y7 20 4.0 4.0 CCTV CORRIDOR 7F 2 50 100

40A 4P 21 B7 20 4.0 4.0 ELCP-4F 1 200 200


30 mA
ELCB 22 R8 20 4.0 4.0 ISOLATOR FOR CBSP-2 2000 2000

23 Y8 SPACE 0

24 B8 SPACE 0

TOTAL CONNECTED LOAD: 2756 841 991 4.6

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15 TYP.+ ROOF (COMMERCIAL & RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: ELECTRICAL ROOM AT 8TH FLOOR

DB No: EDB-8F-LL

FED FROM: ESMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR 8F 8 18 144 ELCP

2 Y1 10 2.5 2.5 CORRIDOR 9F 8 18 144 ELCP

40A 4P 3 B1 10 2.5 2.5 CORRIDOR 10F 8 18 144 ELCP


100 mA
ELCB 4 R2 10 2.5 2.5 CORRIDOR 11F 8 18 144 ELCP

ELECTRICAL,TELECOM, STO, WM,


5 Y2 10 2.5 2.5 3 2 13 60 159
G. CHUTE AT 8F
ELECTRICAL,TELECOM, STO, WM,
6 B2 10 2.5 2.5 3 2 13 60 159
G. CHUTE AT 9F
ELECTRICAL,TELECOM, STO, WM,
7 R3 10 2.5 2.5 3 2 13 60 159
G. CHUTE AT 10F
40A 4P
ELECTRICAL,TELECOM, STO, WM,
100 mA 8 Y3 10 2.5 2.5 3 2 13 60 159
G. CHUTE AT 11F
ELCB
9 B3 SPACE 0

10 R4 20 4.0 4.0 CCTV CORRIDOR 8F 2 50 100

11 Y4 20 4.0 4.0 CCTV CORRIDOR 8F 1 50 50

40A 4P 12 B4 20 4.0 4.0 CCTV CORRIDOR 9F 2 50 100


32A TPN
30 mA
ISOLATOR
ELCB 13 R5 20 2.5 2.5 CCTV CORRIDOR 9F 1 50 50

14 Y5 20 4.0 4.0 CCTV CORRIDOR 10F 2 50 100

15 B5 20 4.0 4.0 CCTV CORRIDOR 10F 1 50 50

16 R6 20 4.0 4.0 CCTV CORRIDOR 11F 2 50 100

17 Y6 20 4.0 4.0 CCTV CORRIDOR 11F 1 50 50

40A 4P 18 B6 20 4.0 4.0 ELCP-8F 1 200 200


30 mA
ELCB 16 R6 20 4.0 4.0 AIR CRAFT WARNING LIGHT 100 100

17 Y6 20 4.0 4.0 AIR CRAFT WARNING LIGHT 100 100

18 B6 20 4.0 4.0 AIR CRAFT WARNING LIGHT 100 100

19 R7 20 4.0 4.0 AIR CRAFT WARNING LIGHT 100 100


40A 4P
30 mA 20 Y7 SPACE 0
ELCB
21 B7 SPACE 0

TOTAL CONNECTED LOAD: 897 762 753 2.4

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15 TYP.+ ROOF (COMMERCIAL & RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: ELECTRICAL ROOM AT 12TH FLOOR

DB No: EDB-12F-LL

FED FROM: ESMDB-GF-LL

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
MCB
RATING OF RATG. SL. CIR WIRE WIRE
RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER OF ELCB No. No. SIZE SIZE
IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 CORRIDOR 12F 8 18 144 ELCP

2 Y1 10 2.5 2.5 CORRIDOR 13F 8 18 144 ELCP

40A 4P 3 B1 10 2.5 2.5 CORRIDOR 14F 8 18 144 ELCP


100 mA
ELCB 4 R2 10 2.5 2.5 CORRIDOR 15F 8 18 144 ELCP

5 Y2 10 2.5 2.5 STAIR - 1 (12F TO ROOF) 12 18 216 ELCP

6 B2 10 2.5 2.5 STAIR - 2 (12F TO ROOF) 12 18 216

ELECTRICAL,TELECOM, STO, WM, G.


7 R3 10 2.5 2.5 3 2 13 60 159
CHUTE AT 12F
ELECTRICAL,TELECOM, STO, WM, G.
8 Y3 10 2.5 2.5 3 2 13 60 159
CHUTE AT 13F
ELECTRICAL,TELECOM, STO, WM, G.
40A 4P 9 B3 10 2.5 2.5 3 2 13 60 159
CHUTE AT 14F
100 mA
ELCB ELECTRICAL,TELECOM, STO, WM, G.
10 R4 10 2.5 2.5 3 2 13 60 159
CHUTE AT 15F

11 Y4 2.5 2.5 ROOF 6 7 3 60 13 18 505

12 B4 2.5 2.5 ROOF 8 13 104


32A TPN
ISOLATOR
13 R5 20 4.0 4.0 CCTV CORRIDOR 12F 2 50 100

14 Y5 20 4.0 4.0 CCTV CORRIDOR 12F 1 50 50

40A 4P 15 B5 20 4.0 4.0 CCTV CORRIDOR 13F 2 50 100


30 mA
ELCB 16 R6 20 4.0 4.0 CCTV CORRIDOR 13F 1 50 50

17 Y6 20 4.0 4.0 CCTV CORRIDOR 14F 2 50 100

18 B6 20 4.0 4.0 CCTV CORRIDOR 14F 1 50 50

19 R7 20 4.0 4.0 CCTV CORRIDOR 15F 2 50 100

20 Y7 20 4.0 4.0 CCTV CORRIDOR 15F 1 50 50

40A 4P 21 B7 SPACE 0
30 mA
ELCB 22 R8 20 4.0 4.0 AIR CRAFT WARNING LIGHT PANEL 1000 1000

23 Y8 20 4.0 4.0 ELCP-12F 1 200 200

24 B8 20 4.0 4.0 ISOLATOR FOR CBSP-3 2000 2000

TOTAL CONNECTED LOAD: 1856 1424 2773 6.1

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2 LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
EMCC-R AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : ESMDB-GF-LL PLOT 1341040

LOCATION : ROOF Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 63 N/A 25 FIRE RATED 4C-16 1x1C-16 7.73 7.73 7.73 23.20 20.88 3.77

OUT GOINGS

LPF-01 SP 20 25 FIRE RATED 3C-4 1x1C-4 0.5 0.5 0.5 1.5 1.35 ELS

SPF-01 TP 20 25 FIRE RATED 3C-4 1x1C-4 1.5 1.5 1.5 4.4 3.96 ELS

SPF-02 TP 20 25 FIRE RATED 3C-4 1x1C-4 1.5 1.5 1.5 4.4 3.96 ELS

SEF-01 TP 20 25 FIRE RATED 3C-4 1x1C-4 0.3 0.3 0.3 0.8 0.72 ELS

LWPF-01 TP 20 25 FIRE RATED 3C-4 1x1C-4 0.3 0.3 0.3 0.8 0.72 ELS

BOOSTER PUMP(2 DUTY + 1


TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 3.8 3.8 3.8 11.3 10.17 3.77 ELS5
STANDBY)

TOTAL CONNECTED LOAD / PHASE 7.73 7.73 7.73 23.20 20.88 3.77

MAX. DEMAND ( 3 PH) : 20.88 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 23.20 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 62 of 63
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB :
ESMDB-MTR AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.

FEED FROM : EDB PLOT 1341040

LOCATION : GND MTR ROOM Dubai – UAE

CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT

INCOMER TP 160 N/A 25 XLPE/SWA/LSZH 4C-70 1x1C-35 22.00 22.00 22.00 66.00 59.40 0.00

OUT GOINGS

ISOLATOR FOR MTR ROOM


TP 32 25 XLPE/SWA/LSZH 4C-10 1x1C-10 2.0 2.0 2.0 6.0 5.40 ELS1
GF
ISOLATOR FOR GSM ROOM
TP 63 25 XLPE/SWA/LSZH 4C-16 1x1C-16 6.7 6.7 6.7 20.0 18.00 ELS1
GF
ISOLATOR FOR GSM ROOM
TP 63 25 XLPE/SWA/LSZH 4C-16 1x1C-16 6.7 6.7 6.7 20.0 18.00 ELS1
10F
ISOLATOR FOR GSM ROOM
TP 63 25 XLPE/SWA/LSZH 4C-17 1x1C-17 6.7 6.7 6.7 20.0 18.00 ELS1
ROOF

TOTAL CONNECTED LOAD / PHASE 22.00 22.00 22.00 66.00 59.40

MAX. DEMAND ( 3 PH) : 59.40 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 66.00 kW

Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A

( 1 Phase ) ( 3 Phase ) ( 3 Phase ) CR/3971/06

LV-P4-3S-01 Page 63 of 63