You are on page 1of 1

1 2 3 4 5 6 7

TMD-ER-104.22
A TYPICAL MOUNTING DETAIL A
MULTIPLE CONNECTION OF METALLIC STRUCTURE TO EARTHING SYSTEM BY EARTHING TERMINAL
NOT DRAWN TO SCALE
METALIC DEVICE/STRUCTURE
B B

1
WELDED CONNECTION

EARTHING LUG
(SEE DETAIL A)
SCREW
ROUND WASHER
NUT
C C
CABLE LUG

EARTHING CONDUCTOR
(INSULATED Cu CABLE)
ANCHOR BOLT

D LOCAL EARTHING TERMINAL (Cu) D


SCREW
ROUND WASHER
NUT

CABLE LUG

E GROUND LEVEL E
PROTECTIVE UPVC PIPE Ø25
FOAM SEALED
EARTHING CONDUCTOR
(INSULATED Cu CABLE)

CONNECTION TO EARTHING SYSTEM


F F
1

CONCRETE FOUNDATION

DETAIL -A- View -1-


METALIC DEVICE/STRUCTURE

METALIC EARTHING LUG


G DEVICE/STRUCTURE G
WELDED CONNECTION SCREW
50

STEEL PLATE ROUND WASHER

OPENING Ø11 NUT


50
H CABLE LUG H
CONCRETE FOUNDATION
300

CABLE HOLDER
200

LOCAL EARTHING TERMINAL (Cu)


I I
EARTHING CONDUCTOR
300

(INSULATED Cu CABLE)

CONCRETE FOUNDATION

PROTECTIVE UPVC PIPE Ø25


J FOAM SEALED J

K K

1) ALL DIMENSIONS ARE IN [mm] UNLESS OTHERWISE SPECIFIED.


L 2) NO DIRECT CONNECTION SHALL BE MADE BETWEEN DISSIMILAR METALS UNLESS PRECAUTIONS AGAINST CORROSION HAVE BEEN TAKEN.
3) BULK MATERIAL DIMENSION (SCREW, NUT, ROUND WASHER, ETC.) SHALL BE ADJUSTED FOR PROPER INSTALLATION OF MAIN EQUIPMENT DIMENSION.
L
1 2 3 4 5 6 A4