Cooling System Page 1 of 1

 
018-018   Cooling System 
 
 

Specifications 
Coolant Capacity  
Engine only High Temperature Water Circuit 181 liters [48 gal]

Low Temperature Aftercooler (LTA) Water Circuit 34 liters [9 gal]

Jacket Water Outlet Temperature 
High Temperature 90°C [194°F] or 95°C [203°F]

Thermostat Modulating Range (Multiple Turbocharger Engine only) 
High Temperature 83° to 95°C [181° to 202°F]

Low Temperature 46° to 57°C [115° to 135°F]

Electronic Temperature Control Valve Modulating Range (Single Turbocharger Engine only) 
High Temperature 87° to 90°C [189° to 194°F]

Low Temperature 37° to 40°C [99° to 104°F]

 
 
NOTE: Use the monthly average dewpoint to determine the maximum power for a given LTA 
return temperature 